8.0  FAILURES IN OPERATION  

 

Consider point 4.2. for all inspections. 

Possible failures and repair: 

 

• 

Fan is not running 

Check power supply and motor protection. If ok, check motor. If motor with two separate 
windings, check both speeds. Have the motor repaired if necessary.  

• 

Air volume too low  

Check direction of rotation. If incorrect, change the motor poles. If ok, check working 
point and system configuration.  

• 

Motor protection is tripping    

Compare motor data. If ok, check power supply and motor (short circuit, damaged 
bearings, impeller blocked or touching other parts). 
Have the motor or eventually the whole fan repaired.  

     

Excessive noise 

Check if bearings are damaged, impeller is blocked or touching other parts. Have the 
motor or eventually the whole fan repaired

    

 Vibrations 

Check working point and system configuration. Should the real system pressure drop be 
higher than intended, some fan types might work in the instable area of the fan curve. 
Contact the service department of the manufacturer.  
Damages or dust on the impeller. Clean it, eventually it has to be rebalanced or 
exchanged.  
 

 
In case of doubt always contact the service department of the manufacturer. After a fire the 
fan has to be inspected by the manufacturer.  

 
 
9.0  WARRANTY  
 

Warranty is only valid when transport, storage, mounting, connection and periodic controls, 
have been carried out in accordance with the above mentioned instructions and in 
accordance with valid regulations for electrical installations and fire protection. In order to 
proof that the warranty is valid, the operator has to present the duly filled in and signed 
acceptance and maintenance report. 
 

 

 

We point out that it is very important to do the installation carefully. Only then 
an undisturbed and safe operation can be guaranteed. 
 

 
 

Encls: 

• 

Warranty 

• 

reports 

• 

manufacturers declaration 

 
 
 

Summary of Contents for WVA

Page 1: ...0 F200 F300 F400 F600 in accordance with EN 12101 3 600 C 120 Min Type WVA F400 and WVI F400 F200 F300 F400 in accordance with EN 12101 3 400 C 120 Min Approval no 99 2121 2 3 TU Munich and appendix of 24 04 2001 Systemair GmbH Seehöfer Str 45 97944 Boxberg Windischbuch Tel 49 0 79 30 92 72 0 Fax 49 0 79 30 92 72 92 info systemair de www systemair de ...

Page 2: ...NTING INSTRUCTION 4 4 1 Test before mounting 4 4 2 Safety instructions for mounting initial operation maintenance and control 4 4 3 Mounting of the fan 4 4 4 Installation instructions 5 5 0 INITIAL OPERATION 6 6 0 SITE APPROVAL 7 7 0 MAINTENANCE AND CONTROL 7 8 0 FAILURES IN OPERATION 8 9 0 WARRANTY 8 Enclosures Warranty Control sheet Manufacturers declaration ...

Page 3: ...n be dangerous for human beings and equipment This risk is completely in the hands of the operator 2 0 TECHNICAL DESCRIPTION Casing The casing is manufactured from steel and has lacquer as a finish Impeller The impeller of type WVI WVA F600 is manufactured from stainless steel of type WVI WVA F400 from galvanized steel The impeller is directly connected with the motor shaft by a hub and secured sc...

Page 4: ... protected in a way that unauthorized people do not have access Any risk to touch the impeller without the intention to do so during above mentioned work has to be excluded switch off the fan and secure against re start Only when this risk is excluded and only when necessary protection guards already mounted to the fan on arrival either at the inlet or outlet may be removed All general rules regar...

Page 5: ...ature time classification When mounted outside the inlet flange and the cooling duct have to be secured with bird screen and weather protection Fans of type WVA have to be installed outside the fire zone those fans are approved only for installation outside on external wall Place the fan on two steel mounting brackets fixed securely to the external wall Connect the fan at the upper side with a smo...

Page 6: ...gram is attached to the documentation Another wiring diagram is fixed to the lid of the terminal box Electrical data are attached to these instructions and can also be found on the name plate of the fan at the fan casing As the motors are supplied without thermal protection motor protection devices have to be provided at site Should a frequency inverter be used for daily ventilation purposes the m...

Page 7: ...rew between motor shaft and hub is fixed tightly and if necessary re fix 3 Verify if the fan impeller is dirty and if necessary clean it 4 Verify the function of all parts relevant for safety 5 Verify the function of the control system 6 Measure the resistance in the windings 7 Measure the operating current 8 Check for eventual vibrations 9 Check if there is excessive noise in the motor bearings T...

Page 8: ...int and system configuration Should the real system pressure drop be higher than intended some fan types might work in the instable area of the fan curve Contact the service department of the manufacturer Damages or dust on the impeller Clean it eventually it has to be rebalanced or exchanged In case of doubt always contact the service department of the manufacturer After a fire the fan has to be ...

Page 9: ...iner Aussenwand Kabeleintritt Ansaug Ausblas Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug zugelassener elastischer Anschluss rund oder rechteckig ORVN Ansaug aus einem Kanal an einer Aussenwand ORVN Ansaug aus einem Kanal an einer Aussenwand Kabeleintritt Kuehlluft Brandraum Ausblas Ansaug zugelassener elastischer Anschluss rund oder rechteckig WVI Ansaug aus einem Kanal an einer Außenwand WVI...

Page 10: ... Kuehlluft Brandraum Ausblas Ansaug Bodenaufstellung ORVN U oder I Profil 80 freie Laenge max 1000 mm zert elastischer Stutzen Wandaufhaengung ORVZ Ausblas U oder I Profil 80 Ansaug wahlweise nur 1 zert Brandraum elastischer Stutzen Wandaufhaengung ORVN Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug U oder I Profil 80 zert elastischer Stutzen Bodenaufstellung WVI Deckenaufhängung WVI Wandaufhäng...

Reviews: