11.3 Maintenance
To ensure a reliable operation of the fan, we recommend periodic maintenance intervals. These maintenance intervals must be speci-
fied by the operator. The frequency of maintenance activities or additional activities must be decided ac cording to the use of the fans. It
is important for traceability to create a maintenance plan, in which the work performed is written down.
The maintenance intervals should be shorter if the following conditions (among others) apply:
· Fan used as kitchen exhaust application
· Ambient temperature > 104°F or < 14°F
The following check list provides points of reference for the tasks to be carried out.
Table 3 Activities
Activity
As required
Periodic intervals
Check the fan and components for visible damage, corrosion, and
contamination
X
Inspect the rotor for damage and imbalance
X
Check that the condensate drain functions correctly
X
Clean the fan / ventilation system (see Chapter Cleaning)
X
Inspect screwed connections and tighten them if necessary
X
Ensure that the intake of the fan is free from dirt
X
Check that fan and components are being used as intended
X
Check the current consumption
X
Check that the vibration dampers function correctly (if used)
X
Check that the electrical and mechanical protective devices function
correctly
X
Check if the name plate of the fan is legible
X
Check that connection terminals and cable glands are tightly screwed
and have no visible damage / defects
X
Check flexible connections for leaks
X
11.4
Spare parts
◊ Use original spare parts from Systemair only.
◊ When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
12
Cleaning
12.1
Safety information
◊ Cleaning may only be carried out by adequately qualified persons, details see Table 1
Qualifications
, page 5.
◊ Wear protective equipment during all work in the vicinity of the fan, details see 2.2
Personal protective equipment
, page 5.
◊ Observe the 5 rules of electrical safety, see 2.3
5 rules of electrical safety
, page 5.
◊ Ensure that the power supply has been switched off (all-pole circuit breaker).
◊ Ensure that the rotor is at a standstill.
Note:
If you have questions, please contact Systemair. Defective fans must be completely replaced.
i