41
Alarm Description
Reset Type
Probable cause
Action taken by the control
- Derated mode: Warning & go to low
fixed speed fan control
- Unit stopped
Supply Fan Pressure
Failure
Manual
Defective sensor or installation
fault
Unit stopped
Exhaust Fan Pressure
Failure
Manual
Defective sensor or installation
fault
Unit stopped
Pressure Drop across
Heat Exchanger Sensor
Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: Warning and frost
protection deactivated
- Unit stopped
Room Pollution Sensor
Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: Warning & Go to low
fixed speed fan control
- Unit stopped
External Fire
Manual /
Automatic
configurable
in the extra
settings menu
Input of the controller activated
Configurable in Actual/Setpoint Extra
settings
•
Supply-fan off, Extract-fan off
(default)
•
Supply-fan on, Extract-fan on
•
Supply-fan on, Extract-fan off
•
Supply-fan off, Extract-fan on
When “on” is selected, fan is running at
a configurable fixed fan speed
Battery low or missing,
Change it quickly
Automatic
Internal monitoring
Warning
Pump Collective Failure Automatic
Input of the controller activated
Warning
Supply Air Humidity
Sensor Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: humidifier disabled
Extract Air Humidity
Sensor Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
Room Sensor Humidity
Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
Maximum humidity
Manual
Input of the controller activated
Humidifier stopped
Summary of Contents for HHFlex C
Page 1: ...1177fil HHFlex C R P S AHU Control Operating Instructions V8 00 ...
Page 7: ...7 2 5 Mapping of Inputs Outputs ...
Page 43: ...43 7 3 BACnet IP BACnet communication takes place via IP IP port main controller ...
Page 44: ...44 7 4 ANNEX 1 BACNET PROTOCOL IMPLEMENTATION AND CONFORMITY ...
Page 45: ...45 ...
Page 46: ...46 ...