background image

D440-03-00 

I56-3475-000 

 

 

©2009 System Sensor

Three-Year Limited Warranty

System Sensor warrants its enclosed product to be free from defects in materials and 

workmanship  under  normal  use  and  service  for  a  period  of  three  years  from  date  of 

manufacture. System Sensor makes no other express warranty for the enclosed prod-

uct. No agent, representative, dealer, or employee of the Company has the authority to 

increase or alter the obligations or limitations of this Warranty. The Company’s obliga-

tion of this Warranty shall be limited to the replacement of any part of the product which 

is  found  to  be  defective  in  materials  or  workmanship  under  normal  use  and  service 

during the three year period commencing with the date of manufacture. After phoning 

System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization 

number, send defective units postage prepaid to: System Sensor, Returns Department, 

RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. Please 

include a note describing the malfunction and suspected cause of failure. The Company 

shall not be obligated to  replace units which are found to be defective because of dam-

age, unreasonable use, modifications, or alterations occurring after the date of manufac-

ture. In no case shall the Company be liable for any consequential or incidental damages 

for breach of this or any other Warranty, expressed or implied whatsoever, even if the 

loss or damage is caused by the Company’s negligence or fault. Some states do not 

allow the exclusion or limitation of incidental or consequential damages, so the above 

limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, 

and you may also have other rights which vary from state to state.

FIGURE 5. WIRING DIAGRAM FOR RTS151KEYA TO DH100ACDC 

4-WIRE DUCT SMOKE DETECTOR:

FIGURE 4: WIRING DIAGRAM FOR RTS151KEYA TO DNRA 2-WIRE DUCT SMOKE DETECTOR:

FIGURE 6. WIRING DIAGRAM FOR RTS151KEYA TO DH100 2-WIRE 

DUCT SMOKE DETECTOR:

NOTE: Terminal 6 of the RTS151KEYA is not used when wired to a 2-wire detector. 

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)

Power

DH100ACDCLPA

RTS151KEYA

5

4

3

*

* Sup. contacts 

cannot 

be used if they are 

wired to control 

panel.

1

2

3

4

5

6

3

4

5

Test +

Test / Reset –

Reset +

Test

Reset

RA +

RA –

V Out +

DH100

RTS151KEYA

6

2

1 Alarm

LED

No Connection

H0193-05

H0612-10

H0156-08

FIGURE 7. WIRING DIAGRAM FOR RTS151KEYA TO DH400ACDCA 

DUCT SMOKE DETECTOR:

5

7

11

10

6

3

4

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)

Power

DH400ACDCA

RTS151KEYA

5

4

3

*

* Sup. contacts 

cannot be used if 

they are wired to 

control panel.

H0156-09

FIGURE 8. WIRING DIAGRAM FOR RTS151KEYA TO BEAM1224A/

BEAM1224SA SMOKE DETECTOR:

H0585-04

3

2

1

5

4

RTS151KEYA

BEAM1224A/BEAM1224SA

REMOTE ALARM OUT

AUX (–)

TEST INPUT

REMOTE TROUBLE OUTPUT

RESET INPUT

TEST

RESET

T2-3

T3-3

T2-4

T2-2

T2-1

OPTIONAL YELLOW LED

NOTE: RTS151KEYA CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS. 

CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS

(RED LED) ALARM

24 VAC (+10%, –15%)

FULL WAVE RECTIFIED,

UNFILTERED POWER

MAY BE USED

RTS151KEYA

(OPTIONAL) REMOTE

TEST STATION

MAGNET

TEST

SWITCH

ALARM

LED (RED)

4

5
2

1

(+)

(–)

+ RA

+ RTS

– RA

+ TEST COIL

– TEST COIL

+ IN

+ OUT

(–)
(+)

DNRA

24 VDC

AUX POWER

SUPPLIED

BY USER

(100mA

SUPPLY)

RTS151KEYA

(OPTIONAL) REMOTE

TEST STATION

24 VAC (+10%, –15%)

FULL WAVE RECTIFIED,

UNFILTERED POWER

MAY BE USED

MAGNET

TEST

SWITCH

ALARM

LED (RED)

4

5

2

1

(+)

(–)

+ RA

+ RTS

– RA

+ TEST COIL

– TEST COIL

+ IN

+ OUT

24 VDC

AUX POWER

SUPPLIED

BY USER

(100mA

SUPPLY)

DNRA

NOTE:

 THE USE OF THE RTS151KEYA REQUIRES THE INSTALLATION OF 

AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.

METHOD #1 - AUX POWER LOCATED

 AT DUCT DETECTOR

METHOD #2 - AUX POWER LOCATED

AT TEST STATION