background image

Summary of Contents for EIS 120

Page 1: ......

Page 2: ...struction 100 40 50 Fire damper FDMB Solid wall construction Stuffing box mineral stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness 15 mm Duct I...

Page 3: ...ral stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness 15 mm Duct Installation opening perimeter has to be reinforced by standard drywall profile...

Page 4: ...l stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness 15 mm Duct 40 50 min 110 Concrete min 125 Aerated Concrete Installation in a solid ceiling c...

Page 5: ...B Solid wall construction Stuffing box mineral stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness 15 mm Duct Installation in a solid wall constru...

Page 6: ...amper FDMB Gypsum wall construction Fire protection plate of mineral wool Stuffing box mineral stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness...

Page 7: ...mineral stone wool min density 140 kg m Fire protection mastic min thickness 1 mm Cement lime plate min thickness 15 mm Duct Around the perimeter min 110 Concrete min 125 Aerated Concrete Installation...

Page 8: ...tar or gypsum Gypsum wall construction Solid wall construction Duct Fire protection plate of mineral wool Mineral stone wool Fire protection mastic min thick ness 1 mm Cement lime plate min thickness...

Page 9: ...50 Fire damper FDMB Solid ceiling construction Mortar or gypsum Gypsum wall construction Solid wall construction Duct Fire protection plate of mineral wool Mineral stone wool Fire protection mastic mi...

Page 10: ...9 100 100 100 Fire damper FDMB Installation frame Solid wall construction 100 100 100...

Page 11: ...reinforced by standard drywall profiles 100 100 100 Fire damper FDMB Installation frame Gypsum wall construction Fire protection plate of mineral wool Installation opening perimeter has to be reinforc...

Page 12: ...11 Fire damper FDMB Installation frame Solid ceiling construction min 110 Concrete min 125 Aerated Concrete 150 150 150 150 150 150...

Page 13: ...has to be used reinforcement VRM III fixing X 23 AxB 500x400 X 36 AxB 500x400 123 110 B B 60 A A 60 375 B X B 60 A X A 60 60 X 2 60 X 2 B B 60 A A 60 375 B X B 60 A X A 60 60 X 2 60 X 2 X 23 AxB 500x4...

Page 14: ...ocess 2 The control mechanism has to be protected covered against damage and pollution during installation process 3 Min gap for installation installation opening is 25 mm circular dimension D 50 mm o...

Page 15: ...abelled BUILD IN EDGE on the damper body The fire damper can also be integrated outside the wall construction Duct and the damper part between the wall construction and the damper blade labelled BUILD...

Page 16: ...de of fire damper exceeds body of fire damper by the value a and c or e and f There has to be enough space in duct for blade rotation Values a and c or e and f has to be respected when projecting rela...

Page 17: ...ing into operation these revisions must be done according to requirement set by national regulations 1 2 S3 S1 S2 S5 S4 S6 5 80 BAT Tf Tf LED 1 2 S3 S1 S2 S5 S4 S6 N L1 5 80 BAT Tf Tf LED BAT AC 230V...

Page 18: ...tion CLOSED If this is not possible then the starting mechanism spring must be checked or the base plate must be replaced The base plate is attached to the damper body with M5 screws 16 Before enterin...

Page 19: ...urface finish 2 Damper blades are made of fire resistant asbestos free boards made of mineral fibres 3 Damper controls are made of galvanized materials with no other surface finish 4 Springs are galva...

Page 20: ...19 MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz www mandik com...

Reviews: