background image

D770-53-00 

I56-2617-001R 

 

 

©2005 System Sensor

System Sensor warrants its enclosed product to be free from defects in materi-

als and workmanship under normal use and service for a period of three years 

from date of manufacture. System Sensor makes no other express warranty for 

this air duct smoke detector. No agent, representative, dealer, or employee of 

the Company has the authority to increase or alter the obligations or limitations 

of this Warranty. The Company’s obligation of this Warranty shall be limited 

to the replacement of any part of the product which is found to be defective 

in materials or workmanship under normal use and service during the three 

year period commencing with the date of manufacture. After phoning System 

Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization 

number,  send  defective  units  postage  prepaid  to:  System  Sensor,  Returns 

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please 

include  a  note  describing  the  malfunction  and  suspected  cause  of  failure. 

The Company shall not be obligated to  replace units which are found to be 

defective because of damage, unreasonable use, modifications, or alterations 

occurring  after  the  date  of  manufacture.  In  no  case  shall  the  Company  be 

liable  for  any  consequential  or  incidental  damages  for  breach  of  this  or  any 

other Warranty, expressed or implied whatsoever, even if the loss or damage 

is caused by the Company’s negligence or fault. Some states do not allow the 

exclusion or limitation of incidental or consequential damages, so the above 

limitation or exclusion may not apply to you. This Warranty gives you specific 

legal rights, and you may also have other rights which vary from state to state.

1.  Waterflow  detectors  may  not  work  or  operate  properly  if  sprinkler  piping  being 

monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler 

systems should be checked regularly for such blocking material.
2. Alarms generated by the activation of waterflow detectors may not be received by 

a central station if telephone or other communication lines to the detector are out of 

service, disabled, or open.
3. Vane-type waterflow detectors have a normal service life of 10–15 years. Hard water 

systems, however, may reduce waterflow detector service life significantly.

WARNING

The Limitations of Waterflow Alarm Devices

4.  Waterflow detectors are not a substitute for insurance. Building owners should always 

insure property and lives being protected by sprinkler systems.
5. If valves controlling the water supply to a sprinkler system are closed, vane-type 

waterflow  detectors  will  not  work.  All  valves  controlling  a  sprinkler  water  supply 

should be sealed or locked in the normally open position. The normally open position 

should be monitored by a sprinkler supervisory switch.

20

0

5

10

15

25

Dial setting

0

5

10

15

20

25

Table of dial settings

embossed here

(see below)

Delay

adjustment

dial

Figure 6. Delay adjustment dial:

GROUND

SCREW

(GREEN)

MOUNTING

PLATE

Figure 5. Ground screw location:

W0103-00

W0102-03

Dial setting equals delay in seconds
Reference only

Please refer to insert for the Limitations of Fire Alarm Systems

Three-Year Limited Warranty