Topvex SX03, SX04, SX06 

 

Installation description 

 
205871  

 

Systemair AB 

9

Condensation/heat insulation. 

Outdoor air duct and discharge ducts must always be well insulated against condensation. Correct 
insulation installation on ducts connected to the unit is especially important. All ducting installed in cold 
rooms/areas must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic 
diffusion barrier. In areas with extremely low outdoor temperatures during the winter, additional insulation 
must be installed. Total insulation thickness must be at least 150 mm.  
 

NOTE! If the unit is installed in a cold place make sure that all joints are covered with insulation, 
and tape well. 

Electrical connection 

The unit must not be put into operation before all the electrical safety precautions have been read and 
understood. See 

fig. 3 

where to find the electrical connection box. See page 10 and 11 and the enclosed 

wiring diagram where to connect the electrical cables. 
 

Mains supply/Model  

 

Model 

230V 1~ 

400V 3N~ 

230V 3~ 

Remark 

Topvex SX 03 EL 

 

X X 

Heater can be reconnected to 230V 3~ 

Topvex SX 03 HW 

 

 

 

Topvex SX 04 HW 

X

 

 

 

 

Topvex SX 04 EL 

 

X X 

Heater can be reconnected to 230V 3~ 

Topvex SX 06 HW 

 

X X 

 

Topvex SX 06 EL 

 

X X 

Heater can be reconnected to 230V 3~ 

The units are designed for continuous operation and permanent connection to the mains.  
 

 

Power consumption/Model    

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

Model Fans 

(W 

tot.

El Heating battery 

Fuse (mains) 

Topvex SX 03 EL 400V 3N~ 

992 

6 kW 

3x16 A 

Topvex SX 03 HW 230V 1~ 

992 

------- 

13 A 

Topvex SX 04 EL 400V 3N~ 

1520 

12 kW 

3x32 A 

Topvex SX 04 HW 230V 1~ 

1520 

------- 

13 A 

Topvex SX 06 EL 400V 3N~ 

2104 

16 kW 

3x32 A 

Topvex SX 06 HW 400V 3N~ 

2104 

------- 

3x10 A 

Topvex SX 04 EL 230V 3~ 

1520 

12 kW 

3x40 A 

Topvex SX 06 EL 230V 3~ 

2104 

16 kW 

3x63 A 

Topvex SX 06 HW 230V 3~ 

2104 

------- 

3x13 A 

Summary of Contents for Topvex SX03 EL

Page 1: ...Corrigo ver no 1 2 1 00 Topvex SX03 SX04 SX06 Compact Air Handling Unit Installation description GB GB...

Page 2: ...f machinery Basic concepts general principles for design Part 1 Basic terminology methodology EN ISO 12100 2 Safety of machinery Basic concepts general principles for design Part 2 Technical principle...

Page 3: ...ments Table of contents Declaration of Conformity 2 Introduction 3 Table of contents 3 Dimensions and weight 4 Topvex SX03 4 Topvex SX04 SX06 5 Component description Topvex SX 6 Transport and storage...

Page 4: ..._______________________________________________________________ Topvex SX03 SX04 SX06 Installation description Original 205871 4 Systemair AB Dimensions and weight 62 375 470 106 1320 750 1600 43 43 1...

Page 5: ...4 mm Topvex SX06 mm A 800 800 B 500 600 C 250 300 D 187 180 E 167 167 F 150 100 G 1041 1127 H 171 164 I 183 183 J 30 30 K 1747 2000 L 520 520 X 355 410 Y 212 204 Z 106 106 Topvex SX04 SX06 Topvex SX04...

Page 6: ...9 10 11 12 3 4 5 6 11 10 8 13 Fig 3 Model M N mm Topvex SX03 500 630 Topvex SX04 500 698 Topvex SX06 550 824 Description 1 Connection supply air 2 Connection extract air 3 Connection outdoor air 4 Con...

Page 7: ...into operation Fig 4 Place the unit preferably in a separate room e g storage room laundry room attic or similar The electronic components should not be exposed to lower temperature than 0 C or highe...

Page 8: ...stalled in a non heated place the drain pipe and trap needs to be insulated well to prevent the water from freezing L 32 mm Fig 5 Fig 6 H mm Max negative pressure Pa 85 500 110 750 135 1000 Table 1 No...

Page 9: ...t must not be put into operation before all the electrical safety precautions have been read and understood See fig 3 where to find the electrical connection box See page 10 and 11 and the enclosed wi...

Page 10: ...reference 10 DO5 Alarm output for all alarms 24V AC Max 2 0 A continuous load 11 AI Ref Sensor supply air reference 12 AI 1 Sensor supply air These inputs may only be wired to voltage free contacts To...

Page 11: ...he unit from factory The supply air sensor is enclosed in the package upon delivery Timer extended forced running When the unit is in shut down mode or running on low or medium speed it can be forced...

Page 12: ...or B alarm Function sketch Accessories dashed components Designation Component description DO Damper outdoor air DEH Damper exhaust air WCB Water cooling battery WVA Water valve actuator Fig 7 The im...

Page 13: ...et in the control panel The electric heating coil has both automatic and manual overheating protection The manual overheating protection which is controlled by the emergency thermostat is reset by pre...

Page 14: ...mary circuit Fig 9 Control panel The SCP control panel is delivered with a 10m cable that is pre connected to the panel and with a fast coupling ISDN contact pre connected to the Topvex unit The ISDN...

Page 15: ...n is at the root of the menu tree Pressing DOWN will move you through the menu choices at this the lowest level UP will move you back through the choices To enter a higher menu level use UP or DOWN to...

Page 16: ...he right to make changes and improvements to the contents of this manual without prior notice Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www sy...

Reviews: