Figure 2.  Feed Pairs into Termination Manager 

“T” designates top
surface

Orange pair

Brown pair

Blue pair

Green pair

 

Figure 3.  Fold Pairs Back into Slots 

Blue on top

White on top

Orange on top

 

Termination Manager Instructions 

 

 

The  termination  managers  provide  pair  positioning, 
control,  and  strain  relief  features  to  the  rear 
termination  area  of  the  panel.  See  Figure  1.  
Instructions  for  using  the  termination  manager  are 
listed below. 

Feed Pairs into Termination Manager (Figure 2) 

1.  Trim  jacket  back  at  least  3  inches  (76mm)  to 

expose twisted pairs. 

2.  Without rearrangement out of the jacket, position 

pairs in-line per pair colors below: 

T568B Wiring Application (Shown) 

Blue, Brown, Orange, Green 

T568A Wiring Application 

Blue, Brown, Green, Orange 

3.  Insert held pairs through holes on top surface of 

termination  manager,  two  pairs  per  hole  as 
shown. (The TOP surface is identified with a “T”, 
which  can  be  oriented 

either

  right  side  up  or 

upside down). 

4.  Continue  to  feed  pairs  through  termination 

manager  until  resistance  is  encountered  at  the 
jacket. This will usually be about 1/4 inch (6mm) 
from the jacket. 

 

Fold Pairs Back into Slots (Figure 3) 

5.  Fold  each  pair  over  into  adjoining  slots  on  bottom 

end  of  termination  manager.  To  ease  item  8,  it  is 
recommended  that  conductor  colors  be  viewed  in  the  slots 
as listed below: 

T568B Wiring Application (Shown)  

 

BL/OR Pairs 

– Blue/Orange conductors on top 

BR/GR Pairs 

– both white conductors on top 

T568A Wiring Application 

BL/GR Pairs 

– Blue/Green conductors on top 

BR/OR Pairs 

– both white conductors on top 

6.  Ensure  that  pairs  are  in  slots  completely  without  being 

pinched  over  bottom  end  surface. 

It  may  be  necessary  to 

add twist to align pairs with slots.

 

 

Figure 1. Termination Manager 

Summary of Contents for PATCHMAX GS3

Page 1: ...termination manager 760062364 PM GS3 48 w Termination Mgt PATCHMAX GS3 Cat 6 U UTP copper patch panel 48 port equipped with termination manager 760001669 PM GS3 2U PATCHMAX GS3 24 port panel kit witho...

Page 2: ...anagers 1 2 1 2 Label sheet White 4 labels per sheet 1 2 1 2 Label sheet Blue 4 labels per sheet 4 8 4 8 Hook and loop straps 4 4 4 4 Mounting screws 1 1 1 1 Instruction sheet Specifications Wire Term...

Page 3: ...ons When using this product the following basic safety precautions should be followed to reduce the risk of fire electric shock and injury to persons 1 Never install communications wiring in wet locat...

Page 4: ...2 Populate Panel with Distribution Modules For Panel Kits Only Note Distribution modules are ordered separately 1 From the front side of the panel insert the module into the desired panel opening 2 R...

Page 5: ...spond to items listed on next page Release snap Rotate and remove module Insert module posts into slots Route cables through panel opening Replace module Terminate cables Attach retainer bar Attach re...

Page 6: ...tools Correct procedure for using the termination manager is provided in the next section of this instruction 6 Unsnap module rotate and replace into original panel opening 7 Attach rear retainer bar...

Page 7: ...Green Orange 3 Insert held pairs through holes on top surface of termination manager two pairs per hole as shown The TOP surface is identified with a T which can be oriented either right side up or u...

Page 8: ...Using the D 914 punch tool with M110 blade punch down conductors making sure the tool is straight and that conductors fully engage in the IDC terminals Stagger the punch down tool up and down so that...

Reviews: