Page 1: ...PCA 1000D Part No 38999 Sensor control module for differential pressure and volume Operating Instructions Software version D1673A from Version 1 03 L BAL E120 GB 1419 Index 002 Part No english...
Page 2: ...eneral notes 7 4 2 Temperature in uences during commissioning 8 5 Electrical installation 8 5 1 Safety precautions 8 5 2 EMC compatible installation of control lines 9 5 3 Connection Voltage supply 9...
Page 3: ...pressure sensor 16 7 6 Check sensor function 17 8 Enclosure 17 8 1 Technical data 17 8 2 Connection diagram 19 8 3 Dimensions mm 19 8 4 Manufacturer reference 20 Operating Instructions PCA 1000D L BA...
Page 4: ...trusted with plan ning installation commissioning and maintenance and servicing and who have the corresponding quali cations and skills for their job 1 3 Exclusion of liability To allow for future dev...
Page 5: ...or which exceed those speci ed will be deemed unauthor ised unless contractually agreed Damages resulting from such unauthorised uses will not be the liability of the manufacturer The user will assume...
Page 6: ...module for pressure or volume the purpose of the device is to reach and maintain the target value set To accomplish this the measured actual value sensor value is compared with the adjusted target val...
Page 7: ...nd check for any possible shipping damage Assemble the device on a clean and stable base Do not distort during assembly Use the appropriate mounting devices for proper installation of the unit Do not...
Page 8: ...lectric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engi neering regulation...
Page 9: ...xed to the side 5 4 Output voltage 0 10 V Connection to Terminals A GND Imax Technical data It is not permissible to connect outputs of several devices to each other 5 5 Input for switch over Setpoin...
Page 10: ...ge input for switch over Set point 1 2 Plus connection in area with higher pressure Minus connection in area with lower pressure Multipurpose LC display and internal keyboard 100 Pa p Text line 1 16 g...
Page 11: ...nsor output 0 10 V proportional to measuring range 4 01 Pressure controller PID output 0 10 V depending on adjusted Setpoint and measured actual value 5 00 Air volume sensor Output 0 10 V propotional...
Page 12: ...rating plate 4 Set the mode unit and measuring range and adjust the sensor in the BASE SETUP 5 Set the parameters for control operation for the modes 4 01 and 5 01 under SETTING Information When savi...
Page 13: ...ESC short key i e the originally set values remain Example for Mode 2 01 Factory setting INFO SETTING BASE SETUP P ESC P ESC P ESC 100 Pa p 500 Pa Setpoint 1 4 01 Mode 500 Pa Setpoint 1 500 Pa Setpoin...
Page 14: ...tor Uout 0 0 V 9 9 V 0 0 V 9 9 V Magnitude of the out put voltage 0 10 V UNIcon 2 01 2 01 2 01 2 01 Software version p 0 Pa 0 000 in wg 0 Pa 0 000 in wg Display actual value for volume measurement SET...
Page 15: ...le Autozero OFF ON Automatic 0 offset3 Offset 0 Pa 0 000 in wg Sensor offset auto matically when Auto zero Setting range 1000 Pa 4 000 in wg 1 Setting range 4 01 0 100 sensor measurung range 5 01 0 Ma...
Page 16: ...ighest measuring range Zero point 0 2 10 K nal value 0 2 10 K MB Measuring range NA Zero point deviation EA Final value deviation LA Linearity deviation A Resolution H Hysteresis Nozzle coef cient K F...
Page 17: ...onnect the pressure hoses and check these if necessary 8 Enclosure 8 1 Technical data Type PCA 1000D Part No 38999 320043 42 Pressure measuring range 1 0 1000 Pa 0 4 0 in wg Pressure measuring range 2...
Page 18: ...g depends on position Protection class IP54 according EN 60529 Weight approx 250 g 0 55 lb Permissible ambient temperature 10 50 C 14 122 F Permissible rel humidity 85 no condensation Overload protect...
Page 19: ...max 6 mA 13 24 V Imax 14 mA 1 UB Ausgang Output 0 10 V Imax 0 3 mA UB 10 V Imax 10 mA UB 13 24 V 2 Uout 1 Voltage supply 10 24 V DC 2 Output 0 10 V 3 Pressure connections 4 Voltage input for switch ov...
Page 20: ...ional regulations If you have any questions concerning the use of our products or plan special uses please contact Systemair Industriev gen 3 73930 Skinnskatteberg Telefon 46 0 222 440 00 Telefax 46 0...