installation manual 

1.    PRECAUTIONS 

CAUTION 

CONTENTS 

PAGE 

PRECAUTIONS.........................................................................................................1

ATTACHED FITTINGS............................................................................................2

OUTDOOR UNIT INSTALLATION.......................................................................3

INSTALL THE CONNECTING PIPE......................................................................4

ELECTRICAL WIRING.............................................................................................9

TEST RUNNING......................................................................................................11

PRECAUTIONS ON REFRIGERANT LEAKAGE...............................................11

TURN OVER TO CUSTOMER..............................................................................12

Ensure that all Local, National and International regulations 
are satisfied.
Read this ”PRECAUTIONS ” carefully before Installation. 
The precautions described below include the important 
items regarding safety. Observe them without fail.
After the installation work, perform a trial operation to check
for any problem.
Follow the Owner’s Manual to explain how to use and 
maintain the unit to the customer.
Turn off the main power supply switch (or breaker) before 
maintenance the unit .
Ask the customer that the Installation Manual and the Owner’s
Manual should be kept together .

New Refrigerant Air Conditioner Installation 

CAUTION 

Do not connect the Appliance from Main Power Supply.

WARNING

THIS AIR CONDITIONER ADOPTS THE NEW HFC 
REFRIGERANT(R410A)WHICH DOES NOT DESTROY OZONE
LAYER.

The characteristics of  R410A refrigerant are; Hydrophilic, oxid- 
izing membrane or oil, and its pressure is approx.1.6 times high- 
er than that of refrigerant R22.Accompanied with the new refrig- 
erant, refrigerating oil has also been changed ,Therefore, during 
 installation work, be sure that water, dust, former refrigerant, or 
 refrigerating oil does not enter the refrigerating cycle. 
To prevent charging an incorrect refrigerant and refrigerating oil,  
the sizes of connecting sections of charging port of the main  
unit and installation tools are charged from those for the  
conventional refrigerant. 
 

Accordingly the exclusive tools are required for the new  
refrigerant (R410A): 
For connecting pipes, use new and clean piping designed for  
R410A,and please care so that water or dust does not enter.  
Moreover, do not use the existing piping because there are  
problems with pressure-resistance force and impurity in it. 

This unit  must be connected to the main power supply by 
means of a switch with a contact separation of at least 3 mm.
The installation fuse must be used for the power supply line of 
 this conditioner.

Ask an authorized dealer or qualified installation professional to
install/maintain the air conditioner.

Inappropriate installation may result in water leakage,electric shock
or fire.

Turn off the main power supply switch or breaker before 
attempting any electrical work.

Make sure all power switches are off.Failure to do so may cause 
electric shock.

Connect the connecting cable correctly.

If the connecting cable is connected in a wrong way, electric parts 
may be damaged.

When moving the air conditioner for the installation into another
 place, be very careful not to enter any gaseous matter other
 than the specified refrigerant into the refrigeration cycle.

If air or any other gas is mixed in refrigerant, the gas pressure in the 
refrigeration cycle becomes abnormally high and it may result 
in pipe burst and injuries on persons.

Do not modify this unit by removing any of the safety guards or
by by-passing any of the safety interlock switches.
Exposure of unit to water or other moisture before installation 
may cause a short-circuit of electrical parts.

Do not store it in a wet basement or expose to rain or water.

After unpacking the unit, examine it carefully if there are 
possible damage.
Do not install in a place that might increase the vibration of the 
unit.
To avoid personal injury (with sharp edges), be careful when 
handling parts.
Perform installation work properly according to the Installation 
Manual.

Inappropriate installation may result in water leakage, electric shock 
or fire.

When the air conditioner is installed in a small room, provide 
appropriate measures to ensure that the concentration of 
refrigerant leakage occur in the room does not exceed the 
critical level.
Install the air conditioner securely in a location where the base 
can sustain the weight adequately.
Perform the specified installation work to guard against an 
earthquake.

If the air conditioner is not installed appropriately, accidents may 
occur due to the falling unit.

If refrigerant gas has leaked during the installation work, 
ventilate the room immediately.

If the leaked refrigerant gas comes in contact with fire, noxious gas 
may generate.

After the installation work, confirm that refrigerant gas doer not 
leak.

If  refeigerant gas leaks into the room and flows near a fire source, 
such as a cooking range, noxious gas might generate.

Electrical work must be performed by a qualified electrician in 
accordance with the Installation Manual. Make sure the air 
conditioner uses an exclusive power supply. 

Summary of Contents for SYSVRF AIR EVO HP Mini

Page 1: ...Outdoor unit Mini VRF Heat Pump INSTALLATION MANUAL GB SYSVRF AIR EVO HP Q R ...

Page 2: ...intain the air conditioner Inappropriate installation may result in water leakage electric shock or fire Turn off the main power supply switch or breaker before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cable correctly If the connecting cable is connected in a wrong way electric parts may be damaged When mov...

Page 3: ...se copper pipe with 1 0 mm or more thickness for φ15 9 Use copper pipe with 1 0 mm or more thickness for φ19 0 Flare nut and flare works are also different form those of the conventional refrigerant take out the flare nut attached to the main unit of the air conditioner and use it Before installation Be careful to the following items before installation Air purge For air purge use a vacuum pump Do...

Page 4: ...ion place Near a private power station or high Frequency equipment The insulation of the metal parts of the building and the air conditioner should comply with the regulation of National Electric Standard Install indoor unit outdoor unit power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference 3 2 Installation space Unit mm 300 600 300 2000 Wall...

Page 5: ... the bends meet the following requirements 4 1 Refrigerant piping Fig 4 1 Large pipe Four condensed water outlets on the chassis for selection display as the follow figure Please pay attention to avoid the components while connect to the connecting pipes While installing the outdoor unit pay attention to the installation place and the drainage pattern if it s installed at the alpine zone the froze...

Page 6: ...units Main pipe size mm Iiquid pipe Branch Pipe 4 1 4 1 R410A Indoor unit connecting pipes diameters 1 R410A Indoor unit connecting pipes diameters 4 3DŽ 2 Example 1 In the Fig 4 5 The downstream inner units of the L2 and its total capacity is 28 2 56ˈrefers to the Table 4 4 the air liquid side of L2 is Φ15 9 Φ9 5DŽ 1 1 1 1 1 1 D E F H I G The straight distance between copper pipe turning and the co...

Page 7: ...door unit will be attenuated When capacity of indoor unit greater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time When the capacity of indoor unit is greater than or equal to 16 8kW the caliber of primary gas pipe should be augmented from Φ16 to Φ19 12 7 Flaring nut A 45 R410A A 56 6 4 Flaring nut 15 9 Flaring ...

Page 8: ...e capacity is decreasing it still can increase the gas side main pipe size ŏ Pδ N θ N ε ŏ Pδ N θ N ε Inner branch pipes are a f the size selection please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m Indoor unit branch pipe The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its...

Page 9: ...frigerant Amount to be Added Using vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit indoor unit connection NOTE Additional refrigerant volume of divergent pipe is 0 1kg per item Consider ...

Page 10: ...or unit Indoor unit Indoor unit Signal wire between indoor units 1 3 4 1 4 3 1 1 4 3 4 3 Branch Box Branch Box CCM Branch Box Please use 3 core shielded wire and connect the shielded layer to Grounding Power Supply Power Supply CCM For 8 18kW Fig 5 3 Outdoor Unit Indoor Unit Power wiring indoor Communication Bus Power 220 240V 50Hz 1 Phase 208 230V 60Hz 1 Phase Power 220 240V 50Hz 1 Phase 208 230V...

Page 11: ...on is indicated in broken line table users can select it when necessary CAUTION Indoor Outdoor Unit Signal Wire Connect the wire according to their numbers For 10 5 18kw Fig 5 4 Outdoor Unit Indoor Unit Power 220 240V 50Hz 1 Phase 220 240V 60Hz 1 Phase 208 230V 60Hz 1 Phase Power wiring indoor Communication Bus Indoor Unit Indoor Unit wire distribution box Switch Circuit breaker Switch Circuit bre...

Page 12: ...work address of indoor units NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users can purchase the wire controller when necessary To wire controller Display board WHITE BLUE BLACK P Q X Y E YELLOW GRAY To Outdoor COMM BUS To Central Control Monitor CCM COMM...

Page 13: ...ition 2 Calculate the indoor cubage B m as the minimum cubage 3 3 Calculate the refrigerant amount İ critical amount Counter measure against high amount 1 Install mechanical ventilator to keep the refrigerant amount under critical level ventilate regularly 2 Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate b Leak alarm related to mechanical ventilator...

Page 14: ...202000171943 MDV12I 013IW SYSVRF AIR EVO HP Q R_IM April 2014 ...

Reviews: