6.5  Alarms List 

 

Alarm Description 

Reset Type 

Probable cause 

Action taken by the control 

Low Supply Air 
Temperature Alarm 

Automatic 

Unit with heat recovery only 
During 10 minutes, SAT < SAT 
controlled point – 3 K 

Unit is stopped for 50 minutes then 
restarted. 

High Supply Air 
Temperature Alarm 

Automatic 

Unit with heat recovery only 
During 10 minutes, SAT > SAT 
controlled point + 3 K 

Warning. 

Heat Exchanger Failure 

Manual 

Input of the controller activated 

Warning only, control signal to rotor is 
cancelled 

Extract Fan failure 

Manual 

Input of the controller activated 

Unit stopped 

Supply Fan failure 

Manual 

Input of the controller activated 

Unit stopped 

Electrical pre-heater 
maximum temp alarm 

Manual 

Input of the controller activated 

Electrical pre-heaters are stopped and 
unit stopped after cool down delay 

Electrical heater, 
maximum temp alarm 

Manual 

Input of the controller activated 

Electrical heaters are stopped and unit 
stopped after cool down delay 

Frost protection of pre 
heat hot water coil 

Manual 

Input of the controller activated 

Unit stopped, valves opened at 80% & 
heat demand/pumps activated 

Frost protection of 
booster hot water coil 

Manual 

Input of the controller activated 

Unit stopped, valves opened at 80% & 
heat demand/pumps activated 
Same reaction with change over water 
coil 

Supply Filter High Delta 
P Alert 

Manual 

Input of the controller activated 

Warning 

Extract Filter High Delta 
P Alert 

Manual 

Input of the controller activated 

Warning 

End Filter High Delta P 
Alert 

Manual 

Input of the controller activated 

Warning 

Supply Pressure Filter 
Failure 

Manual 

Defective sensor or installation 
fault 

 
Warning  

Exhaust Pressure Filter 
Failure 

Manual 

Defective sensor or installation 
fault 

Warning 

Pressure End Filter 
Failure 

Manual 

Defective sensor or installation 
fault 

Warning 

Inlet Air Temperature  
Sensor Failure 

Automatic 

Defective sensor or installation 
fault 

Warning, no more pre-heater control and 
heat recovery at 100% 

Supply Air Temperature 
Sensor Failure 

Automatic 

Defective sensor or installation 
fault 

Configurable in Actual/Setpoint Config. 
menu 
- Derated mode: Warning, boosters 
stopped & heat recovery at 100% 
- Unit stopped 

Extract Air Temperature 
Sensor Failure 

Automatic 

Defective sensor or installation 
fault 

Configurable in Actual/Setpoint Config. 
menu 
- Derated mode: Warning & go to SAT 
control with heat recovery at 100% 
- Unit stopped 

Room Sensor 
Temperature Failure 

Automatic 

Defective sensor or installation 
fault 

Configurable in Actual/Setpoint Config. 
menu 
- Derated mode: Warning, go to SAT 
control, no more summer night 
ventilation and room temp surveillance 
- Unit stopped 

Outdoor Air 
Temperature Sensor 
Failure 

Automatic 

Defective sensor or installation 
fault 

Warning & no more OAT compensation, 
no more summer night ventilation 
- Unit stopped 

Supply Air Pressure 
Sensor Failure 

Automatic 

Defective sensor or installation 
fault 

Configurable in Actual/Setpoint Config. 
menu 

Summary of Contents for HHFlex C

Page 1: ...1177fil HHFlex C R P S AHU Control Operating Instructions V8 00 ...

Page 2: ...al display 11 3 6 Web panel 11 3 7 Connection to the unit 11 3 8 Login Screen 12 3 9 Overview Screen 13 3 10 Dashboard screen 13 3 11 Actual Setpoint screen 14 3 12 Alarm Status screen 14 3 13 Inputs Output screen 14 3 14 Analog Inputs screen 15 3 15 Analog Outputs screen 15 3 16 Digital Inputs screen 16 3 17 Digital Outputs screen 16 3 18 Time Program screen 17 3 19 Settings screen 18 3 20 Factor...

Page 3: ...Warm Up at Unit Start Up 26 5 5 Unit Frost Protection 26 5 6 Chilled water Cooling Coil 26 5 6 1 Temperature Control 26 5 8 Change over water Coil for Heating and Cooling 27 5 8 1 Heat Cool Thermostat TS01 27 5 8 2 Temperature Control 27 5 8 3 Water Coil Frost Protection TA05 27 5 8 5 Warm Up at Unit Start Up 28 5 8 6 Unit Frost Protection 28 5 8 7 Defrost of heat pump 28 5 8 8 Backup electric hea...

