Maintenance/trouble setting
28
DVV-Ex XS-XL 23.02.2015
10.3
Maintenance, service
DANGER
Loss of explosion protection!
Basically the fan may be repaired at the manufacturer only! Failure to this would expire the ATEX approval
(basically, always consult the manufacturer). Exceptions are non-relevant components. They can be
performed on site by qualified personnel.
The fan is by built-in for-life lubricated ball bearings as far as possible low-maintenance product. After their life time
(app. 30.000 to 40.000 h), a replacement of the bearings is necessary. Observe attached instructions of motor manu-
facturer.
Pay attention to a non-typical noise from bearings.
For damages (e.g. damage to winding) please contact our Service Department. Repairs may be accomplished
only in the company of manufacturer and by the manufacturer. You find the address on the back of these op-
erating instructions.
Maintenance and check points
of fans similarly to VDMA 24186-1 (type, scope and maintenance intervals to be speci-
fied in dependence of use and operating conditions).
VDMA
24186-1
Description
Maintenance interval
Monthly
Every
3 months
Once
a year
Fan and electric motor
1.1.11
Check the drainage for function
×
6.1.1
Check to dirt, damage, corrosion and fastening
×
6.1.2
Functional cleaning
×
10.1.6
Check the terminals for tightness
×
10.1.9
Test the fan for function und operational readiness
(test run app. 15 min.)
×
6.1.4
Check the bearings for noise
×
10.1.3
Check impeller for direction of rotation (all speed)
×
6.1.3
Check impeller if damaged or unbalanced (if neces-
sary provide vibration measurement)
×
10.1
Functional test of automatically bridging of all ther-
mal and overcurrent protective devices
×
10.1.7
Measure the current
×
10.1.12
Test function of protective device
×
Triggering device
Check it for function
×
Test of functions
Test all functions of system from control panel as
well as signal lights
×
Accessories (air ducts, air louvers, flaps,
sound attenuators)
5.5.1
Check accessible ducts inclusive fire protective insu-
lation and fastening for outside damages and corro-
sion (visually)
×
5.5.4
Check accessible flexible connections for tightness
(visually)
×
5.2.1
5.2.3
Flaps and sound attenuators check for dirt, damage
and corrosion
Check mechanical functionality of the flaps
×
5.1.1
Check air louvres for dirt and damage (visually)
×