16
20 21 22 23 24 25 26 27 28 29 30 31 32 33
Air inlet temperature (°C db)
Water inlet temperature (°C)
10
15
20
25
30
35
40
45
50
11
32
14 15 16 17 18 19 20 21 22 23 24 25 26 27
Air inlet temperature (°C)
Water inlet temperature (°C)
40
50
60
70
80
90
100
110
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Air inlet temperature (°C db)
Nominal air flow
(%)
14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52
8 10 12
40
50
60
70
80
90
100
110
Water inlet temperature (°C)
Nominal water flow
(%
)
Operation within
the shaded ranges
requires special
attention to the
minimum water
flow rate.
Caution
7
SysLoop
8. TECHNICAL SPECIFICATIONS
8.1. OPERATING LIMITS
This equipment is designed EXCLUSIVELY for INDOOR installation.
In general, sheltered locations such as garages, roof space, etc, do not provide sufficient protection against
extreme temperatures and/or humidity and may be harmful to the unit’s performance, reliability and service
life.
8.1.1. ENVIRONMENT
* Conditions in
accordance with the
standard: EN 14511-2
MODELS
SL15
SL20
SL30
Nominal air flow *
m
3
/h
435
465
525
65% Nominal air flow
m
3
/h
261
279
315
MODELS
SL15
SL20
SL30
Nominal water flow *
l/h
317
444
617
50% Nominal water flow
l/h
158.5
222
308.5
Maximum hydraulic pressure
bar
10
10
10
* Conditions in
accordance with the
standard: EN 14511-2
8.1.2. TEMPERATURE LIMITS
8.1.3. FLOW LIMITS