AC-400R-3T-TH MANUAL
30
Engineer Setting
Parameter setting
Item
Setting range Initial value
Contents
Type of
humidifier
Electrode
/ Heating
/ Proportion
Electrode
This function set the type of humidifier and operation method.
Electrode : Set when use electrode type humidifier.
Heating : Set when use heating type humidifier.
Proportion : Set when use proportion type.
Cooling
step
OFF/
1 ~ 2 step
/ Proportion
2 step
This function set the cooling operation method when cooling operation.
OFF : Set when prohibit cooling operation.
1 ~ 2 step : Set the cooling operation step.
Proportion : Set when use proportion to the cooling operation.
Heating
step
OFF /
1 ~ 5 step
/ Proportion
5 step
This function set the heating operation method when heating operation.
OFF: Set when prohibit heating operation.
1 ~ 5 step : Set the heating operation step.
Proportion : Set when use proportion to the heating operation.
Humidi-
fication
step
OFF/
1 ~ 2 step
/ Proportion
1 step
This function set the humidifying operation method when humidifying operation.
OFF : Set when prohibit humidifying operation.
1 ~ 2 step : Set the humidifying operation step. (When using the electrode
type humidifier, the maximum output is 1step.)
Proportion : Set when use humidifying operation to proportion. (It is not applied
when using the electrode humidifier.)
Dehumid
ification
step
OFF /
1 ~ 2 step
/ Proportion
2 step
This function set the dehumidifying operation when dehumidifying operation.
OFF : Set when prohibit dehumidifying operation.
1 ~ 2 step : Set dehumidifying operation step.
Proportion : Set when use dehumidifying operation to proportion.
Alarm Contents
Alarm setting explanation
Status
Occur cause
Controller operating status at alarm
Remote sensing
Sensing time :
5 sec / Input
contact : A contact
/ Auto return
It occurs when the controller is not
detected or detected according to the
input contact set value for the detection
time on the remote sensing input(DI2) at
the time of operation or stop.
The controller is operated or stopped by the
remote contact only while the controller is
running, and the controller can not be started
from the monitor when the remote is detected
in the stop state.
Halon sensing
Sensing time :
0.5 sec / Input
contact : Selectable
/ Manual return
It occurs when the controller is not detected
or detected according to the input contact
set value for the detection time on the halon
sensing input(DI2) at the time of operation or
stop.
All operation status is stopped when halon is
detected. Even if halon detection is canceled,
user must set the controller directly to ON to
operate normally.
Halon detection is not released, it remains stopped.
Blower check
Sensing time :
10 sec / Input
contact : A contact
/ Auto return
After COMP output(DO3,5) when occurs
alarm when not detected in the blowing
alarm(DI3) status input for 10 seconds.
When an alarm occurs, not only all the outputs
but also the blower outputs are turned OFF.
When the alarm returns, the alarm is canceled
and the controller operates normally.
Comp 1~2 check
Sensing time :
Selectable / Input
contact : B contact
/ Manual return
After COMP output(DO3,5) when occurs
when detected or not detected according
to the input contact set value in COMP
Alarm(DI4,5) status input during alarm
sensing time.
When an alarm occurs, only the corresponding
compressor output for which an alarm has
occurred is stopped, and the operation is
switched to the operation standby unit. And the
other operation of the controller operates
normally.