background image

10

Maintenance of the unit

4.3

To change filters

Fig. 4 Heat exchanger filters

The filters cannot be cleaned and must be changed as necessary. This is nor-
mally done 1–2 times per year depending on the air pollution at the installa-
tion site.

It is very important to change filters regularly for performance and energy ef-
ficiency of the unit.

When it’s time to change the filters an alarm is shown on the control panel
display. When this occurs do the following:

1. Stop the unit by disconnecting the mains.

2. Open and remove the side cover. See chapter 4.2.

3. Pull out the filters towards you. Some force may be needed.

4. Insert the new filters. Make sure that the correct filter types are inserted.

See note above.

5. Close and fasten the side cover and connect the unit to mains.

6. Reset the filter time. See chapter 4.3.1.

4.3.1

To reset the filter change time

Once filter is changed, it is necessary to reset filter time. Go to

Filter

menu

(see 3.2.2

Home screen overview

, page 4, pos. E) or if filter alarm is present,

click on alarm status line (see 3.2.2

Home screen overview

, page 4, pos. 5)

and select filter alarm. Select

CHANGE FILTER

, in the pop up menu define a

new filter period and press

OK

to confirm selection.

Filter time is now reset.

Note:

The menu is locked by default. Enter a password (default
password is 1111).

To reset filter change timer for SAVE LIGHT

• Push and hold

and

buttons for 3 seconds to reset the filter timer

(filter change LED will turn off).

4.3.2

To select a different filter kit

Standard filters are designed for good outdoor air quality. It is possible to se-
lect and order filter kits for poorer air quality environment.

To change filter kit type

1. Touch

Select different filter kit

button in the alarm menu.

Alternatively, go to

Filter

menu (3.2.2

Home screen overview

, page 4,

pos. E).

2. Select filter kit from the list.

3. Touch

OK

button.

254538 | v1

Summary of Contents for 488819

Page 1: ...Document in original language 254538 v1 SAVE VTR 150 B User Manual GB...

Page 2: ...stemair UAB All rights reserved E OE Systemair UAB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Page 3: ...nge the temperature 7 3 2 7 To change the airflow 7 3 2 8 To set a week schedule 8 4 Maintenance of the unit 9 4 1 Maintenance Schedule 9 4 2 To access internal components 9 4 3 To change filters 10 4...

Page 4: ......

Page 5: ...t Systemair will require these in the case of a warranty claim 1 3 Type label Before calling your service representative make a note of the specification and production number from the type label whic...

Page 6: ...SAVE LIGHT control panel Fig 2 Explanation of symbols SAVE LIGHT is a basic control panel for SAVE series resi dential air handling units SAVE LIGHT allows to change airflow levels and indicates when...

Page 7: ...ensation when the unit has been stopped 3 1 3 To cancel sleep mode Press any button to cancel the sleep mode SAVE LIGHT returns to the sleep mode after 3 minutes of inactivity All control panel lights...

Page 8: ...ge number and the second number indicates a total number of pages available Many options show up in a form of the pop up window Select the option from the displayed list in the pop up window and press...

Page 9: ...uick information screen shows the following information 1 Time 2 Outdoor temperature 3 Current User mode Alarm 4 Fan speed off Minimum Low Normal High Maximum 5 Supply air temperature 6 Relative humid...

Page 10: ...irflow setting in Week Schedule Manual Manual selection of airflow levels The unit can be set run at one out of four available airflow speeds Off Low Normal High Note The fan can be set to OFF by acti...

Page 11: ...ettings of all modes can be modified in Service menu 3 2 6 To change the temperature Touch the thermometer symbol on the home screen to open the temperature settings window Use up and down arrows to i...

Page 12: ...Use arrow buttons and to increase or decrease value Confirm with OK button Note Scheduled time can start but never end at midnight 00 00 The latest END TIME period is 23 59 Scheduled time cannot go t...

Page 13: ...ied out correctly and written evidence thereof is provided 4 1 Maintenance Schedule Task 6 months 1 year 3 years When necessary General inspection X Filter change X X Fan cleaning X Heat exchanger cle...

Page 14: ...set the filter change time Once filter is changed it is necessary to reset filter time Go to Filter menu see 3 2 2 Home screen overview page 4 pos E or if filter alarm is present click on alarm status...

Page 15: ...not exposed to moisture 4 Remount the rotor Don t forget to reconnect the rotor power and sensor cables 4 5 To clean fans Danger Make sure that the Mains supply to the unit is disconnected before perf...

Page 16: ...ve the side cover 3 Remove the broken drive belt 4 Use tape to attach the drive belt to the rotating heat exchanger and rotate the exchanger by hand to get hold of the drive belt 5 Remove the tape and...

Page 17: ...of the installation The duct runs should therefore be cleaned changed when necessary Steel ducts can be cleaned by pulling a brush soaked in hot soapy water through the duct via diffuser louvre openi...

Page 18: ...panel or via a hardwired switch 6 Check the analogue inputs in the service menu to verify that the temperature sensors are functioning correctly 7 In case of installed electrical other re heater batte...

Page 19: ...254538 v1...

Page 20: ...SAVE VTR 150 B User Manual 254538 en_GB 2021 03 15 v1 Systemair UAB Lin st 101 LT 20174 Ukmerg LITHUANIA Phone 370 340 60165 Fax 370 340 60166 www systemair com...

Reviews: