6.5 Alarms List
Alarm Description
Reset Type
Probable cause
Action taken by the control
Low Supply Air
Temperature Alarm
Automatic
Unit with heat recovery only
During 10 minutes, SAT < SAT
controlled point – 3 K
Unit is stopped for 50 minutes then
restarted.
High Supply Air
Temperature Alarm
Automatic
Unit with heat recovery only
During 10 minutes, SAT > SAT
controlled point + 3 K
Warning.
Heat Exchanger Failure
Manual
Input of the controller activated
Warning only, control signal to rotor is
cancelled
Extract Fan failure
Manual
Input of the controller activated
Unit stopped
Supply Fan failure
Manual
Input of the controller activated
Unit stopped
Electrical pre-heater
maximum temp alarm
Manual
Input of the controller activated
Electrical pre-heaters are stopped and
unit stopped after cool down delay
Electrical heater,
maximum temp alarm
Manual
Input of the controller activated
Electrical heaters are stopped and unit
stopped after cool down delay
Frost protection of pre
heat hot water coil
Manual
Input of the controller activated
Unit stopped, valves opened at 80% &
heat demand/pumps activated
Frost protection of
booster hot water coil
Manual
Input of the controller activated
Unit stopped, valves opened at 80% &
heat demand/pumps activated
Same reaction with change over water
coil
Supply Filter High Delta
P Alert
Manual
Input of the controller activated
Warning
Extract Filter High Delta
P Alert
Manual
Input of the controller activated
Warning
End Filter High Delta P
Alert
Manual
Input of the controller activated
Warning
Supply Pressure Filter
Failure
Manual
Defective sensor or installation
fault
Warning
Exhaust Pressure Filter
Failure
Manual
Defective sensor or installation
fault
Warning
Pressure End Filter
Failure
Manual
Defective sensor or installation
fault
Warning
Inlet Air Temperature
Sensor Failure
Automatic
Defective sensor or installation
fault
Warning, no more pre-heater control and
heat recovery at 100%
Supply Air Temperature
Sensor Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: Warning, boosters
stopped & heat recovery at 100%
- Unit stopped
Extract Air Temperature
Sensor Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: Warning & go to SAT
control with heat recovery at 100%
- Unit stopped
Room Sensor
Temperature Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
- Derated mode: Warning, go to SAT
control, no more summer night
ventilation and room temp surveillance
- Unit stopped
Outdoor Air
Temperature Sensor
Failure
Automatic
Defective sensor or installation
fault
Warning & no more OAT compensation,
no more summer night ventilation
- Unit stopped
Supply Air Pressure
Sensor Failure
Automatic
Defective sensor or installation
fault
Configurable in Actual/Setpoint Config.
menu
Summary of Contents for HHFlex C
Page 1: ...1177fil HHFlex C R P S AHU Control Operating Instructions V8 00 ...
Page 7: ...7 2 5 Mapping of Inputs Outputs ...
Page 43: ...43 7 3 BACnet IP BACnet communication takes place via IP IP port main controller ...
Page 44: ...44 7 4 ANNEX 1 BACNET PROTOCOL IMPLEMENTATION AND CONFORMITY ...
Page 45: ...45 ...
Page 46: ...46 ...