DESCRIPTION

The M200F-RF radio repeater is a battery operated RF device 

designed for use with the M200G-RF radio gateway, running 

on  an  addressable  fire  system  (using  a  compatible  proprietary 

communication protocol).

The repeater contains a wireless transceiver and plugs into the 

B501RF wireless sensor base. It is used to extend the RF range of 

the radio fire detection system.
This device conforms to EN54-25 and EN54-18. It complies with 

the requirements of EN 300 220 and EN 301 489 for conformance 

with the R&TTE directive.

SPECIFICATIONS

Supply Voltage:  

3.3 V Direct Current max.

Standby Current:  

120 µA@ 3V (typical in normal operating mode)

Red LED Current Max:  4mA

Re-Sync Time: 

35s (max time to normal RF communication from 

device power on)

Batteries: 

4 X Duracell Ultra123

Battery Life: 

 

4 years @ 25

o

C

Radio Frequency:   

865-870 MHz; 

RF Output Power:  

14dBm (max)

Range:  

500m (typ. in free air)

Relative Humidity: 

10% to 93% (non-condensing)

INSTALLATION

This equipment and any associated work must be installed in 
accordance with all relevant codes and regulations.

Figure 1 details the mounting of the B501RF base.

Spacing between radio system devices must be a minimum of 1m

Figure 2 details attaching the repeater to the base

Anti-Tamper Features

The base includes a feature that, when activated, prevents removal 

of the repeater from the base without the use of a tool.  See Figures 

3a and 3b for details on this. 

Head Removal Warning -

 An alert message is signalled to the CIE 

via the Gateway when a repeater is removed from its base.
Figure  4  details  the  battery  installation  and  the  location  of  the 

rotary address switches.

Important

Batteries should only be installed at the time of commissioning

Warning

Using these battery products for long periods at temperatures below 
-20°C can reduce the battery life considerably (by up to 30% or more)

Observe the battery manufacturer’s precautions for use and 

requirements for disposal

SETTING THE ADDRESS

Set the loop address by turning the two rotary decade switches on 

the underside of the repeater (see figure 4), using a screwdriver 

to rotate the wheels to the desired address. The repeater will take 

one module address on the loop. Select a number between 01 and 

159 (Note: The number of addresses available will be dependent 

on panel capability, check the panel documentation for information 

on this). 
Insert the repeater into the base and rotate it clockwise until it locks 

into place.

M200F-RF

RADIO SYSTEM REPEATER

INSTALLATION INSTRUCTIONS

E N G L I S H

PLASTIC LEVER

Figure 1: B501RF Mounting

Figure 3a: Activation of Tamper Resist Feature

Figure 2: Attaching the Repeater to the Base

-30°C

60°C

BREAK TAB AT DOTTED LINE BY 
TWISTING TOWARDS CENTRE OF BASE

Figure 3b: Removing Repeater From Base if 

Tamper Resist is Activated

USE A SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC IN THE DIRECTION OF THE ARROW

≤ 

M4

50-60 mm

104 mm

51 mm

32 mm

M200F-RF

B501RF

115 g

48 g

+

=

229 g

(66 g)

107 mm

BULGE

IN BASE

REPEATER

LED

LINE UP REPEATER LED 
WITH BULGE AND TWIST 
CLOCKWISE (ONLY ONE LED 
WILL OPERATE AS KEY)

I 56- 3893- 001

Summary of Contents for M200F-RF

Page 1: ...nd 3b for details on this Head Removal Warning An alert message is signalled to the CIE via the Gateway when a repeater is removed from its base Figure 4 details the battery installation and the location of the rotary address switches Important Batteries should only be installed at the time of commissioning Warning Using these battery products for long periods at temperatures below 20 C can reduce...

Page 2: ...r use in fire detection and fire alarm systems for buildings 0333 16 DOP IRF006 Pittway Tecnologica S r l Via Caboto 19 3 34147 Trieste Italy ROTARY ADDRESS SWITCHES Repeater Status LEDs Repeater Status LED State Meaning Power on initialisation no fault Long Green pulse Device is un commissioned factory default 3 Green blinks Device is commissioned Fault Blink Amber every 1s Device has an internal...

Page 3: ...del ripetitore senza l impiego di un utensile Vedere le figure 3a e 3b per altre informazioni Avviso di rimozione del sensore Un messaggio di avviso viene trasmesso al pannello di controllo tramite il gateway quando il ripetitore viene rimosso dalla base Nellafigura4sonoillustratil alloggiamentobatterieeiselettorirotanti Importante Installare le batterie esclusivamente al momento della messa in es...

Page 4: ...evetti in corso Dichiarazione di Conformità CE Ai sensi della norma EN60950 e della Direttiva R TTE 1999 5 CE Il presente prodotto è conforme alle seguenti Direttive 2006 95 CE Bassa tensione 2004 108 CE Compatibilità elettromagnetica Il testo completo della Dichiarazione di Conformità è disponibile presso System Sensor Europe Stato del ripetitore e LED Stato del ripetitore Stato del LED Significa...

Page 5: ...tidor se quita de su base la central CIE recibe un mensaje de alerta mediante la pasarela La figura 4 muestra la instalación de la batería y la ubicación de los selectores giratorios de dirección Configurar la dirección lazo antes de instalar las baterías ver sección siguiente Importante Instalar las pilas sólo en el momento de la puesta en funcionamiento Aviso Usar estos productos a pilas durante...

Page 6: ... en sistemas de detección y alarma de incendios para edificios 0333 16 DOP IRF006 Pittway Tecnologica S r l Via Caboto 19 3 34147 Trieste Italy SELECTORES GIRATORIOS DE DIRECCIÓN Patente pendiente Declaración de conformidad CE Cumplimiento de las directivas EN60950 y 1999 5 CE R TTE Este producto cumple la s siguiente s directiva s 2006 95 CE Límite de tensión 2004 108 CE Compatibilidad electromag...

Page 7: ...aters Bei Entfernen des Repeaters aus dem Sockel geht über das Gateway eine Störungsmeldung an die Brandmeldeanlage Abbildung 4 zeigt die Batterieinstallation und die Lage der Adressdrehschalter Wichtig Stellen Sie immer erst die Geräteadresse ein bevor Sie die Batterien einsetzen Die Batterien erst zum Zeitpunkt der Inbetriebnahme einsetzen Warnung Bei längerem Einsatz bei Temperaturen von unter ...

Page 8: ...nsatz in Brandmelde und Feueralarmanlagen für Gebäude 0333 16 DOP IRF006 Pittway Tecnologica S r l Via Caboto 19 3 34147 Trieste Italy ADRESSDREHSCHALTER Angemeldete Patente EG Konformitätserklärung Gemäß EN60950 und 1999 5 EG R TTE Richtlinie Dieses Produkt entspricht den folgenden Richtlinien 2006 95 EG Niederspannungsrichtlinie 2004 108 EG Elektromagnetische Verträglichkeit Die vollständige Lis...

Page 9: ...age d alerte est signalé à la centrale via l interface lorsqu un répétiteur est retiré de son socle Se reporter à la Figure 4 pour plus de détails sur l installation des piles et roues codeuses sélection adresse Important Installer les piles uniquement au moment de la mise en service Avertissement L usage de ces produits fournit des piles dans les températures au dessus de 20 C pour les périodes p...

Page 10: ...me incendie 0333 16 DOP IRF006 Pittway Tecnologica S r l Via Caboto 19 3 34147 Trieste Italy ROUES CODEUSES SÉLECTION ADRESSE LEDs Etat Répétiteur Etat du Répétiteur Etat LED Signification Mise en route pas de dérangement Clignotant lent vert Dispositif non programmé défaut de l usine 3 clignotes en vert Dispositif est mis en service Dérangement Clignote en jaune toutes les 1s Dérangement interne ...

Reviews: