Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
DI
Status of the Digital inputs.
→
UI
Status of Universal Analogue inputs
or Universal Digital inputs.
→
AO
Status of the Analogue outputs.
→
DO
Status of the Digital outputs.
→
Temperature
Outd temp: ºC
Supply air temp
Act.: ºC
→
Setp: 18ºC
Supply air temp. 18°
C
Neutral zone 0.0 °C
Actual outdoor air temperature.
Actual supply air temperature.
Choose setpoint value.
A neutral zone can be set around
the setpoint value.
Note:
See Corrigo manual-
Ventilation application for
more information.
Frost protection
Actual: ºC
Actual water temperature in the
water heating battery.
(Only visible
for HW units).
→
Air Control
Frequency control
manual SAF
Output: %
Frequency control manual.
Fans controlled by setting fixed
output signal.
This menu option becomes visible
if the unit is configured for
"Manual frequency”.
Frequency control
manual SAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp.
output.
–20°C = 0 %
0°C = 0 %
Act. Comp: 0 %
Pressure control
SAF
Actual: Pa
Setp.: Pa
The actual external pressure and set
point for the supply air fan.
Only visible if the unit is configured
for "Pressure control" (VAV
accessory).
Pressure control
SAF
Setp 1/1: 500 Pa
Setp 1/2: 250 Pa
Set the external pressure set point
for normal speed (1/1) and reduced
speed (1/2) for the supply air fan.
Outdoor comp.Setp.
1
—20°C = 0 Pa
10°C = 0 Pa
Act. Comp: 0 Pa
Set the SAF pressure compensation
for the settable outdoor
temperature. The outdoor
compensation is linear and is set
using two parameter pairs which
give the value of the compensation
at two different outdoor
temperatures. The compensation
can be positive or negative.
Shows the actual pressure
compensation.