Page 4: ... 36 5 21 2 Default settings for relative humidity control 37 5 23 Dehumidification control 38 5 23 1 Description control algorithm 38 5 23 2 Default settings for relative humidity control 38 6 DIAGNOSTICS TROUBLESHOOTING 39 6 1 General 39 6 2 Displaying Alarms 39 6 2 1 E DSP External display unit 39 6 2 2 Web Panel 39 6 3 Alarm report 39 6 4 Resetting Alarms 39 6 5 Alarms List 40 7 BUS COMMUNICATI...

Page 5: ...supplied separately must be read understood and followed Apply all standard safety codes and practices Wear safety glasses and gloves Use the proper tools to move heavy objects Move units carefully and set them down gently 1 2 Avoid Electrocution Only personnel qualified in accordance with IEC International electro technical Commission recommendations may be permitted access to electrical componen...

Page 6: ...t unit from restarting 2 3 Battery The resources and the program are stored in RAM To ensure that they are not lost and that the hardware clock continues to run when there is a power failure the controller is equipped with a buffer battery The buffer time is at least 5 years The buffer battery is a 3V lithium battery CR2032 The battery voltage is monitored When battery is low the P B Indication LE...

Page 7: ...7 2 5 Mapping of Inputs Outputs ...

Page 8: ...ith automatic detection change over TCP EXOline TCP BACnet IP Modbus IP requires EXOreal 3 1 1 01 or later Modbus 8 bits 1 or 2 stop bits Odd even Fs or no parity Speed Port 1 and Port 2 adjustable 1200 38400 bps 2 6 3Casing Protection class IP20 Mounting DIN rail mounting or mounting in cabinet Plastic Polycarbonate PC 2 6 4Inputs Analogue inputs AI 0 4 20 mA 0 10 V 0 200 mV PT 1000 DIN Ni1000 LG...

Page 9: ... There are one or more unacknowledged alarm s Flashing red There are one or more remaining acknowledged alarm s Fixed red You are in a dialogue box where it is possible to switch to change mode Flashing yellow Change mode Fixed yellow 3 3 Log in The standard passwords are 3333 for basic level with the lowest access guest and 2222 for level giving more access operator Menu tree external display ...

Page 10: ...NTROLLER SLAVE 2 CONTROLLER TIME SCHEDULE RUN SCHEDULE LOW SPEED NIGHTCOOLING RECIRCULATION PUMPTEST HOLIDAYS SETTINGS PRESSURE FAILURE SUPPLY TEMPERATURE FILTER SENSOR SUPPLY EXHAUST END LOW HIGH SUPPLY FAN EXTRACT FAN FACTORY INPUTS OUTPUTS RUNTIME ADJUST TIME DATE COMMUNICATION DEFAULTSCREEN SOFTWARE VERSION TYPE AND SERIAL NR MODBUS CONFIG BACNET IP CONFIG MANUAL AUTO ACCES RIGHTS MAIN CONTROL...

Page 11: ...ntroller is working in service IP address mode when Digital Input DI7 of the main controller is closed connect 24VDC to DI7 and is working in user IP address mode when DI7 is open The default service IP and user IP address of the unit is 169 254 24 1 The user IP address can be changed in the Settings menu when operating in service IP address mode or with the E DSP under Service Communication The s...

Page 12: ...Klick on the login button There are three login levels Basic level with the lowest access Login Guest Password 1111 Level giving more access Login Operator Password 2222 Level with full access for manufactory purpose only ...

Page 13: ...r No settings can be made 3 10 Dashboard screen Displays relevant modes and actual values All values written in blue can be changed As soon as a value has been changed and you have pressed enter the value is downloaded to the HHFlex controller Users logged in as Operator can make changes on this pages ...

Page 14: ...lex controller Users logged in as Guest can make changes on this pages 3 12 Alarm Status screen Shows actual Alarms and Status of the unit Alarms can acknowledged blocked or unblocked Users logged in as Guest or Operator can make changes BE CAREFUL Blocking Alarm can lead to unsafe situations 3 13 Inputs Output screen Shows actual values for all inputs and outputs This is a read only folder No set...

Page 15: ... frost protection max temperature electric heater and minimum airflow electric heater will be ignored 3 15 Analog Outputs screen Shows actual values for all analog outputs For testing purpose only all functions can manually set here to a certain value Only users logged in as Operator can make changes BE CAREFUL All settings which are made here will be executed Protections like frost protection max...

Page 16: ... frost protection max temperature electric heater and minimum airflow electric heater will be ignored 3 17 Digital Outputs screen Shows actual values for all digital outputs For testing purpose only all functions can manually set here to a certain value Only users logged in as Operator can make changes BE CAREFUL All settings which are made here will be executed Protections like frost protection m...

Page 17: ...ght cooling schedule Recirculation schedule Pump test schedule Holiday program All values written in blue can be changed by users logged in as Guest or Operator As soon as a value has been changed and you have pressed enter the value is downloaded to the HHFlex controller The day begins at 00 00 hours and ends at 24 00 hours ...

Page 18: ... a value has been changed and you have pressed enter the value is downloaded to the HHFlex controller Only users logged in as Operator can make changes BE CAREFUL Bad PID parameters can lead to unstable control 3 20 Factory Screen For manufactory purpose only data can be read but changed only by manufactory ...

Page 19: ...e TT02 control To activate this function select supply air temp in the configuration menu If OAT correction is selected there is compensation on the supply air temperature according the graph 4 2 Economy mode based on OAT TT06 If the option Eco mode on Outdoor Temp is selected in the configuration menu Actual Setpoint then mechanical heating cooling can be disabled between 2 OAT values Heat recove...

Page 20: ...e this function select room temp in the configuration menu If OAT TT06 correction is selected there is outdoor compensation on setpoint according the graph RAT TT05 setpoint correction 30 20 10 0 10 20 30 40 50 C OAT C TT06 X1 X3 Y3 2 K Y1 2 K Y2 0 K X2 ...

Page 21: ...room temperature drops below threshold Maximum Room Temperature TT05 Surveillance Restart unit with mechanical cooling if room temperature rises above threshold These functions are available only for control on room temperature or when night cooling is selected To set the parameters for this function go to the menu Actual Setpoint Room Temperature Summer Night Ventilation Free Cooling Restart unit...

Page 22: ...can also be selected with a remote contact on a digital input of the controller To activate this function set Runmode to Contacts 4 3 3Air Flow Control To activate this function set Fan control to Flow or Flow high low in the configuration menu Setpoints for this function are available in the menu Actual Setpoint flow supply fan and flow extract fan Supply and extract air are maintained at the des...

Page 23: ... than 3 K by default from the actual setpoint an internal timer is started After an elapsed time of 10 minutes by default the unit is switched off and a low temperature alarm is generated in the controller The auto reset function starts the unit again after 50 minutes by default If the low temperature condition still exists the cycle is repeated if not the unit continues to run If a low temperatur...

Page 24: ...trolled 4 2 Occupancy Management Occupancy can be monitored internally stand alone mode or externally remote mode The mode of operation must be selected in the web browser under runmode in the Actual Setpoint screen or with the external display under Runmode The following modes of operation can be selected Manual Off Unit is always in unoccupied mode Manual On Unit is always running in occupied mo...

Page 25: ...e For units with electrical heaters the fans may stop with a short delay to evacuate heat from the unit 5 HHFlex OPTIONAL CONTROL FUNCTIONS 5 1 Air Dampers Parameter for this function is available in the menu Actual Setpoint extract fan supply fan The exhaust CD05 opening extract CD02 opening supply CD04 opening and fresh air intake CD01 opening can be equipped with dampers If a start command for ...

Page 26: ...Up This function is not active when indoor unit is selected To avoid unintentional frost alarm a startup delay mode for winter operation is programmed If the outdoor temperature is below a preset value default 5 C the fans will only be started after a fixed preset time delay 5 min in order to pre heat the heating coil During this time delay the hot water control valve is opened at a preset value d...

Page 27: ...ode heating mode if water temperature is above 28 C cooling mode if water temperature is below 18 C If the temperature is between the above mentioned settings the last monitored thermal mode is maintained until the preset value of the other mode is exceeded 5 8 2Temperature Control If heat recovery is not enough to control temperature the Cold Water Coil will be basically controlled as shown in th...

Page 28: ...the supply fan is controlled like in occupied mode The extract fan is off 5 8 8 Backup electric heater The application of a change over water coil involves a greater risk on unavailability of heating capacity when required This situation occurs for instance when there is no warm water available because the heat pump is in cooling or defrosting mode If a backup electric heater is selected to secure...

Page 29: ...ulating pulse signal generated by the controller During each voltage pulse period the solid state relays are activated and give power supply to the heating rods The pulse signal is basically an on off voltage signal but due to its switching frequency a proportional performance operation of the electric heater is achieved The pulse control signal operates on all groups simultaneously 5 9 2Overheati...

Page 30: ...signal generated by the controller During each voltage pulse period the solid state relays are activated and give power supply to the heating rods The pulse signal is basically an on off voltage signal but due to its switching frequency a proportional performance operation of the electric heater is achieved The pulse control signal operates on all groups simultaneously 5 10 2 Overheating protectio...

Page 31: ... equipped with a frost coil with frost protection thermostat the frost thermostat on the heating coil downstream the heat recovery device is omitted The default hardware setting for the frost thermostat alarm is 5 C 5 11 3 Warm Up at Unit Start Up This function is not active when indoor unit is selected To avoid unintentional frost alarm a startup delay mode for winter operation is programmed If t...

Page 32: ... this minimum airflow has been reached an on off output allows operation of the outdoor unit compressors if a cooling or heating demand exists The minimum air flow is pre configured based on the AHU size but can be adjusted in the Factory menu 5 13 Water pump anti blocking system To avoid rotor blocking the pump receives a periodic run command pre configured every Monday from 10 00 to 10 02 h this...

Page 33: ...y loaded 5 15 3 Minimum fresh air threshold The mix command can be clamped by the minimum fresh air threshold value For example if minfreshair 20 then the maximum allowed value for mix command is 100 20 80 The primary heat recovery system shall be turned off when the recirculation is 100 Output command Recirculation Analog Outdoor Analog Exhaust Digital INDOOR OUTDOOR 100 50 0 100 Mix command 100 ...

Page 34: ...g capacity with fresh air calculation In some condition sucha as duct pressure airflow control the airflow may vary in great proportion Indeed the amount of fresh air cannot be fixed considering only the recirculation damper opening Thus the fresh air rate can be estimated using Mixing Air Temperature method To do this an additional temperature sensor is needed after the mixing section and before ...

Page 35: ...y possible if the HHFlex controller is configured to control the supply air temperature TT02 During this mode supply air temperature control can be deactivated but ventilation will be controlled as in the occupied period 5 19 Heat pump defrost In the defrost period of a heat pump connected to the AHU the recirculation mode can be forced This ensures that no cold air is introduced during the period...

Page 36: ...e outdoor temperature compensation if activated depending on offset actual setpoint measured value a master control signal will determine the actual setpoint of the supply air humidity control loop actual humidity in supply air is measured depending on offset the slave control signal to the humidifier adjusts the performance for the momentary demand the set limitations for supply air humidity will...

Page 37: ... decreasing supply temperature at rising outdoor temperature TT06 e g outdoor temperature rising from 10 C to 20 C causes a supply temperature shifting from 22 C to 16 C Attention For every unit it shall be checked if the default values are suitable for the actual application humidification process and moisture demand in the building Correct parameter settings for humidification require basic know...

Page 38: ...roller software calculates the matching moisture content depending on offset the slave control signal to the cooling coil adjusts the dehumidification performance for the momentary demand a peak value selector within the controller will always transmit the highest control signal generated by cooling dehumidification demand to the cooling coil the set limitations for supply air humidity will limit ...

Page 39: ...re displayed in de Alarm Status screen 6 3 Alarm report To permit alarm and alert reporting on LEDs or on the building management system two outputs are available on the customer terminal strip A digital 24 VDC output to report alarms A digital 24 VDC output to report service alerts 6 4 Resetting Alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type eit...

Page 40: ... controller activated Warning Extract Filter High Delta P Alert Manual Input of the controller activated Warning End Filter High Delta P Alert Manual Input of the controller activated Warning Supply Pressure Filter Failure Manual Defective sensor or installation fault Warning Exhaust Pressure Filter Failure Manual Defective sensor or installation fault Warning Pressure End Filter Failure Manual De...

Page 41: ...igurable in the extra settings menu Input of the controller activated Configurable in Actual Setpoint Extra settings Supply fan off Extract fan off default Supply fan on Extract fan on Supply fan on Extract fan off Supply fan off Extract fan on When on is selected fan is running at a configurable fixed fan speed Battery low or missing Change it quickly Automatic Internal monitoring Warning Pump Co...

Page 42: ...n whether to read or write values A function also describes what signal type it is meant for Supported Modbus functions 1 Read Coils 2 Read Discrete Input 3 Read Holding Register 4 Read Input Register Direct 16 Bit 5 Write Single Coil 6 Write Single Register 15 Write Multiple Coils 16 Write Multiple Registers 7 2 4Max 47 registers Max 47 registers can be read in one message 7 2 5Communication limi...

Page 43: ...43 7 3 BACnet IP BACnet communication takes place via IP IP port main controller ...

Page 44: ...44 7 4 ANNEX 1 BACNET PROTOCOL IMPLEMENTATION AND CONFORMITY ...

Page 45: ...45 ...

Page 46: ...46 ...

Page 47: ...47 Systemair B V Zanddonkweg 7a 5144 NX Waalwijk The Netherlands Phone 31 0 85 00 66 200 www systemair nl ...

Reviews: