5. REMARKS TO ROOM SENSORS

Location and Accuracy of Room Sensors

The room sensor should be mounted in a suitable location for measuring accurate room temperature. The 

accuracy of the temperature measurement also depends directly on the temperature dynamics of the wall. 

It is important, that the back plate is completely flush to the wall so that there is sufficient circulation of 

air through the vents in the cover, otherwise, deviations in temperature measurement will occur due to 

uncontrolled air circulation. The temperature sensor should not be covered by furniture or other objects. 

Mounting next to doors (due to draught) or windows (due to colder outside wall) should be avoided.

6. SURFACE AND FLUSH MOUNTING

The measuring result is influenced by the thermal characteristics of the wall. A solid concrete wall responds 

to thermal fluctuations within a room in a much slower than a light-weight structure wall. Room temperature 

sensors installed in flush-mounted boxes have a longer response time to thermal variations. In extreme 

cases they detect the radiant heat of the wall even if the air temperature in the room is lower for example.

7. DIMENSIONS

Dimensions in mm

8. MOUNTING

1. 

Make sure the power is disconnected

2. 

Insert the screwdriver in the plastic teeth of thermostat; 

clockwise rotation of the screwdriver will separate front 

cover from base plate. Please follow the wiring diagram 

to connect the wires.

3. 

Fix the thermostat base plate to the wall through the 

four screw holes with distance between axes of 60 mm.

4. 

Fasten base plate and front cover. Do not press the panel 

in order to protect LCD.

Summary of Contents for TControl EASY 3S

Page 1: ...Controller for Fan Coil Units Installation and maintenance manual TControl EASY 3S...

Page 2: ......

Page 3: ...INSTALLATION INSTRUCTION NOTICE D INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE INSTRUCCIONES DE INSTALACI N English Fran ais Espa ol Deutsch Italiano...

Page 4: ...IBILITY AND RESIDUAL RISKS 4 4 SECURITY ADVICE CAUTION 4 5 REMARKS TO ROOM SENSORS 5 6 SURFACE AND FLUSH MOUNTING 5 7 DIMENSIONS 5 8 MOUNTING 5 9 MAINTENANCE INSTRUCTIONS 6 10 TERMINAL CONNECTION PLAN...

Page 5: ...EC fan motor if there is an ECOSPEED card 2 TECHNICAL DATA Measuring values temperature Output switch contact 5x contact NO 2x heating cooling 3x fan stages 250 V max load 3 A fan stages switchover p...

Page 6: ...ion with any equipment that in case of a failure may threaten directly or indirectly human health or life or result in danger to human beings animals or assets Ensure all power is disconnected before...

Page 7: ...E AND FLUSH MOUNTING The measuring result is influenced by the thermal characteristics of the wall A solid concrete wall responds to thermal fluctuations within a room in a much slower than a light we...

Page 8: ...lation Heating On off key Mode key Fan speed key Valve open Fahrenheit Setting parameter Celsius 6 TControl EASY 3S 9 MAINTENANCE INSTRUCTIONS It is recommended to clean the touch surface with a damp...

Page 9: ...ck on off 2 lock Mode 3 lock fan speed 4 lock temp setting 5 lock all the keystrokes 0 3 not used 4 Temp upper limit Range 1 50 C 30 C 5 Temp lower limit Range 1 50 C 16 C 6 LCD backlight 0 without ba...

Page 10: ...tcheover pause 0 5 s 13 HANDLING By pressing or button the room temperature set point can be adjusted between 16 30 C 60 86 F See also parameter 4 and 5 If an external temperature sensor is used in 2...

Page 11: ......

Page 12: ...T CONTROL EASY 01 N 1GB As part of our ongoing product improvement programme our products are subject to change without prior notice Non contractual photos Systemair AC SAS Route de Verneuil 27570 Ti...

Reviews: