System Sensor PERTRONIC Innovair flex D4120 Installation And Maintenance Instructions Manual Download Page 2

SENSOR MODULE 

COVER

POWER BOARD MODULE COVER

SENSOR HEAD

METAL 

SAMPLING TUBE

POWER BOARD

EXHAUST TUBE

4-WIRE

MAGNET TEST LOCATION

(sold seperately)

[3] GENERAL DESCRIPTION

Smoke introduced into an air duct system will be distributed throughout the
entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.

Model D4120 and D4S Duct Smoke Detectors utilize 4-wire photoelectric tech-
nology for the detection of smoke. This detection method, when combined 
with an efficient housing, samples air passing through the duct allowing de-
tection of a developing hazardous condition. When sufficient smoke is sensed, 
an alarm signal is initiated and appropriate action can be taken to shut off 
fans, blowers, change over air handling systems, etc. These actions can fa-
cilitate the management of toxic smoke and fire gases throughout the areas 
served by the duct system.

The D4120 and D4P120 detectors are designed to operate on 24 VDC/VAC or 
120 VAC. Alarm and supervisory relay contacts are available for control panel 
interface (alarm initiation), HVAC control, and other auxiliary functions. Aux-
iliary relays are provided for fan shut down. Detector interconnection provides 
signaling of up to 50 other detectors in the loop for multiple fan shut down. 
These detectors are not designed for 2-wire applications.

[3.1] DETECTOR FEATURE SET

-Utilizes 2D51 plug-in head
-2 sensors to 1 power board capability
-Cover missing signal
-Sampling tubes install from front or rear of detector
-Compatible with existing accessories

[4] CONTENTS OF THE DUCT SMOKE DETECTOR KIT

1.

Sensor/power board assembly and cover(s)

2.

Three #10 sheet metal screws for mounting

3.

Drilling template

4.

One sampling tube end cap

5.

One plastic exhaust tube

NOTE: A sampling tube must be ordered to complete the installation. It must 
be the correct length for the width of the duct where it will be installed. 
See Table 1 on page 3 to determine the inlet tube required for different duct 
widths. 

[5] DETECTOR INSTALLATION

[5.1] VERIFY AIR FLOW DIRECTION AND VELOCITY

Model D4120 detectors are designed to be used in air handling systems with
air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12
feet can be accommodated. Be sure to check engineering specifications to
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

[5.2] DETERMINE MOUNTING LOCATION AND CONFIGURATION

On ducts wider than 18 inches it is recommended that the detector be 
mounted downstream of a bend, obstruction in the duct, or the supply or 
return air inlet.

Exception:

 Installation of duct detectors can be on or within a commercial 

packaged rooftop heating and air-conditioning system, fire/smoke dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in 

Figure 2

. If mounting in the square configuration, 

remove the rear attachment screw, rotate the unit at the hinge, and replace the 
screw into the new attachment hole as shown in 

Figure 2

. Do NOT remove 

the hinge screw during this process. Final installation approval shall be based 
upon passing section 7.2.2 and/or 8.2.4 tests.

FIGURE 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[5.3] DRILL THE MOUNTING HOLES

Remove the paper backing from the mounting template supplied. Affix the 
template to the duct at the desired mounting location. Make sure the template 
lies flat and smooth on the duct. 

[5.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes 
using a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 

inch drill at target “B” centers.

[5.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION 

OR D4S SENSOR COMPONENT MOUNTING:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using 
a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch 

drill at target “C” centers. If desired, drill an additional .156 inch hole at the 
location of one of the mounting tabs on the lower housing.

[5.4] SECURE THE DUCT DETECTOR TO THE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION:

 Do not overtighten the screws.

[2] FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS:

H0549-06

I56-2967-008R 

21

/0

9

/2020

Amended by Pertronic Industries, 

21 September 2020 (DST1 not available in Australia and New Zealand)

Summary of Contents for PERTRONIC Innovair flex D4120

Page 1: ...20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contatcs DPD...

Page 2: ...ity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the suppl...

Page 3: ...s in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration espe...

Page 4: ...th previously sold detectors 9 Unit Configuration 9 UNIT CONFIGURATION A three position Dip Switch is included only on the D4P120 in order to con figure the setup of the unit One switch is used to det...

Page 5: ...or contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble condition to the panel See specifications for contact ratings NOTE 4 Alarm Initiation contact...

Page 6: ...sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system control panel alarm status and control panel execution of all in tended auxiliary fu...

Page 7: ...ust be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel itself may require testing 15 2 RTS2 RTS2 AOS MULTI SIGNALING ACCESSORY The RTS2 and RTS2 AOS mul...

Page 8: ...r every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Mai...

Reviews: