System Sensor DH400ACDCIHT Installation And Maintenance Instructions Manual Download Page 8

[5] Duct Detector Maintenance And Test Procedures

Test and maintain duct detectors as recommended in NFPA 
72.  The  tests  contained  in  this  manual  were  devised  to 
assist  maintenance  personnel  in  verification  of  proper 
detector operation. 

Before conducting these tests, notify the proper authorities 
that the smoke detection system will be temporarily out of 
service. Disable the zone or system under test to prevent 
unwanted alarms.

After conducting these tests, record the appropriate infor-
mation in the Detector Test Log at the end of this manual.

[5.1] Smoke Entry Tests
[5.1.1] Air Flow

To verify sufficient sampling of ducted air, use a manom-
eter  to  measure  the  differential  pressure  created  from  air 
flow across the sampling tubes. The pressure should mea-
sure no less than 0.01 inches of water and no greater than 
1.20 inches of water.

[6.1.2] Smoke Response

To  determine  if  smoke  is  capable  of  entering  the  sens-
ing  chamber,  visually  identify  any  obstructions.  Plug  the 
exhaust  and  inlet  tube  holes  to  prevent  ducted  air  from 
carrying  smoke  away  from  the  detector  head,  then  blow 
smoke  such  as  cigarette,  cotton  wick,  or  punk  directly  at 
the head to cause an alarm. REMOVE THE PLUGS AFTER  
TESTING  OR  THE  DETECTOR  WILL  NOT  FUNCTION 
PROPERLY.

[6.1.3] Filter Replacement

The filters do not substantially affect smoke behavior even 
when they are up to 90% clogged. Quarterly visual inspec-
tion is usually often enough to determine if filters should 
be  replace  because  only  a  high  percentage  of  contamina-
tion affects duct detector performance.

Figure 9. Wiring diagrams for optional accessories (see Figure 7 for APA451 wiring diagram):

ALARM SIGNAL (+)

AUX POWER (–)

5

6

(+)

(–)

DUCT DETECTOR

DH400ACDC

PA400 (OPTIONAL)

AUDIBLE ALERT

ALARM SIGNAL (+)

AUX POWER (–)

5

6

(+)

(–)

DUCT DETECTOR

DH400ACDC

RA400Z (OPTIONAL)

REMOTE (LED)

ANNUNCIATOR

RED

ALARM SIGNAL (+)

AUX POWER (–)

5

6

1

2

DUCT DETECTOR

DH400ACDC

RTS451/RTS451KEY

(OPTIONAL) REMOTE 

TEST STATION

R

E

D

5

3

4

3 RESET

TEST

4

FIELD

INSTALLED

JUMPER

RESET (–)

TEST (–)

H0242-00

[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble

Standby-   Check for the presence of the blinking red LEDs 

(blinks  about  every  10  seconds)  through  the 
housing cover.  If the APA451 accessory is used, 
its green Power LED should be illuminated con-
tinuously.

 
Trouble-    If  the  detector  LEDs  do  not  blink  or  if  the 

APA451 Power LED is not illuminated, the detec-
tor lacks power (check wiring, panel, or power 
supply), the head is missing (install), or the unit 
is defective (return for repair).

Test-         The trouble condition can be caused intention-

ally  to  verify  correct  operation  of  the  system. 
Remove  power  to  the  unit,  remove  the  detec-
tor  head  (see  Figure  11),  or  place  the  M02-04-
01  magnet  into  the  Reset  locator,  as  shown  in  
Figure 10. These actions should cause a trouble 
condition  locally  and  at  the  system  control 
panel.

D400-64-00                                                                                              8                                                                                              I56-991-08R

Summary of Contents for DH400ACDCIHT

Page 1: ...Fig 11 Detector Head Removal 9 Fig 12 RTS451 RTS451KEY Test Coil Installation 10 Fig 13 Ion Head Exploded View 10 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in th...

Page 2: ...4 7 Perform detector check 5 4 8 Install the cover 8 4 1 Verify Duct Air Flow Direction And Velocity Model DH400ACDCIHT detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary use a velocity meter to check the air ...

Page 3: ...o the sampling tube holes as indicated in Figure 4 Table 1 Inlet tubes required for different duct widths Outside Duct Width Inlet Tube Required 1 to 2 ft ST 1 5 2 to 4 ft ST 3 4 to 8 ft ST 5 8 to 12 ft ST 10 4 4 1 Installation For Ducts Less Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct directly opposite the hole already cut for the inle...

Page 4: ...TION FLANGE H0108 02 AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations wi...

Page 5: ...l strip with clamp ing plates Wiring connections are made by stripping about 3 8 inch of insulation from the end of the wire sliding the bare end under the plate and tightening the clamping plate screw The detector may be wired for interconnection to UL listed control panels or for stand alone service per NFPA 90A Refer to the wiring diagrams of Figures 6 7 and 8 to select the appropriate circuit ...

Page 6: ... IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDCIHT LAST DETECTOR IN THE LOOP DH400ACDCIHT EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY...

Page 7: ...S REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM I...

Page 8: ...ke behavior even when they are up to 90 clogged Quarterly visual inspec tion is usually often enough to determine if filters should be replace because only a high percentage of contamina tion affects duct detector performance Figure 9 Wiring diagrams for optional accessories see Figure 7 for APA451 wiring diagram ALARM SIGNAL AUX POWER 5 6 DUCT DETECTOR DH400ACDC PA400 OPTIONAL AUDIBLE ALERT ALARM...

Page 9: ...head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD H0243 00 H0244 00 5 2 3 Sensitivity Tests 5 2 3 1 MOD400R Sensitivity Test After verification of alarm capability use the MOD400R test module with a voltmeter to check detector sensitivity as described in t...

Page 10: ...H400ACDCIHT Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization smoke detector for separately powered systems or stand alone systems Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke Environmental Limits Operating Temperature 32 to 158 F 0 to 70 C Storage Temperature 22 to 158 F 30 to 70 C Humidity 10 to 93 R H non co...

Page 11: ...ements This enclosure provides protection in outdoor installations against rain sleet and snow or in indoor installations against dripping water NOTE The DH400 OE 1 is designed solely for the use with System Sensor model DH400ACDCIHT high temperature duct smoke detector Preparation Locate the two adhesive backed gaskets packaged with the enclosure NOTE In order to provide effective sealing these g...

Page 12: ... repair or replace units which are found to be defective because of damage unrea sonable use modifications or alterations occurring after the date of manu facture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or fault Some st...

Reviews: