16/31 |
S-RA1
Product Handling
Warning
Some damper parts can have sharp edges. To prevent injuries, use gloves when you install or move the damper. If
you use or operate the damper incorrectly, there is a risk of:
- electric shock.
- fire.
- other damage.
Ensure that installation is performed by a trained person. The S-RA1 is made of sheet metal. Be careful when you
move the smoke control damper. It is necessary to move the bigger dampers with suitable lifting equipment (forklift,
crane). Please follow both textual and graphic instructions.
1. Unpacking:
• Remove the packaging
2. Functionality check:
• Perform damper's functionality check (see "Operation Manual" section).
3. Placing the damper:
• Prepare the opening and/or duct connection surfaces as per the desired installation type.
• Carefully lift the smoke control damper with the forklift, crane or manually.
• Place the damper into the duct until the casings stop.
4. Fixing the damper:
Note:
Make sure to continually check the alignment of the damper against the duct connection when performing the
next steps.
• Fix the damper to the duct using suitable self-tapping screws through the duct installations in connection area.
• Verify there is no skewing of the damper body by measuring diagonally the nominal dimension.
5. Electrical connection:
• Check the wiring diagram of dampers activation mechanism and connect the damper accordingly to the on-site
system and power supply.
6. Finishing:
• Clean the damper from the debris and excess material from the filling or insulation.
• Perform damper's functionality check (see "Operation Manual" section).
• Connect the continuous duct or mount the removed grille.
• Create and/or fill out the Operating Journal included with the smoke control damper (Operating Journal can be also
downloaded at design.systemair.com)