D200-101-00
9
I56-3888-103
Either replace the filter assembly or carefully brush off the
accumulated dust.
Note:
If replacing the filter, remove the foam gasket from the old
filter and place onto the new filter. When placing the new filter into
the slot, ensure that the gasket is correctly aligned.
Refit the filter, close and secure the cabinet door. The unit will
initialise and restart.
Smoke Sensors
The smoke sensors are located under the sensor cover (see Figure
9 displayed earlier in the guide). To access the sensors, follow the
sequence below:
Do
NOT
interchange the devices and do
NOT
alter the rotary
address switch settings on the sensors. If replacing a sensor,
ensure that the address set on the new sensor is the same as on
the sensor being replaced.
LASER SAFETY INFORMATION
The detector contains a Class 1 laser product. Radiation emitted
inside the smoke sensor is completely contained within its housings
and protective covers during all phases of operation.
USB CONNECTION
PC connectivity is provided by an on board USB
B
socket located
centrally between the filter and the sensor (see Figure 9 displayed
earlier in the guide). The USB interface allows access to a range
of additional options, via the PipeIQLT application software, when
connected to a PC. The USB connecting cable should be removed
during normal operation.
1
2
3
PipeIQ
™
LT QUICK START INSTRUCTIONS
Overview of PipeIQLT
The PipeIQLT software program is a convenient and powerful
Windows
®
based application that can be used to quickly and
accurately design pipe networks, generate configuration parameters
for correct set-up and operation, and facilitate commissioning and
monitoring of the performance of FAAST LT Aspiration devices.
PipeIQLT provides a graphical interface on a PC to:
• Develop and verify the performance of pipe network solutions.
• Configure the design parameters to suit local fire codes and
standards.
• Generate Pipe Layouts, BoMs, Configuration and Event Log
Reports.
• Control, Test and Monitor FAAST LT devices.
There is a comprehensive
Help Menu
to guide the user through
the different windows and options. The contents have a detailed
index and a versatile search facility to locate relevant topics.
Minimum System Requirements
Microsoft Windows XP SP3 or Windows 7
1 GB of RAM.
Graphics hardware with 128 MB of memory and support for
OpenGL 2.0 or later.
5 GB of free hard disc space
Installing PipeIQLT
PipeIQLT is supplied on a mass storage device with each
FAAST LT unit, or it can be accessed as a download from www.
systemsensoreurope.com.
To install from the mass storage device
Insert and view the removable storage device. Click on
PipeIQLT
Setup
:
Click
OK
and follow the instructions (see:
PipeIQLT Setup and
Installation Wizard
section below).
To install from the website
Click on the link to PipeIQLT at
www.systemsensoreurope.com.
Click on
PipeIQLT download
. The download security warning will
appear. Select
Save
, then click
OK
.
When the download completes, click
Run
to display the above
dialog box. Click
OK
and follow the instructions (see:
PipeIQLT
Setup and Installation Wizard
section below).
PipeIQLT Setup and Installation Wizard
When the below dialog box appears, click
Setup
to start the wizard: