12 / 16 | PP-105_201608 | FGS
4 Inspection of the FGS
Each FGS should be inspected immediately after installation, as
well as every 12 months, based on the following steps:
1.
Identification of the FGS
2.
Date of inspection
3. Check the electrical connection of the activation mechanism
4.
Check the electrical connection of the end switches
5.
Check the FGS for cleanliness, and eventual treatment (when
necessary)
6. Remove the protective grating.
7. Check the tightness of the blades, and record their eventual
correction (when applicable)
8.
Check the Intumex and rubber sealings, and record their
eventual correction (when applicable)
9.
Check the safety FGS closure - for details see Chap. 3
10.
Check the FGS functionality (for details see Chap. 3) with
regard to opening and closing the control system, tracking
the physical behaviour of the FGS and the signalisation of
the end positions, and record their eventual correction (when
applicable)
11.
Set into the operating position - see Chap. 2.1
12. Assemble the protective grating.
13.
Record into Operating log (page 13) with the name and
signature of the technician.
The FGS is usually part of a system. In this case the system must
be checked as specified in its operational and maintenance
requirements – this is a task for the installer of the entire system.
5 Warranty conditions
For the warranty conditions, please contact our Systemair
colleagues in your respective country.
Before installing the FGS, its functionality must be tested
according to Chapter 3 (“Functionality check“)
DO NOT INSTALL A NON-FUNCTIONING FGS!
Changes to the functionality of the FGS, caused by transport or
installation, aren‘t reclaimable after installation (deformations,
damages, mechanical damage of the sealing material, foreign
objects which can constrain the blade movement, improper
handling of the activating mechanism, etc.)
The FGS is transported via a covered means of transport, on
pallets or in boxes. When handling during transportation and
storage, the FGS must be protected against damage and weather
conditions. Blades of FGS must be in closed position. These
products must be stored in a closed and dry area where the
temperature is kept within the range of -20 °C to +50 °C.