A
B
C
D
E
F
SERVICE MODE SETTINGS
• Start programming: Press and hold buttons
A
and
C
for 6 seconds.
The indicator lights flash three times.
• Press one of the buttons
A
to
F
to change the setting.
• Save the changes by pressing and holding buttons
A
and
C
for 3 seconds.
The indicator lights flash twice.
FUNCTIONS – MONOLIT EC
Button Functions
Factory settings
LED indication
A:
Damper opening time 18 s.
Deactivated
Off
Option to change damper opening time
Contact Customer Services Off
B:
Damper timer 60 min.
Activated
On
C:
Function -16, see User Instructions
Deactivated
Off
(Please note that the function description has changed)
D:
No basic ventilation (0 V)
Deactivated
Off
E:
Damper and central fan timer 60 min.
Activated
On
(Only applies to function -16)
F:
Damper service interval 72 hours
Activated
On
FUNCTION MONOLIT AC CENTER
Button Functions
Factory settings
LED indication
A:
Damper opening time 18 s.
Deactivated
Off
Option to change damper opening time
Contact Customer Services Off
B:
If function -17: Damper timer 60 min.
Activated
On
If function -16: Damper and motor timer 60 min.
C:
Function -16, User Instructions
Deactivated
Off
(Please note that the function description has changed)
F:
Damper service interval 72 hours
Activated
On
24