D200-101-00
5
I56-3888-103
Table 2: Wiring Terminal Designations
(Note - Terminals marked CH2 will only be available on 2 channel
models)
POWERING UP
Using Default Settings
1. Connect a suitable 24VDC supply (complying with European
Standard EN 54-4) to pins 1 and 2 on terminal block T1 (See
Table 2)
2. Check the voltage at the connector. Make sure it is within the
required voltage range.
3. If the voltage is within the specified range, connect the power
connector to the unit.
4. Close and secure the housing door; verify the fan starts up and
air flows out of the exhaust port. The unit takes 1-3 minutes to
initialise and stabilise in normal mode.
Configuring Other Options
To change any of the default options, it will be necessary to
connect the detector to a PC/laptop with the PipeIQLT software
installed; see
USB connection
section later in this guide for
more information on this (and the FAAST LT Advanced Setup and
Control Guide).
Table 3: Relays
No.
Function
1
Ext Power In +
Primary PSU
T1
2
Ext Power In -
Primary PSU
3
Aux Power In +
Not used in default
4
Aux Power In -
Not used in default
5
NC Alarm Relay
CH1
T2
6
C Alarm Relay
CH1
7
NO Alarm Relay
CH1
8
NC Alarm Relay
CH2
T3
9
C Alarm Relay
CH2
10
NO Alarm Relay
CH2
11
NC Fault Relay
CH1
T4
12
C Fault Relay
CH1
13
NO Fault Relay
CH1
14
NC Fault Relay (AUX)
CH2
T5
15
C Fault Relay (AUX)
CH2
16
NO Fault Relay (AUX)
CH2
17
Sounder Output 1 -
47 k-ohm EOL Resistor
T6
18
Sounder Output 1 +
19
Sounder Output 2 -
47 k-ohm EOL Resistor
T7
20
Sounder Output 2 +
21
Configurable Input +
(Reset) Default is active = short circuit
(unsupervised)
T8
22
Configurable Input -
(Reset)
23
NC Pre-Alarm Relay
CH1
T9
24
C Pre-Alarm Relay
CH1
25
NO Pre-Alarm Relay
CH1
26
NC Pre-Alarm Relay
CH2
T10
27
C Pre-Alarm Relay
CH2
28
NO Pre-Alarm Relay
CH2
RELAY
ACTION:
NOTES
ALARM 1 or 2
Set ON when ALARM CONDITION is met
on a channel
Default condition = Level 1. Alarm state is
latched as default. A manual RESET is
necessary to deactivate LED and relay.
PRE-ALARM 1 or 2
Set ON when PRE-ALARM CONDITION
is met on channel.
Default condition = Level 1.
FAULT 1 or 2
When FAULT CONDITION on Ch1 or Ch2
or a common FAULT occurs. Fault is also
indicated when in SERVICE mode and
when the unit is unpowered.
Fault state is not latched (default)
SOUNDER 1 or 2
Set ON when a channel is in ALARM /
PRE-ALARM. Sounder 1 corresponds to
Ch1 and Sounder 2 corresponds to Ch2
Default condition = set on in ALARM.
EXTERNAL RESET
The default setting for the configurable external input is Device
Reset (terminal block T8). A short circuit connection between these
terminals will cause the FAAST LT unit to perform a reset.