Display shows
Description
Reset filter alarm
by setting the Reset alarm to Yes.
Filter alarm
Set
the time until the filter alarm should be activated, 1-15 month.
Set
the status for
Cooling
to Active or Not Active. Preset is: Not Active.
Function: Controls a cold-water cooling battery with a 0-10 V DC signal.
Functions
Set
the status for
Fire function
to Active or Not Active. Preset is: Not
Active.
Set
how the unit should operate if the fire alarm function is activated, run
on High fan-speed or Shut off. Preset is: Shut off.
Function: Decides how the unit should operate at fire alarm.
Applies only to HW units.
Set
the status for
Frost protection
to Active or Not Active. Preset is: Not
Active.
Set
the alarm limit,
°
C, on the supply air temperature.
Function: When supply air temperature decreases, below the set alarm
limit, the fans stops, the hot water valve actuator opens fully and the
Fresh/Exhaust air dampers (accessory) close.
Set
the status for
Cool Recycling
to Active or Not Active. Preset is: Not
Active.
Function: Starts the heat exchanger, to recycling the cold extract air
temperature, when the extract temperature is 3K lower than the Fresh air
temperature.