background image

WFD

B

B

COM

COM

WFD

B

B

COM

COM

nonsilenceable

initiating zone of listed

Fire Alarm Control Panel

Typical Fire Alarm Control Panel Connection

Two Waterflow Detectors Shown

power source

compatible

with bell

local

bell

COM

B

Typical Local Bell Connection

Top View

NOTE: Common and B connections will

close when vane is deflected, i.e.,

when water is flowing. Dual switches

permit applications to be combined

on a single detector.

end-of-line-resistor

Break wire as shown for

supervision of connection.

DO NOT allow stripped wire

leads to extend beyond

switch housing. DO NOT

loop wires.

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

B

COM

A

Schematic of

Individual Switch

in “No Waterflow”

Condition

T16-0010-XXX

B

COM

A

COM

COM

SWITCH 1     SWITCH 2

      B      B    

 A

•CAUTION•
ROUTE WIRING
AWAY FROM
SHARP EDGES
& COMPONENTS

SWITCH SCHEMATIC
•READY• STATE

Operational Testing

Always notify a central station monitoring waterflow alarms before repair-
ing, maintaining, or testing waterflow alarm devices.
1.  Replace the cover and tighten the tamper proof screws with the tamper 

proof wrench. Store the wrench in a secure place.

2.  Open the inspector’s test valve and time how long it takes for the 

detector to indicate a flow condition. The detector should remain 
activated until the inspector’s test valve is closed. Air pockets in the 
sprinkler system may increase the apparent delay.

Maintenance

To prevent accidental water damage, control valves should be shut 
tight and the system completely drained before waterflow detectors are 
removed or replaced.

Inspect detectors in accordance with applicable NFPA codes and standards 
and/or the authority having jurisdiction for leaks and replace if a leak 
occurs. Test detectors at least quarterly, as described under Operational 
Testing, to ensure proper operation. Test more often if required by the 
authority having jurisdiction.

Under normal conditions, System Sensor waterflow detectors should 
provide years of trouble-free service. However, if the delay mechanism or 
switch enclosure needs to be replaced, follow these directions. To replace 
the delay mechanism or switch enclosure, use a 3⁄16

˝

 socket head screw-

driver to remove the three screws that hold it in place. Either mechanism 
can be easily replaced without removing the detector from the pipe or 
draining the pipe. To replace the delay mechanism, request Part No. A3008-
00. For switch enclosure, request Part No. A77-01-02. Do not repair or 
replace any other waterflow detector components. If any other part of the 
detector does not perform properly, replace the entire detector. Installation 
methods other than those listed in this installation manual may prevent 
the device from reporting the flow of water in the event the associated 
sprinkler system is activated by a fire. System Sensor is not responsible for 
devices that have been improperly installed, tested, or maintained.

D770-24-00 

3 I56-1452-004R

W0183-00

Figure 3. Assembly diagram:

W0234-00

Figure 4. WFD wiring:

COVER

SWITCH
ENCLOSURE
(REPLACEMENT
P/N A77-01-02)

GROUND SCREW
(GREEN)

CONDUIT
ENTRANCE

U-BOLT NUT

DIRECTION OF
FLOW ARROW

PIPE

U-BOLT

HOLE SIZE

(REFER TO CHART)

SADDLE GASKET

ROLL PADDLE (VANE)

OPPOSITE OF FLOW ARROW

WHILE INSERTING

PLASTIC VANE

PIPE SADDLE

DELAY MECHANISM

(REPLACEMENT

P/N A3008-00)

To remove a detector:
1.  Drain the pipe.
2. Turn off electrical power to 

the detector and disconnect the 
wiring.

3. Loosen the nuts and remove 

the U-bolts.

4.  Gently lift the saddle far enough 

to get your fingers under it. 
Then, roll the vane so it will fit 
through the hole while continu-
ing to lift the waterflow detec-
tor saddle.

5. Lift the detector clear of the 

pipe.

CAUTION

If a vane breaks in a pipe, find 
and remove it. If it is not removed, 
the vane may restrict the flow of 
water to all or part of the sprinkler 
system. 

Reviews: