1. Mounting
1.1 Surface mounting
Factory-made, the hub is delivered in a surface-mounted housing. The distances between
the holes for wall mounting are shown in the drawing below.
Alternatively, the base board can be removed from the housing. The board is then suitable
for mounting on a DIN rail.
2. Connection of the RZHC-HUB to the master cabinet EVC-MC
A free network port of the main switch cabinet EVC-MC is connected to the RZHC-HUB at
the "Controller BACnet/Modbus" port.
Connection via RJ45 network cable.
Total cable length:
max. 150 m
(AWG 26/7)
Alternatively, a network installation cable + network connector RJ45 can also be used for
on-site assembly. Total cable length: max. 250 m (AWG 23)