SystemAir NOVA drive 370 Product Description Download Page 11

Systemair NOVA drive 370

|  

11

DIR

0V

Direction 

CW/CCW

Motor parameters

Break

Reset / Automatic test

B

A

0V

Pot. meter

C

A

B

D

F

E

5.2.3 Motor settings and direction

Figure 11 – Motor settings and direction

The dip settings (A) of the motor must be set accordingly:
• 

Dips 1-3 are used for motor selection. Refer to Table 5 for more information.

• 

Dip 4 is used for break functionality. When set to ON when the motor is stopped it will break by shorting the wind-
ings making it harder to rotate. When set to OFF it is easier to turn the rotor, when the motor is not running.

• 

Dip 5 must be set to OFF. The usage is reserved for fault reset.

When DIR in (B) is left unconnected the motor will rotate in one direction. If DIR is connected to 0V it will rotate in the 
opposite. Connect DIR to 0V if you wish to change the direction the motor rotates. Note that the direction will change 
the next time the motor starts, not when it is already rotating.
Maximum speed can be reduced and set as 50-100% of the maximum speed given by the dip switch settings. This 
can be done using the potentiometer in (C).

It is possible to reset faults and warnings by toggling dip switch 5 (off->on->off) in less than 5 seconds. This will also 
set the inverter to use analog control unless new Modbus messages are received.

If using the alarm signal in the relay connect it in (E).

6 Motor parameters

Motor parameters are set using dip switches 1-3. A table is depicted bellow with the correspondence between dip 
switches and motor parameters selected.

Dip switch (123)

Id

Motor

MaxSpeed (RPM)

000

0

90TYD-S214-M

200

100

1

90TYD-S214-M

250

010

2

120-TYD-S214-M

250

110

3

120-TYD-S214-M

300

001

4

120-TYD-S214-M

350

101

5

120-TYD-S214-L

300

011

6

120-TYD-S214-L

350

Table 5 – Motor parameters selection

Summary of Contents for NOVA drive 370

Page 1: ...Systemair NOVA drive 370 Product Description...

Page 2: ...have a minimum shaft speed of 0 2rpm By external gear wheel it can run exchangers from 0 02 20rpm Control signal 0 10V Modbus RTU have an un linear function to ensure a linear heat transfer Extract su...

Page 3: ...Product description 4 3 Environmental constraints 4 4 Technical data 5 5 Mechanical and electrical installation 7 6 Motor parameters 11 7 LED behaviour 12 8 Fault behaviour 12 9 RHC features 13 10 Mo...

Page 4: ...the electrical installation on the rating plate matches the power supply Please refer to Table 2 for maximum fuse ratings and type CAUTION Risk of hot surfaces and electric shock if the unit has been...

Page 5: ...utral or phase to phase earth ground Frequency Hz 50 Hz 2 Hz Max input current 230V supply Arms 3 6 External input fuse size Type MAX C16 Minimum supply without speed reduction Vrms 207 Minimum supply...

Page 6: ...RS485 24V protected Control interface alarm 1x Alarm relay NC C NO Maximum 2A 250Vac or 6A 24Vdc Indicators Red Green Yellow LED on the PCB check Figure 6 for position Settings Dipswitch for Motor se...

Page 7: ...entation shall be vertical with the cable glands facing downwards This is to ensure the best thermal performance of the product For reference please refer to Figure 2 Figure 2 Mounting orientation of...

Page 8: ...Motor U V W Supply N L Alarm NC COM NO Solid wire 1 2 0 2 4 0 mm2 26 12 AWG Stranded wire 1 0 2 2 5 mm2 26 14 AWG Flat blade max 3 5 mm Analogue Control 0V Uin Uout Rotary Sensor 0V RUN DIR MODBUS 0V...

Page 9: ...ing Grounding hazard For the operator safety it is important to ground the drive properly and follow the provided grounding guidelines RCD compatibility For extra safety protection a Residual Current...

Page 10: ...anner until power is reset Enable rotary guard To use the rotary guard the sensor must be supplied with 10 V from Uout 10V and connected to ground 0V The out put from the sensor must be connected to R...

Page 11: ...if you wish to change the direction the motor rotates Note that the direction will change the next time the motor starts not when it is already rotating Maximum speed can be reduced and set as 50 100...

Page 12: ...how the latest error as it has higher priority Rotary guard Rotary guard passed When the rotary guard passes it shows the red green red green sequence 200ms each LED If the inverter has no warnings or...

Page 13: ...9 for a diagram When the inverter is running the motor and the rotary input is high for more than 10 seconds the functionality is disabled At this point a power reset is needed to enable it again 9 2...

Page 14: ...owing Modbus registers are available All the registers are either input registers 16 bit read only denoted by R or holding registers 16 bit read write denoted by RW Register Address Type Description B...

Page 15: ...rd in 0x115 R Rotor guard value 0 or 1 Test running 0x116 R 1 when test is running 0 otherwise Speed external 0 10V 0x117 R 0 4095 speed input Trimmer 0 10V 0x118 R 0 4095 trimmer input Extended SW ve...

Page 16: ...Safety req Automatic electrical controls for household and similar use EN 60335 2 40 2004 A11 2014 A12 2005 Safety req Particular requirements for electrical heat pumps air conditioners and dehumidifi...

Page 17: ...286rpm Current 0 79 0 46A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 2 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation...

Page 18: ...ent 1 37 0 79A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 5 5 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction...

Page 19: ...rent 2 04 1 18A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction C...

Page 20: ...no www systemair no Systemair B V Zanddonkweg 7a 5144 NX Waalwijk NETHERLANDS Tel 31 0 85 00 66 200 info systemair nl www systemair nl Systemair HVAC Spain S L U C Montecarlo 14 Fuenlabrada ES 28942...

Reviews: