Instruction Sheet
Page 7 of 8
Figure 2. Feed Pairs into Termination Manager
“T” designates top
surface
Orange pair
Brown pair
Blue pair
Green pair
Figure 3. Fold Pairs Back into Slots
Blue on top
White on top
Orange on top
1
Termination Manager Instructions
The termination managers provide pair positioning,
control, and strain relief features to the rear
termination area of the panel. See Figure 1.
Instructions for using the termination manager are
listed below.
Feed Pairs into Termination Manager (Figure 2)
1. Trim jacket back at least 3 inches (76mm) to
expose twisted pairs.
2. Without rearrangement out of the jacket, position
pairs in-line per pair colors below:
T568B Wiring Application (Shown)
Blue, Brown, Orange, Green
T568A Wiring Application
Blue, Brown, Green, Orange
3. Insert held pairs through holes on top surface of
termination manager, two pairs per hole as
shown. (The TOP surface is identified with a “T”,
which can be oriented
either
right side up or
upside down).
4. Continue to feed pairs through termination
manager until resistance is encountered at the
jacket. This will usually be about 1/4 inch (6mm)
from the jacket.
Fold Pairs Back into Slots (Figure 3)
5. Fold each pair over into adjoining slots on bottom
end of termination manager. To ease item 8, it is
recommended that conductor colors be viewed in the slots
as listed below:
T568B Wiring Application (Shown)
BL/OR Pairs
– Blue/Orange conductors on top
BR/GR Pairs
– both white conductors on top
T568A Wiring Application
BL/GR Pairs
– Blue/Green conductors on top
BR/OR Pairs
– both white conductors on top
6. Ensure that pairs are in slots completely without being
pinched over bottom end surface.
It may be necessary to
add twist to align pairs with slots.
Figure 1. Termination Manager