16
ELECTRICAL CONNECTIONS
WARNING
BEFORE CARRYING OUT ANY WORK ON THE
EQUIPMENT, MAKE SURE THAT THE ELECTRICAL
POWER SUPPLY IS DISCONNECTED AND THAT THERE
IS NO POSSIBILITY OF THE UNIT BEING STARTED
INADVERTENTLY.
NON-COMPLIANCE WITH THE ABOVE INSTRUCTIONS
CAN LEAD TO INJURY OR DEATH BY ELECTROCUTION.
The electrical installation must be performed by a fully qualified electrician, and in accordance with local electrical
standards and the wiring diagram corresponding to the unit model.
Any modification performed without our prior authorisation may result in the unit’s warranty being declared null
and void.
The power supply cable section must be sufficient to provide the appropriate amperage to the unit’s main power
terminals, at start-up and under full load operating conditions.
The power supply cable shall be selected in accordance with the following criteria:
Power supply cable length.
1.
Maximum unit starting current draw – the cables shall supply the appropriate amperage to the unit
2.
terminals for starting.
Power supply cables’ installation mode. (do not leave cable weight hang on connecting lugs)
3.
Cables’ capacity to transport the total system current draw.
4.
Starting current and total current draw are indicated on the unit’s wiring diagram.
Short circuit protection shall be provided by others. This protection shall comprise fuses or circuit breakers with
high breaking capacity, mounted on the distribution board. The distribution board must support the intensity of the
whole of the machines installed.
If the remote controls include a ambient temperature sensor and/or a room stat with temperature setting, these
shall be connected with shielded cable and shall not installed in the same conduit as the power supply cable to
avoid induced voltages and create faults in the unit’s operation.
VERY IMPORTANT:
3N~400V-50HZ
The outdoor unit is equipped as standard with a phase sequence and cut-out controller located in the electrical
box.
THIS PRODUCT IS EQUIPPED WITH A PHASE SEQUENCE CONTROLLER. THE LED’s INDICATE THE
FOLLOWING CONDITIONS:
Green LED = 1
Yellow LED =1
Low voltage supply
T h e c o m p r e s s o r r o t a t i o n
direction is correct
Green LED = 1
Yellow LED =0
Phase inversion or phase absent
(L1)
The compressor and the fans
do not start.
Green LED = 0
Yellow LED =0
Phase absent (L2 or L3)
the compressor and the fans do
not start.
Summary of Contents for Rooft@ir 100
Page 2: ......
Page 28: ......
Page 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Page 50: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXII RT40 RT50 CONTROL pCO1 1 3 1 4 1 3 1 4 ...
Page 51: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXIII POWER AS L1 A1 A3 L2 L3 T1 T2 T3 ...
Page 52: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXIV 5 0 ...
Page 53: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXV RT60 RT70 RT80 CONTROL pCO1 ...
Page 54: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXVI RT100 RT110 CONTROL pCO1 ...
Page 56: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXVIII 5 0 5 0 ...
Page 57: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXIX ...
Page 58: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXX ...