MUB (Multibox) Series

Installation instructions

Systemair

Troubleshooting

1 Warnings

The following admonitions will be presented in the different sections of the document.

Danger

• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or

electrical work!

• All electrical connections must be carried out in accordance with local rules and regulations.

Warning

• In order for the unit to be considered safely installed the doors if equipped with handles have to be

locked with a key to prevent unauthorized or accidental opening

• The unit must be duct connected or in some other way provided with protection so that it is not

possible to come in contact with the fans through the duct connections

• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use

protective clothing.

• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is

used. Use protective clothing.

Caution

• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a

spanner to tighten the connection.

Topvex FR03, FR06, FR08, and FR11

Installation instructions

206638

1

Systemair AB

 WARNING

Before performing any maintenance to the unit, ensure that the unit's power is disconnected and locked out.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Reduced airflow

Elevated pressure in duct system.

Check duct system for obstructions.
Clean dirty filters.

Potentiometer speed control is set too low.

Adjust potentiometer.

Excessive buildup of debris on wheel.

Clean wheel.

Motor is rotating in wrong direction.

Adjust wheel rotation as shown under  
"Operation" (see Page 2).

Wheel is not aligned properly.

Adjust wheel so it is centered on inlet.

Excessive noise/vibration

Wheel is not balanced.

Clean all debris from wheel. Verify wheel balance 
and contact supplier if necessary.

Wheel is not aligned properly and rubbing  
against casing.

Adjust wheel so it is centered on inlet.

Foreign objects are located inside the wheel 
or casing.

Remove objects. Verify wheel balance and check for 
possible damage. Contact supplier if necessary.

Fan has stopped

Incorrect supply voltage or current.

Verify that supply voltage/current match 
nameplate values.

Fuse has blown

Replace with a new fuse. Verify that the new 
fuse is sized correctly.

Breaker has tripped.

Reset the breaker.

Motor has overheated.

See "Thermal Overload Protection" (Page 2).

Motor is blocked.

See "Thermal Overload Protection" (Page 2).

Summary of Contents for MUB16

Page 1: ...MUB Multibox Series Installation instructions Systemair MUB Multibox Series Centrifugal Inline Fans with integrated speed control Installation Operation and Maintenance Manual Item 404998 Date rev 052113 ...

Page 2: ...nal motor protection Assemble the fan in the direction of airflow see arrow on unit s nameplate Ensure that there is a distance of at least 2 5 times the wheel diameter between the inlet outlet and any elbows or transitions in the duct The fan must be installed so that vibrations are not transmitted to duct systems or frame of building Make sure the assembly of the fan is firmly fixed and stable T...

Page 3: ...IM A B C MUB 16 500 19 5 8 420 16 1 2 60 2 3 8 MUB 20 600 23 5 8 520 20 1 2 60 2 3 8 MUB 24 H 700 27 5 8 620 24 1 2 60 2 3 8 Dimensions are in mm inches 230 230 460 575 230 460 230 460 1 3 3 3 3 3 3 3 3 5 2 6 1 6 1 52 2 9 1 85 8 5 4 3 775 770 830 1150 750 1000 2800 2700 4 4 3 3 2 0 1 9 3 7 2 4 10 7 5 4 15 15 15 15 15 15 20 15 43 95 43 95 43 95 58 128 58 128 58 128 68 150 68 150 8 8 8 or more detai...

Page 4: ...he water battery when connecting water pipes to connectors Use a spanner to tighten the connection Topvex FR03 FR06 FR08 and FR11 Installation instructions 206638 1 Systemair AB WARNING Before performing any maintenance to the unit ensure that the unit s power is disconnected and locked out PROBLEM POSSIBLE CAUSE SOLUTION Reduced airflow Elevated pressure in duct system Check duct system for obstr...

Page 5: ...0142 100142 100142 100142 450823 450823 413519 413519 4 Panel Screw 479000 479000 479000 479000 479000 479000 479000 479000 479000 479000 5 Fuse Block 410591 410591 410591 410591 413491 413491 413491 413491 413491 413491 6 Fuse 410961 410695 410961 410959 410973 410970 410973 410970 410978 410975 Fuse Size Amp 8 5 8 6 6 3 5 6 3 5 15 8 7 Potentiometer 413416 413416 413416 413416 413416 413416 41341...

Page 6: ... Transducer Temperature Humidity Pressure CO2 Speed setting 1V 10V Integrated Sensor Transducer Temperature Humidity Pressure CO2 Controler PID NC COM Alarm Relay Motor Failure 2A 250VAC AC1 Speed setting PWM 1 10 kHz 100 PWM n max ca 10 PWM n min 10 PWM n 0 Start up at 1 4V Umin 15V Imax 10mA PWM 12V Voltage Range for EC models Nominal Voltage Nominal Voltage Range 120V 1 100 130V 240V 1 200 277V...

Page 7: ...sequential damages incurred in the use of the ventilation system Systemair is not responsible for providing an authorized service centre near the purchaser or in the general area Systemair reserves the right to supply refurbished parts as replacements Transportation removal and installation fees are the responsibility of the purchaser The purchaser is responsible for adhering to all codes in effec...

Page 8: ...nc reserves the right to make changes and improvements to the contents of this manual without prior notice Systemair Inc 50 Kanalflakt Way Bouctouche NB E4S3M5 Canada Phone 1 519 550 3307 10048 Industrial Blvd KS 66215 United States Phone 1 517 648 2863 www systemair net ...

Reviews: