English
7
HAN
8. TECHNICAL SPECIFICATIONS
IMPORTANT
A main fuse must mandatorily be provided on the power supply.
²
Fuses not supplied
²
Cables not supplied
Units are supplied pre-charged with refrigerant fluid.
This equipment contains fluorinated gas with greenhouse gas effects covered by the Kyoto agreement.
(1) At nominal air flow and at maximum fan speed without air filter
13
15
17
19
25
31
Compressor type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor quantity
1
1
1
1
1
1
Number of circuit
1
1
1
1
1
1
Refrigerant
R410A
Charge of circuit
kg
SEE NAME PLATE
13
15
17
19
25
31
Indoor fan
Number of fan
1
1
1
1
1
1
Type
Centrifugal
Drive type
Direct
Belt / variable pitch pulley
Motor nominal power
input
kW
0.60
0.75
0.75
1.10
1.10
1.50
Power supply
V/Ph/Hz
230V/1~/50Hz
400V / 3~N /50Hz
Nominal airflow
m
3
/h
2640
2940
3190
3860
4780
5530
Available static
pressure
(1)
Pa
100
170
160
210
240
250
Outdoor fan
Number of fan
1
1
1
1
1
1
Type
Propeller
Number of blades
3
3
3
3
5
5
Fan diameter
mm
610
610
610
610
710
710
Drive type
Direct
Nominal airflow
m
3
/h
9000
9000
9000
9000
12000
12000
Motor nominal power
input
kW
0.49
0.49
0.49
0.49
0.90
0.90
Power supply
V/Ph/Hz
230V/1~/50Hz
13
15
17
19
25
31
Power supply
400V / 3~N /50Hz
Maximum current
A
16
17
20
21
29
30
Starting current
A
70
69
79
107
119
126
Fuse rating FFG aM
A
16
20
20
25
32
32
8.1. REFIGERATION SPECIFICATIONS
8.2. ELECTRICAL SPECIFICATIONS
8.3. AERAULIC SPECIFICATIONS
Summary of Contents for HAN 13
Page 2: ......
Page 23: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 29: ...HAN 13 T1PRI T1SEC VII HAN APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 30: ...HAN 15 17 19 T1PRI T1SEC VIII HAN APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 31: ...HAN 25 31 T1PRI T1SEC IX HAN APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 38: ...XVI HAN APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...