background image

D200-101-00

5

I56-3888-103

Table 2: Wiring Terminal Designations

(Note - Terminals marked CH2 will only be available on 2 channel 

models)

POWERING UP
Using Default Settings

1.  Connect a suitable 24VDC supply (complying with European 

Standard EN 54-4) to pins 1 and 2 on terminal block T1 (See 

Table 2)

2.  Check the voltage at the connector. Make sure it is within the 

required voltage range.

3.   If the voltage is within the specified range, connect the power 

connector to the unit.

4.   Close and secure the housing door; verify the fan starts up and 

air flows out of the exhaust port. The unit takes 1-3 minutes to 

initialise and stabilise in normal mode.

Configuring Other Options

To change any of the default options, it will be necessary to 

connect  the  detector  to  a  PC/laptop  with  the  PipeIQLT  software 

installed; see 

USB connection

 section later in this guide for 

more information on this (and the FAAST LT Advanced Setup and 

Control Guide).

Table 3: Relays

No.

Function

Ext Power In + 

 

Primary PSU  

T1

Ext Power In - 

 

Primary PSU  

Aux Power In + 

 

Not used in default 

Aux Power In  - 

 

Not used in default 

NC Alarm Relay  

CH1  

T2

C Alarm Relay  

CH1  

NO Alarm Relay  

CH1  

NC Alarm Relay  

CH2  

T3

C Alarm Relay  

CH2  

10 

NO Alarm Relay  

CH2  

11 

NC Fault Relay  

CH1  

T4

12 

C Fault Relay  

CH1  

13 

NO Fault Relay  

CH1  

14 

NC Fault Relay (AUX) 

CH2  

T5

15 

C Fault Relay (AUX) 

CH2  

16 

NO Fault Relay (AUX) 

CH2  

17 

Sounder Output 1 - 

47 k-ohm EOL Resistor 

T6 

18 

Sounder Output 1 + 

19 

Sounder Output 2 - 

47 k-ohm EOL Resistor 

T7 

20 

Sounder Output 2 +  

21 

Configurable Input + 

(Reset) Default is active = short circuit 

(unsupervised)

T8

22 

Configurable Input - 

(Reset)

23 

NC Pre-Alarm Relay  

CH1  

T9

24 

C Pre-Alarm Relay  

CH1  

25 

NO Pre-Alarm Relay   

CH1  

26 

NC Pre-Alarm Relay  

CH2  

T10

27 

C Pre-Alarm Relay  

CH2  

28 

NO Pre-Alarm Relay  

CH2  

RELAY 

ACTION: 

NOTES

ALARM 1 or 2 

Set ON when ALARM CONDITION is met 

on a channel  

Default condition = Level 1. Alarm state is 

latched as default.  A manual RESET is 

necessary to deactivate  LED and relay. 

PRE-ALARM 1 or 2  

Set ON when PRE-ALARM CONDITION 

is met on channel. 

Default condition = Level 1. 

FAULT 1 or 2 

When FAULT CONDITION on Ch1 or Ch2 

or a common FAULT occurs. Fault is also 

indicated when in SERVICE mode and 

when the unit is unpowered.  

Fault state is not latched (default) 

SOUNDER 1 or 2 

Set ON when a channel is in ALARM / 

PRE-ALARM. Sounder 1 corresponds to 

Ch1 and Sounder 2 corresponds to Ch2 

Default condition = set on in ALARM. 

EXTERNAL RESET

The  default  setting  for  the  configurable  external  input  is  Device 

Reset (terminal block T8). A short circuit connection between these 

terminals will cause the FAAST LT unit to perform a reset.

Summary of Contents for FL0111E

Page 1: ...5o C excluding sounders Configurable Input Activation Time 2s min Relay Contact Ratings 2 0 A 30 VDC 0 5A 30 VAC Environmental Ratings Temperature 10 C to 55 C Relative Humidity 10 to 93 non condensin...

Page 2: ...s fixed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten th...

Page 3: ...allation 1 2 3 4 5 6 Figure 8 Pipe Holes FAAST LT MODEL INLET PIPE HOLE OUTLET PIPE HOLE FL0111E 1 2 or 1 or 2 5 FL0112E 1 2 or 1 or 2 6 FL0122E Channel 1 1 2 or 1 or 2 Channel 2 3 4 or 3 or 4 5 6 Tab...

Page 4: ...EL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR...

Page 5: ...Alarm Relay CH2 11 NC Fault Relay CH1 T4 12 C Fault Relay CH1 13 NO Fault Relay CH1 14 NC Fault Relay AUX CH2 T5 15 C Fault Relay AUX CH2 16 NO Fault Relay AUX CH2 17 Sounder Output 1 47 k ohm EOL Res...

Page 6: ...R DR IFT CO MP EN SA TIO N TEMPERATURE INPUT DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL 1 SMOKE FAULT FAULT POWER LEVEL 2 SMOKE INITIALIZATION ALARM...

Page 7: ...channel unit Upper row Ch1 Lower row Ch2 LOW FLOW ON Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Sensor initialization fault Try to restart device Replace faulty sensor...

Page 8: ...the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and the fault relay will indicate a fault When...

Page 9: ...used to quickly and accuratelydesignpipenetworks generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration...

Page 10: ...mputer in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen an...

Reviews: