This is a cord connected appliance; not intended to be field wired.  Accessing or tampering with the electrical enclosure voids 
the UL marking and manufacturer’s warranty.  Use this product in the manner intended by the manufacturer.  For additional 
questions, contact Fantech Technical Services.

 Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, 
including fire-rated construction.

        Dryer exhaust must always be vented to the outdoors.

Calculating Duct Length (STEP 1)

To calculate the length of your planned duct run, measure from the dryer to the external venting point in roof or wall.  Add up the total 
number of elbows in the exhaust duct.  Using the table below, calculate the equivalent duct length of the fittings and add to the 
measured duct length.

DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH

DRYER EXHAUST DUCT FITTING TYPE

EQUIVALENT LENGTH

45-degree elbow

2-1/2 feet

90-degree elbow

5 feet

     

Source: IRC-2018 Table M1502.4.5.1

Elevation

Max. Eq. Duct Length (ft)

Sea Level

125

2000

114

4000

106

6000

98

8000

92

10,000

85

Fan Mounting Location (STEP 2)

The DEDPV-705 can be mounted a minimum of 5 linear feet, maximum linear 40 ft, down-stream of the dryer outlet connection.  If the 
DEDPV is installed less than 15 ft downstream of the dryer exhaust, a secondary lint trap is required to be installed between the dryer 
and DEDPV.  Beyond 15ft, a secondary lint trap is considered optional but recommended for extending routine maintenance intervals.

Figure A.

Mounting the Fan (STEP 3)

A mounting bracket and hardware pack is included and should be used to rigidly mount the fan to a wall stud, rafter, or joist. 

Electrical box must be mounted in the vertical plane for correct pressure sensing

Horizontal 

  Angled 

  Vertical

Installation

If mounted horizontally, a 1/8 inch weep 
hole may need to be drilled in the bottom 
of the fan in order to prevent water from 
accumulating at the lowest point

Summary of Contents for Fantech DEDPV-705

Page 1: ...ng 2 pcs FC4 Clamps 4 pcs Grommet for Tubing 1 pc Mounting Bracket and Hardware 1 pc Indicator Panel 1 pc 4 x 4 Indicator Cover Plate 1 pc 50 ft 15 4 m Communication Cable 1 pc Warning Label for Indicator Cover Plate 1 pc registration fantech app REGISTER THIS PRODUCT TO INCREASE YOUR PRODUCT WARRANTY BY AN EXTRA YEAR in USA only IMPORTANT SAFETY INSTRUCTIONS INSTRUCTIONS IMPOTANTES POUR LA SÉCURI...

Page 2: ...INTENANCE 7 TROUBLESHOOTING 8 No Indicator Light 8 Single Flash 8 Double Flash 8 Triple Flash 8 WARRANTY 9 A Dryer Exhaust Duct Power Ventilator DEDPV is a term used for an appliance specifically designed to assist a single residential dryer gas or electric in overcoming dryer performance loss caused by long or restrictive duct configurations Dryer Exhaust Duct Ventilator differs from the term dry...

Page 3: ...to open any doors other than those necessary to access the dryer AVERTISSEMENT POUR RÉDUIRE LE RISQUE D INCENDIE DE CHOC ÉLECTRIQUE OU DE BLESSURE RESPECTER LES CONSIGNES QUI SUIVENT a Votre sécheuse est équipée d un ventilateur auxiliaire qui peut être installé loin de la sécheuse comme dans un grenier un vide sanitaire ou un sous sol b Le ventilateur auxiliaire est essential au fonctionnement sé...

Page 4: ...rities having jurisdiction ATTENTION NE PAS INSTALLER DANS LE CONDUIT D EVACUATION DE LA SECHEUSE SI LES INSTRUCTIONS INTERDISENT L INSTALLATION D UN VENTILATEUR AUXILIAIRE NE PAS INSTALLER DANS UN CONDUIT D EVACUATION MESURANT 7 62 MÉTRES 25 PI DE LONGUEUR OU MOINS Le DEDPV 705 est adapté pour surmonter une longueur équivalente de conduit de 125 pieds 38 mètres de conduit en acier galvanisé de 4 ...

Page 5: ...EXHAUST DUCT FITTING TYPE EQUIVALENT LENGTH 45 degree elbow 2 1 2 feet 90 degree elbow 5 feet Source IRC 2018 Table M1502 4 5 1 Elevation Max Eq Duct Length ft Sea Level 125 2000 114 4000 106 6000 98 8000 92 10 000 85 Fan Mounting Location STEP 2 The DEDPV 705 can be mounted a minimum of 5 linear feet maximum linear 40 ft down stream of the dryer outlet connection If the DEDPV is installed less th...

Page 6: ...iameter hole in the duct wall 6 to 8 inches from the inlet of the fan Carefully insert the grommet into the hole Drilling into a metal duct may produce sharp burrs Needle nose pliers can be used to remove or flatten sharp edges a Attach one end of the clear pressure tubing to the pressure sensor located on the electrical box b Mark the opposite end of the pressure tubing inch from the edge and ins...

Page 7: ...If after a complete 5 minute run cycle the DEDPV does not sense pressure from the dryer the DEDPV 705 will engage in a final 5 minute cool down cycle before turning OFF Since fan bearings are sealed and provided with an internal lubricating material no additional lubrication is necessary Fan impeller may accumulate lint Periodic inspection based upon dryer usage should be performed to ensure that ...

Page 8: ...tenance on all dryer exhaust systems are necessary to ensure lint is not accumulating and creating blockages A hall effect sensor integral to the motor is used to sense the rotation of the fan wheel A loose connection within the fan electrical box can cause the system to think there is no rotation Solution Call Technical Support for authorization to open the electrical box and check connection H1 ...

Page 9: ...n for any breach of warranty WARRANTY INVALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applicable consumer protection legislation You may have additional rights which vary from state to state LIMITATION OF WARRANTY AND LIABILITY This warranty does not apply to any Fantech product or part which h...