Trouble-shooting

53

Full heating power but no regulation

Full heating power but no regulation

No heating

No heating

C

BMT/Q

and

CV ..-..-.MQX / -.MQXL

CV ..-..-.MQP / -.MQPL

and

Deactivate the limitation function (not valid for MQU/MQUL heaters), if it is activated, by making sure that

the jumpers ”MIN” and ”MAX” are open.

Strap/short-circuit the terminals for the main sensor.

Disconnect the control signal wiring and strap/short-circuit the control signal input terminals.

If this results in the heating now being turned off, then the fault is in the external sensor circuitry.

If this results in the heating now being turned off, then the fault is in the external control signal.



Check that the sensor is of the correct type and that its termination is made correctly.
Check that the correct function for the Pulser or TTC is selected.
Check the resistance of the sensor and the set value potentiometer. Disconnect them from the terminals before any

measurements is taken.
Sensors for 0...30°C should have the resistance 10k

@ 30°C, 11.7k

@ 20°C and 15k

@ 0°C.

The external set value potentiometer should have the resistance 0...5k .

Ω

Ω

Ω

Ω

Make sure that the control signal has the correct polarity.


Check whether or not the overheating cut-out, with manual reset, has been activated. If it has, then eliminate

the fault and reset it. Read furthermore the paragraph ”Overheating” at page 10.

Check the overheating cut-outs and the heating elements by measurment.
Check whether or not there is mains voltage at the heater terminal blocks. Check the interlocking devices, fuses,

breakers, etc.

Disconnect the sensor from the terminals.


Check whether or not the overheating cut-out, with manual reset, has been activated. If it has, then eliminate

the fault and reset it. Read furthermore the paragraph ”Overheating” at page 10.

Check the overheating cut-outs and the heating elements by measurment.
Check whether or not there is mains voltage at the heater terminal blocks. Check the interlocking devices, fuses,

breakers, etc.

Disconnect the control signal wiring and connect a 9V batteri-cell or another suitable voltage source as a control signal.

If the heater starts now, then the fault is in the external sensor circuitry. Otherwise, the fault is in the regulator
(Pulser/TTC).

If the heater doesn’t start now, then the fault is in the regulator (Pulser/TTC).

CBMT/Q Heater Kit

Summary of Contents for CBMT/Q Series

Page 1: ...mit integriertem Thermostat und mit Strömungsverriegelung Appareil de chauffage de conduits rond avec régulateur de température et blocage de débit intégrés Pyöreät kanavalämmittimet joissa on sisäinen lämpötilansäädin ja virtaussäätö Канальные калориферы со встроенным регулятором температуры и блокировкой по расходу для круглых воздуховодов Ronde kanaalverwarmingen met ingebouwde temperatuurregel...

Page 2: ...on responsible for their safety Children should be supervised to ensure that they do not play with the appliance 1 The heater is designed for insertion into standard spiral ducting and is fixed to the ducting with screws 2 The air must flow through the heater in the direction indicated by the arrow on the side of the connection box 3 The heater can be fitted in either horizontal or vertical ductin...

Page 3: ...d oder MAX Funktion angeschlossen Der Heizregister besitzt einen eingebauten manuell rückstellbaren Überhitzungsschutz der auf der Außenseite des Deckels zurückgestellt werden kann L appareil de chauffage comporte une commande par thyristor Au réchauffeur sont connectés aussi bien le capteur principal gue le capteur pour la fonction MIN ou MAX L appareil est équipé d origine d un thermostat de sur...

Page 4: ...rature limitation function OPEN jumper deactivates the function H Airflow measuring chamber J Potentiometer to adjust the airflow interlocking threshold A yellow LED is indicating that the airflow is too low A red LED at 1 and 2 phase supply or two red LEDs at 3 phase supply indicates that the heating elements are activated WARNING The PCB is at mains voltage level when the heater is connected to ...

Page 5: ...er K J Combined room sensor and set value adjuster M External sensor for MIN MAX DE F Trennschalter J Externer Hauptfühler K Sollwerteinstellung K J Kombinierter Raumfühler und Sollwerteinsteller M Externer Fühler für MIN MAX FR F Interrupteur multipolaire J Capteur principal externe K Réglage de valeur consigne K J Capteur de local et réglage de valeur consigne combinés M Capteur externe pour MIN...

Page 6: ...d set value adjuster M External sensor for MIN MAX DE F Trennschalter J Externer Hauptfühler K Sollwerteinstellung K J Kombinierter Raumfühler und Sollwerteinsteller M Externer Fühler für MIN MAX FR F Interrupteur multipolaire J Capteur principal externe K Réglage de valeur consigne K J Capteur de local et réglage de valeur consigne combinés M Capteur externe pour MIN MAX NL F Werkschakelaar J Ext...

Page 7: ...ter should have the resistance 0 5k Ω Ω Ω Ω Make sure that the control signal has the correct polarity Check whether or not the overheating cut out with manual reset has been activated If it has then eliminate the fault and reset it Read furthermore the paragraph Overheating at page 10 Check the overheating cut outs and the heating elements by measurment Check whether or not there is mains voltage...