Control unit, manual
Man / Auto:
Fanspeed:
Show
if the unit is running in Manual or Automatic mode.
Show
if the fans are running on Low, Medium or High speed or if the unit
is stopped.
Extended running
Activate
extended running. Extended running is the time the unit goes
from OFF (Low fan-speed or shut down mode) to ON (High, Medium or
Low fan-speed). OFF and ON times and fan-speeds are set at the
submenu
Week program.
Control temp.
Set
the desired control temperature value, 16-30
°
C.
Running mode
Set
the running mode of the unit. Choose between:
Auto, Manual high, Manual medium, Manual low or Manual shut off.
Service
Login with 1111 to service level. Log’s out after 5 minutes of inactivity,
with main supply on.
Time / Date
Set
the present time, date and weekday.
Set
the units ON time for each week day, 2 periods/ day.
Preset time is Period 1. 07:00-16:00 Monday-Sunday and Period 2.
00:00-00:00 Monday-Sunday, 00:00-00:00
inactivates
the period.
Week program
Set
the fan-speed when the unit is ON to Low, Medium or High and the
fan-speed when the unit is OFF to Low or shut off.
Preset is: ON = Medium and OFF = Low.
Extended running
Set
how many minutes (0-240) the unit should go from OFF (low fan-
speed or shut down mode) to ON (Low, Medium or High fan-speed).
ON times and fan-speeds are set at submenu
Week program.
Activating extended running can be done by pressing the OK button in
sub menu
Extended running
(user level) or by using an
external
Timer
or a Push button
. Set the minutes to 0 when using a
Timer
.
Display shows