7.2 Start-up
Attention, electrostatic sensitive devices!
Be sure to ground the board at a suitable point in order to prevent
damage to the electronic components being caused by electro-
static discharges. Such damage could occur, e.g., if a metal
water pipe or heating line are brie
fl
y touched.
It is prohibited to touch any other areas of the printed circuit
board than the 3 programming keys.
Procedure
1. You must mount and connect the device in accordance with the
operating instructions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating
plate.
4. Set the mode, unit and measuring range and adjust the sensor
in the
BASE SETUP
.
5. Set the parameters for control operation for the modes
4.01
and
5.01
under
SETTING
.
Information
When saving the Operating Mode, the factory settings are stored.
Therefore all the settings you have made, are lost.
7.3 Menu structure
100 Pa
Δ
p
Display after turning on the voltage supply.
Switch over between actual value display and
“
INFO
”
with the key shortcut for Escape (ESC
=
▼
+
▲
).
INFO
Selection of the menu group (e.g. BASE SETUP) to the right
through the
▼
-key, to the left through the
▲
-key.
Youcangotothemenuitemsinthe
menu
groups (e.g. mode) by using
the P key. Use the arrow keys to move up and down within the
menu group.
Operating Instructions
PCA 1000D
Programming
L-BAL-E120-GB 1419 Index 002