_________________________________________________________________________________________________________
VR 300 ECV/B
Installation description
206552 (12-12-2012)
15
Systemair
AB
Before starting the system
1. Choose required airflow at normal and min. fan speed as follows:
Set the normal and min. fan speed of the ventilation unit from potentiometers in the back of the
speed regulator (
fig. 12
) or cooker hood (see
instructions for cooker hood). The potentiometers are
set by using a screw driver. Turning the potentiometer results in different control voltages to the
fans (see
table 1
). To get an idea of the airflow corresponding to each voltage output see
fig. 15
showing a fan performance diagram displaying performance curves for supply air and extract air.
Speed setting Voltage range
Min. speed
3-7 V
Norm. speed
5-9 V
Table 1
0
10
20
30
40
50
60
70
0
100
200
300
400
500
600
700
80
90
Q (l/s)
3V
4V
6V
10V
1
2
1
Fan performance curve extract air
2
Fan performance curve supply air
Fig.
15
2. Adjust diffusers and air valves in accordance with commissioning or basic setting (see “Diffusers/air
valves”). Make sure that sector shutter in the inlet diffusers are set so that the air stream is not led
towards obstructions like visible joist, wall etc.
3. Choose desired supply air temperature, (see User and maintenance instructions; “Operation”).
Additional accessories
For more information about silencers,
diffusers/air valves, roof units, wall grilles etc. see technical
catalogue and installation respective instructions.
Summary of Contents for VR 300 ECV/B
Page 1: ...A001 VR 300 ECV B 1000W 500W Air Handling Unit Installation description GB GB...
Page 2: ......
Page 17: ...A001 VR 300 ECV B 1000W 500W Luftbehandlingsaggregat Installationsbeskrivning GB SE...
Page 31: ...A001 VR 300 ECV B 1000W 500W Ventilasjonsaggregat Montasjeanvisning GB NO...
Page 44: ...Rett til endringer forbeholdes Produsent www systemair no...
Page 45: ...A001 VR 300 ECV B 1000W 500W L ftungsger t Installationsanweisung GB DE...
Page 58: ...A001 RU VR 300 ECV B 1000 500 GB RU...
Page 59: ...RU...