I56-2877-006R 

 

 06-10

INSTALLATION AND MAINTENANCE INSTRUCTIONS

MP120K 120 VAC Adapter Mounting Plate

SPECIFICATIONS

General Specifications

Standard Operating Temperature: 

–40°F to 151°F (–40°C to 66°C)

Humidity Range: 

10 to 93% non-condensing (indoor products)

Nominal Voltage: 

Regulated 120 VAC

Operating Voltage Range: 

96-132 VAC

Current Draw From AC Line: 

150 mA max.

MP120K may be used with any of the following products, at all horn and strobe settings:
P2R, P2RH, P2RK, P2RHK, P2W, P2WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH, PC2RK, PC2RHK, PC2W, PC2WH, SCR, SCRH, SCRK, SCRHK, SCW, 
SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P, P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P, 
SR-SP, SRH-SP, P2R-SP, P2RH-SP, SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP, CHR, CHW, CHSR, CHSW

GENERAL DESCRIPTION

The MP120K mounting plate is designed to allow the use of 120 VAC to power 
SpectrAlert Advance horns, strobes, horns/strobes, chimes, and chime/
strobes. The MP120K consists of a SpectrAlert Advance mounting plate that 
has been fitted with a power supply that converts 120VAC to nominal 24V 
FWR.

The MP120K must be installed using a 120 VAC power source. This unit 
can only be used for non-synchronous applications; it will NOT work with  
SpecrtAlert Sync•Circuit Modules.

NOTICE:

 This manual shall be left with the owner/user of this equipment.

WIRING

This module has pig-tail wires and is intended to be wired without rigid con-
nections inside a standard electrical box.

Horn 

Horn/strobe 

Strobe Only 

Two Wire System

Any Mix of Models

Wired for Tandem

Operation

120 VAC

Power

A0356-00

I56-2877-006R

FIGURE 1. NON-SYNCHRONIZED DEVICES; ANY COMBINATION OF MODELS POWERED BY A 2-WIRE CIRCUIT.

3825 Ohio Avenue, St. Charles, Illinois 60174

1.800.SENSOR2; Fax: 630.377.6495

www.systemsensor.com