EBR Plug-in 

Relay Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING

Please read the 

System Smoke Detector Applications Guide

, which provides 

detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications. This manual is available online at www.systemsensor.com. 
NFPA 72 guidelines should be observed.

NOTICE:

 This manual should be left with the owner/user of this equipment.

IMPORTANT:

 The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector should be cleaned at 
least once a year.

GENERAL DESCRIPTION

The relay base is intended for use with intelligent systems. Refer to the panel 
manual for maximum allowable number of units per loop. 

Form C latching relay contacts are included for the control of an auxiliary 
function.

SPECIFICATIONS

Base Diameter: 

6.85 in (17.4 cm)

Base Height (less sensor): 

1.61 in (4.1 cm)

Operating Temperature Range: 

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com

Operating Humidity Range: 

10% to 93% Relative Humidity (Non-condensing)

Electrical Ratings

Operating Voltage: 

15 to 32 VDC

Standby Current: 

170 µA

Relay Characteristics

Coil:  

2 coil latching

Contact Type: 

Form C

Contact Relay Ratings

Set Time: 

20 msec 

Reset Time: 

250 msec

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

2 A

25 VAC

PF = 0.35 

Non-coded

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

0.46 A

30 VDC

(L/R = 20ms) 

Non-coded

0.7 A

70.7 VAC

PF = 0.35 

Non-coded

0.9 A

125 VDC

Resistive

Non-coded

0.5 A

125 VAC

Resistive

Non-coded

0.3 A

125 VAC

PF = 0.35 

Non-coded

I56-374

1-00

2R

1

2

3

4

5

6

FIGURE 1. TERMINAL LAYOUT:

CO471-04

BASE TERMINALS

NO. FUNCTION

1.  Normal Close
2. Common
3.  Normal Open
4.  Comm. (–)
5.  Comm. (+) In/Out
6.  Comm. (+) Out/In

  

I56-3741-002R 

 

 06-10