D690-04-00
3
I56-2783-003R
Tone SeLeCTion
Chime tone setting selection is accomplished by using the rotary switch on the
back of the product (see Table 4). The current draw for various tone settings
for chimes is listed in Table 5. The sound measurements for various chime
tone settings are shown in Table 6 for chime and chime/strobe products.
TabLe 4. Chime paTTernS
SeTTinG
repeTiTion raTe
db oUT
1
1 Second Chime
High
2
1 Second Chime
Low
3
1/4 Second Chime
High
4
1/4 Second Chime
Low
5
Temporal Chime
High
6
Temporal Chime
Low
7
5 Second Whoop
High
8
5 Second Whoop
Low
9
One Test Chime
High
TabLe 5. Chime CUrrenT draW (ma)
SoUnd paTTern
db
8–17.5 VoLTS
16–33 VoLTS
dC
FWr
dC
FWr
1 Second Chime
High
34
50
58
51
1 Second Chime
Low
30
51
51
54
1/4 Second Chime
High
34
51
50
50
1/4 Second Chime
Low
31
51
50
52
Temporal Chime
High
30
50
48
54
Temporal Chime
Low
30
47
50
51
5 Second Whoop
High
32
52
34
54
5 Second Whoop
Low
30
40
34
52
One Test Chime
High
48
49
50
50
TerminaL deFiniTionS
moUnTinG
FiGUre 4.
1. Attach mounting plate to junction box. The mounting plate is compatible
with 4˝ square, single gang, double gang, and 4˝ octagon junction boxes.
If using a back box skirt, attach the mounting plate to the skirt and then
attach the entire assembly to the junction box.
2. Connect field wiring according to terminal definitions.
3. If the product is not to be installed at this point, use the dust cover to
prevent contamination of the wiring terminals of the mounting plate.
4. To attach product to mounting plate, hook tabs on the product housing
into the grooves on mounting plate. Then, swing product into position to
engage the pins on the product with the terminals on the mounting plate.
Make sure that the tabs on the back of the product housing fully engage
with the mounting plate.
5. Secure product by tightening the single mounting screw in the front of
the product housing.
A0353-00
A0350-00
Switch
position Sound pattern
db
8–17.5 Volts 16–33 Volts
dC
FWr
dC
FWr
1
1 Second Chime High
58
59
61
61
2
1 Second Chime Low
53
54
52
53
3
1
/
4
Second Chime High
63
64
66
66
4
1
/
4
Second Chime Low
56
56
56
56
5
Temporal Chime
High
62
64
68
69
6
Temporal Chime
Low
54
56
57
57
7
5 Second Whoop High
68
71
75
77
8
5 Second Whoop Low
60
61
62
63
9
One Test Chime
High
56
55
59
57
WirinG
FiGUre 1. non-SYnChronized deViCeS; anY CombinaTion oF
modeLS poWered bY a 2-Wire CirCUiT
Chime
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
Chime
Synchronization Module
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
MD
L
FiGUre 2. SYnChronized deViCeS; anY CombinaTion oF
modeLS poWered bY a 2-Wire CirCUiT
Chime
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
Chime
Synchronization Module
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
MD
L
A0345-00
FiGUre 3.
TabLe 6. Chime & Chime/STrobe oUTpUT (dba)
Wiring
NOTE: For further information on synchronization see MDL, panel, or power