background image

Water temperature 6/12°C

Airflow

Pressure
drop

Inlet air
temp

Inlet air
humidity

Outlet air
temp.

Output

Water flow

Water
pressure
drop

m

3

/h

Pa

°C

% RH

°C

kW

l/s

kPa

PGK 700x400-3-2.0

1920

35

25

50

16.3

5.6

0.22

2.2

1920

43

30

45

17.5

9.9

0.39

6.2

2880

70

25

50

17.0

7.7

0.31

4.0

2880

84

30

45

19.0

12.8

0.51

9.9

3840

114

25

50

17.6

9.5

0.38

5.8

3840

137

30

45

20.0

15.3

0.61

13.5

PGK 800-500-3–2.0

2743

36

25

50

15.9

8.5

0.34

3.4

2743

43

30

45

17.3

14.7

0.58

9.3

4115

72

25

50

16.8

11.5

0.46

6.0

4115

86

30

45

18.8

19.0

0.75

14.8

5486

117

25

50

17.5

14.1

0.56

8.6

5486

140

30

45

19.8

22.5

0.89

20.3

PGK 1000-500-3-2.0

3429

36

25

50

15.9

10.6

0.42

4.1

3429

43

30

45

17.3

18.4

0.73

11.2

5144

72

25

50

16.8

14.4

0.57

7.1

5144

86

30

45

18.8

23.7

0.94

17.8

6858

117

25

50

17.5

17.6

0.70

10.3

6858

140

30

45

19.8

28.2

1.12

24.5

4.2 4 rows

Water temperature 6/12°C

Airflow

Pressure
drop

Inlet air
temp

Inlet air
humidity

Outlet air
temp.

Output

Water flow

Water
pressure
drop

m

3

/h

Pa

°C

% RH

°C

kW

l/s

kPa

PGK 400x200-4-2.0

576

43

25

50

16.4

1.6

0.06

1.2

576

48

30

45

16.4

3.2

0.13

5

864

86

25

50

16.5

2.4

0.09

3

864

98

30

45

17.4

4.5

0.18

9

1152

140

25

50

16.6

3.2

0.13

5

1152

160

30

45

18.3

5.5

0.22

13

PGK

Installation and Service

172391

6

Systemair AB

Summary of Contents for PGK

Page 1: ...PGK Rectangular cooling battery for cold water Installation and Service Document in original language 172391 EN_GB 2013 10 10 A002...

Page 2: ...nts 1 Product information 1 2 Dimensions 1 3 Installation 2 3 1 Installing the unit 2 3 2 Water connections 2 3 3 Droplet eliminator 4 4 Capacity 5 4 1 3 rows 5 4 2 4 rows 6 5 Maintenance 8 5 1 Cleani...

Page 3: ...x250 4 2 0 538 288 120 176 43 3 4 1 36 DE 50x25 PGK 500x300 3 2 0 538 338 175 176 43 3 4 1 23 DE 50x30 PGK 500x300 4 2 0 538 338 175 176 43 3 4 1 64 DE 50x30 PGK 600x300 3 2 0 638 338 170 176 43 3 4 1...

Page 4: ...f screws or slip joints The condensate outlet pos C in figure 2 should be connected across a water trap in order to avoid air leakage Note The size of the outlet should be such that no water will rema...

Page 5: ...with a drain connection pos A and the outlet with an air purging connection pos B 4 After the system has been filled with water check the duct cooler and its connections to ensure that there is no wat...

Page 6: ...f air flow Remove the drip tray from underneath Push the droplet eliminator up until the holder secures it in position Fig 5 Carefully check that the air flow is in the direction of the arrow on the d...

Page 7: ...0 17 5 4 6 0 18 9 7 1800 121 30 45 19 8 7 6 0 30 23 4 PGK 500 300 3 2 0 1080 33 25 50 16 5 3 1 0 12 3 3 1080 37 30 45 17 6 5 6 0 22 9 7 1620 66 25 50 17 0 4 4 0 17 6 3 1620 74 30 45 18 9 7 5 0 30 16 0...

Page 8: ...14 8 5486 117 25 50 17 5 14 1 0 56 8 6 5486 140 30 45 19 8 22 5 0 89 20 3 PGK 1000 500 3 2 0 3429 36 25 50 15 9 10 6 0 42 4 1 3429 43 30 45 17 3 18 4 0 73 11 2 5144 72 25 50 16 8 14 4 0 57 7 1 5144 8...

Page 9: ...0 4 2 0 1296 49 25 50 15 9 5 5 0 22 4 1296 49 30 45 17 8 8 1 0 32 9 1944 95 25 50 16 7 7 5 0 30 8 1944 95 30 45 19 0 11 0 0 44 15 2592 153 25 50 17 4 9 3 0 37 11 2592 153 30 45 19 8 13 6 0 54 23 PGK 6...

Page 10: ...ate outlet and blank off the connection so that any remaining condensate will not run out Remove the drip tray by releasing the excentric lock on the front Lower the drip tray about 2 3 cm and then mo...

Page 11: ...PGK Installation and Service 172391 9 Systemair AB...

Page 12: ...erves the right to make changes and improvements to the contents of this manual without prior notice Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99...

Reviews: