Operating Mode
The fan can be operated continuously within an ambient temperature range of –20°C to 55 °C (–4 °F to 131 °F) and with a
maximum airflow temperature of 55 °C (131 °F). Smoke extract fans (B) F300 (300°/120 min.) and (F) F400 (400°C/120
min.) can be operated continuously with a maximum airflow temperature of 55°C. The maximum airflow temperature for
120 min. is 300°C or rather 400°C.
The standard frequency stamped on the motor must be maintained.
9
Acceptance
The fan is subjected to a test run at the place of manufacturer before being transferred to the customer. This acceptance
test is documented.
10
Transport, Storage, Assembly
Danger!
Danger of personal injury if the fan falls.
Use suitable hoisting devices and fastening equipment.
Do not stand under the load during transport.
Attention!
Risk of damage to the fan or fan parts.
Do not move the device by pulling on the power cord, terminal box, impeller, safety guard or inflow duct.
Use suitable hoisting devices and fastening equipment.
Attention!
Risk of deformation of the fan.
Exercise caution when loading and unloading the fan for transport.
Observe the arrows on the package indicating the correct positioning for transport.
Pos. 01 Leitvorrichtung
Pos. 05 Motor
Pos. 02 Schutzgitter Pos. 06 Motortrageplatte
Pos. 03 Klemmkasten
Pos. 07 Montagebefestigung
Pos. 04 Laufrad
06
02
01
07
04
05
03
Pos. 01 Integrated diffuser
Pos. 05 Motor
Pos. 02 Safety guard
Pos. 06 Motor base plate
Pos. 03 Terminal box
Pos. 07 Fastener
Pos. 04 Impeller
IV
Induction Fan in compact casing with high efficiency radial fan with revision switch (optional). Using for horizontal con
-
struction. All steel parts are hot-dip galvanized, for best corrosion protection. IEC standard motors, insulation class H,
enclosure class IP55. Systemair induction fans have been tested in accordance with EN 12101-3 at LGAI Barcelona and are
CE labelled.