The DH500ACDCs are built to operate on 120/240 VAC or 
24  VAC/DC.  Two  form-C  (SPDT)  relay  contacts  are  avail-
able for control purposes. Two LEDs on each detector latch 
on to provide a local alarm indication. Remote alarm indi-
cation is made possible by using the auxiliary alarm output 
(see Figure 5). The duct detector can be tested and alarm 
can be reset by using the correct respective code commands 
from the panel. See panel instructions for details.

Contents Of The Duct Detector Housing Kit

The DH500ACDC Air Duct Detector Housings consist of the 
following items: (See Figure 1.)

1.  Complete housing base and cover assembly.
2.  Two #10 sheet metal mounting screws.
3.  Two sampling tube filters.
4.  One test magnet.
5.  Drilling template.
6.  Two 5/16-inch O-rings.
7.  Two foam gaskets.
8.  Four #6 self-tapping mounting screws for the sampling 

tube.

9.  One filter adapter.
10.  One inlet tube end plug.
11.  Two #10 speed nuts.

NOTE:

  The inlet sampling tube must be ordered separately. 

It must be the correct length for the width of the duct 
where it will be installed. See Table 1 to determine 
the inlet tube required for different duct widths. A 
smoke  detector  head  (1551  ionization  or  2551  for 
photoelectronic) must be ordered separately.

Figure 1:

SAMPLING TUBE

FILTERS

CONDUIT HOLES

DUCT DETECTOR 

HOUSING

PC BOARD 

INSULATOR

DUCT DETECTOR

COVER

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

(SUPPLIED SEPARATELY)

EXHAUST 

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

(SUPPLIED SEPARATELY)

O-RINGS

FOAM

GASKETS

HOUSING

MOUNTING SCREWS

TEST MAGNET

TUBE

END

PLUG

H0309-00

Installation Sequence 

Page

Step 1. Verify duct air flow direction and velocity ............2
Step 2. Drill the mounting holes .....................................2
Step 3. Mount duct housing ...........................................3
Step 4. Install the inlet tube ...........................................3
Step 5. Complete the field wiring....................................5
Step 6. Install the filters .................................................7
Step 7. Perform detector check .......................................7
Step 8. Install the cover .................................................9
Step 9. Perform the final system check (Testing) .............9

Step 1. Verify Duct Air Flow Direction And Velocity

The DH500ACDCA is designed to be used in air handling 
systems  having  air  velocities  up  to  500  feet  per  minute. 
Be sure to check engineering specifications to ensure that 
the  air  velocity  in  the  duct  falls  within  these  parameters. 
If necessary, use a velocity meter to check the air velocity 
in the duct.

Step 2. Drill The Mounting Holes

Remove the paper backing from the drilling template. Affix 
the template to the air duct at the desired mounting loca-
tion. Make sure the template lies flat and smooth on the air 
duct. Center punch hole targets and remove the template. 
Drill the holes as indicated on the template. Slide the two 
speed nuts over the two small holes (Hole A) next to the 
sampling tube bushing holes (Hole B) previously drilled in 
the duct. (See Figure 2.)

Location  of  detectors  mounted  in  or  on  air  ducts  should 
be  at  least  six  duct  widths  downstream  from  any  duct 
openings,  deflection  plates,  sharp  bends,  or  branch  con-
nections.

See  Note  1  below  for  inlet 
sampling tube and detector 
supply information.

Summary of Contents for DH500ACDC

Page 1: ...d in place to initiate an alarm 24V output maximum load is 80 mA auxiliary alarm output maximum load is 20 mA Auxiliary Relay Contacts Minimum contact current must be greater than 500 mA at 24 VDC 10 amps maximum at 30 VDC 10 amps maximum at 250 VAC General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be ...

Page 2: ...SUPPLIED SEPARATELY EXHAUST FILTER ADAPTER DETECTOR BASE INLET SAMPLING TUBE SUPPLIED SEPARATELY O RINGS FOAM GASKETS HOUSING MOUNTING SCREWS TEST MAGNET TUBE END PLUG H0309 00 Installation Sequence Page Step 1 Verify duct air flow direction and velocity 2 Step 2 Drill the mounting holes 2 Step 3 Mount duct housing 3 Step 4 Install the inlet tube 3 Step 5 Complete the field wiring 5 Step 6 Install...

Page 3: ...ets over sam pling tube bushings SCREW HOLES FOR ATTACHING DETECTOR HOUSING TO DUCT FOAM GASKETS EXHAUST TUBE EXTENSION BUSHING DUCT DETECTOR HOUSING O RINGS MOUNTING SCREWS SAMPLING TUBE BUSHING H0117 00 INLET TUBE END PLUG AIR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Step 4 Install The Inlet Tube The inlet tube shown in Figure 3 is identified by a series of air inlet holes ...

Page 4: ...ION EXHAUST TUBE INLET TUBE INLET TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 4 Tube mounting configurations with varying air flow direction and orientation of detector housing Vertical as well as horizontal mounting is acceptable H0109 00 Install the inlet tube as follows ...

Page 5: ...mping plate screw The DH500ACDC is built for 120 240 VAC or 24 VAC DC to operate auxiliary functions See Figure 5A for operating and wiring details Notes on Jumper Wire J5 See Figure 5A 1 When the detector is used in a 4 wire application relay circuit is being used to control fans dampers etc jumper wire J5 located between the two terminal strips on the printed circuit board must be cut to insure ...

Page 6: ...N THE DH500ACDC TEST RESET NOT USED 4 5 6 7 8 9 10 11 12 13 14 15 16 17 COMMUNICATION LINE FROM PANEL COMMUNICATION LINE TO REST OF SYSTEM NOTE FOR POWER SUPPLY WIRES POLARITY IS NOT IMPORTANT ALWAYS RUN AUXILIARY CONTROL WIRING IN SEPARATE CONDUIT J5 K2 1 2 3 24 VAC 24 VDC 240 VAC 120 VAC NOTE JUMPER WIRE J5 IS REQUIRED TO BE INTACT FOR 2 WIRE APPLICATIONS ONLY CUT J5 FOR 4 WIRE POWER SUPERVISION...

Page 7: ...n The RTS451 RTS451KEY Remote Test Station facili tates testing of the duct detector alarm capability The DH500ACDC duct detector cannot be reset by the RTS451 RTS451KEY It must be reset at the system con trol panel To install the RTS451 RTS451KEY test coil connect the device as shown in Figure 9 Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in...

Page 8: ... DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD Figure 7 Testing detector alarm Figure 8 Detector head removal H0244 00 H0243 00 DETECTOR HEAD TEST COIL Figure 9 RTS451 RTS451KEY Test Coil Installation H0245 0 It is recommended that a permanent Detector Test Log be set up and maintained with a record for each individual smoke dete...

Page 9: ...moval easier 10 Carefully pull the screen out of the cover 11 Clean the screen thoroughly with a soft brush or vacu um cleaner replacement screens part no RS14 12 Brush or vacuum the inside of the cover The cover may then be blown out using clean compressed air 13 Vacuum the sensing chamber before using clean compressed air to loosen and blow out any remaining debris 14 Press the screen back into ...

Page 10: ...d need to come directly from the con trol panel or by using control modules 2 The duct control circuitry auxiliary relay contacts and auxiliary alarm output may change states if the sensor is tested and the LED is turned on for more than 4 sec onds If the LED is latched on for less than 4 seconds the control circuitry of the DH500ACDC will NOT oper ate 3 The panel must not poll the same unit for m...

Page 11: ...send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio D500 07 00 11 I56 432 11R Please refer to insert for the Limitations of Fire Alarm Systems Three Year Limited Warranty Avenue St Charles IL 60174 Please include a note describing the mal function and suspected cause of failure The Company shall not be obli gated to repair or replace units which are foun...

Page 12: ...___ _ __________ _______________________ _______ _ _________ _______ _ __________ _______________________ _______ _ _________ _______ _ __________ _______________________ _______ _ _________ _______ _ __________ _______________________ _______ _ _________ _______ _ __________ _______________________ _______ _ _________ _______ _ __________ _______________________ _______ _ _________ _______ _ ____...

Reviews: