System Sensor PERTRONIC Innovair flex D4120 Installation And Maintenance Instructions Manual Download Page 7

10

9

19
20

1

12

15

3

2

1

D4120

APA151/451

(GREEN LED) POWER

FIELD 
INSTALLED 
JUMPER

11

2

+

AUX OUT +

AUX OUT –

ALARM

R TEST

ACC +

ACC –

R RESET

7

18

8

17

6

16

14

3

13

5
4

SUP, NO
SUP, C

NOTE:

 WIRING DIAGRAM SHOWN IS FOR D4120 4-WIRE DUCT SMOKE 

DETECTOR SYSTEM EQUIPPED WITHOUT A CONTROL PANEL.

NOTE:

 A TROUBLE CONDITION IS INDICATED 

BY LOSS OF GREEN LED

COMMON

(RED LED) ALARM

AUX OUT

AUX OUT

ACC
ACC

AUX

AUX

ACC
ACC

(-)
(-)

(-)
(-)

(+)

(+)

(+)

(+)

RTS2/RTS2-AOS 

D4120/D4120W/D4P120

 

NOTE: If polarity of Acc. (+) and Acc. (—) are reversed, 

an Amber LED on sensor 2 of the duct smoke detector  

power board will exist indicating a trouble condition.

FIGURE 10. DETECTOR SENSOR EXPLODED VIEW:

SENSOR 

COVER

SENSING 

CHAMBER 

COVER AND 

SCREEN

SENSOR 

CHAMBER

COVER 

REMOVAL 

TABS

H0584-02

FIGURE 14. WIRING DIAGRAM:

H0626-01

C1009-00

10

9

19
20

1

12

15

2

6

1
5

4

3

D4120

RTS451/RTS451KEY

(GREEN LED) 

POWER

(RED LED) 

ALARM

FIELD 

INSTALLED 

JUMPER

11

2

+

AUX OUT +

AUX OUT –

ALARM

R TEST

ACC +

ACC –

R RESET

7

18

8

17

6

16

14

3

13

5
4

SUP, NO
SUP, C

FOR RTS451KEY ONLY WITHOUT A CONTROL PANEL

FIELD 

INSTALLED 

JUMPERS

NOTICE: If any unitary packaged air conditioning units are run during the 
drywall installation phase of any building under construction to accelerate 
the drying of joint compound, the subsequent sanding of those drywall joints 
and resulting dust may compromise the sensor heads in duct smoke detectors. 
To avoid this condition it is recommended that the sensor heads be removed 
during the construction phase. 

For additional information visit www.systemsensor.com for a detailed techni-
cal bulletin.

[14] SENSOR REPLACEMENT (PART NO. 2D51)

1.

Remove the sensor head by rotating counterclockwise.

2.

Pull gently to remove it.

3.

 To replace the sensor head, align the mounting features and rotate clock-
wise into place.

[15] OPTIONAL ACCESSORIES

[15.1] RTS451/RTS151/RTS451KEY/RTS151KEY REMOTE TEST

STATION

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector as indicated in the
RTS451/RTS151/RTS451KEY/RTS151KEY manual. The D4120 duct smoke de-
tector can be reset by the RTS451/RTS151/RTS451KEY/RTS151KEY. To install
the RTS451/RTS151/RTS451KEY/RTS151KEY, connect the device as shown in

Figure 13

; wire runs must be limited to 25 ohms or less per interconnecting

wire. If a system control panel is used, the panel itself may require testing.

[15.2] RTS2/RTS2-AOS MULTI-SIGNALING ACCESSORY

The RTS2 and RTS2-AOS multi-signaling accessories are designed for use with 
InnovairFlex 4-wire conventional duct smoke detectors only. The accessory 
has two bicolored LEDs that indicate the sensor status of up to two connected 
duct smoke detectors. The key switch on the unit can be used to select a con-
nected duct detector sensor (either sensor1 or sensor 2), and the selected sen-
sor can be tested or both sensors can be reset simultaneously using the test/
reset button. LED status indications include: Standby (green blink), Trouble 
(amber), Maintenance (amber blink) and Alarm (red).

H0582-17

FIGURE 11. WIRING DIAGRAMS FOR OPTIONAL ACCESSORIES:

[13.1] DETECTOR SENSOR

1.

Remove the sensor to be cleaned from the system.

2.

 Remove the sensor cover by pulling outward on each of the four removal
tabs that hold the cover in place. See 

Figure 10

.

3.

 Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.

4.

Remove the chamber cover/screen assembly by pulling it straight out.

5.

 Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place.

7.

 Replace the cover using the holes for the LEDs for alignment and then
gently pushing it until it locks into place.

8.

Reinstall the detector.

[13.2] REINSTALLATION

1.

Reinstall the detector in its housing.

2.

Restore system power.

3.

Perform Detector Check, Section 12.3.

4.

 Notify the proper authorities testing has been completed and the smoke
detector system is back in operation.

ALARM

AUX OUT –

15

20

(+)

(–)

ALARM 

AUX OUT – 

15

20

(+)

(–)

RED

MHR/MHW 

(OPTIONAL) AUDIO 

ALERT

D4120

DUCT DETECTOR 

D4120

DUCT DETECTOR 

RA400Z(OPTIONAL)

REMOTE (LED) 
ANNUNCIATOR

H0554-00

FIGURE 12. WIRING DIAGRAM FOR D4120 TO APA151 OR APA451:

FIGURE 13. WIRING DIAGRAM FOR D4120 TO RTS451/RTS151/RTS-

451KEY/RTS151KEY:

With the key switch selected, there is also the capability of obtaining a sen-
sitivity measurement of the selected sensor using the SENS-RDR sensitivity 
reader (sold separately).

I56-2967-008R 

21

/0

9

/2020

Amended by Pertronic Industries, 

21 September 2020 (DST1 not available in Australia and New Zealand)

Summary of Contents for PERTRONIC Innovair flex D4120

Page 1: ...20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contatcs DPD...

Page 2: ...ity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the suppl...

Page 3: ...s in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration espe...

Page 4: ...th previously sold detectors 9 Unit Configuration 9 UNIT CONFIGURATION A three position Dip Switch is included only on the D4P120 in order to con figure the setup of the unit One switch is used to det...

Page 5: ...or contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble condition to the panel See specifications for contact ratings NOTE 4 Alarm Initiation contact...

Page 6: ...sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system control panel alarm status and control panel execution of all in tended auxiliary fu...

Page 7: ...ust be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel itself may require testing 15 2 RTS2 RTS2 AOS MULTI SIGNALING ACCESSORY The RTS2 and RTS2 AOS mul...

Page 8: ...r every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Mai...

Reviews: