[4.3] Secure The Detector Housing To The Duct

Remove the duct housing cover. Slide the foam gaskets over 
the tube bushings as shown in Figure 2. Make sure the two 
small holes in the gaskets line up with the two base mount-
ing holes. Put one 5/16-inch O-ring over each of the two 
#10 sheet metal screws. Use the two sheet metal screws to 
screw the detector housing to the duct. CAUTION: Do not 
overtighten the screws.

Figure 2. Installation of foam gaskets over sampling 
tube bushings:

  

SCREW HOLES FOR ATTACHING

DETECTOR HOUSING TO DUCT

FOAM GASKETS

EXHAUST TUBE

(EXTENSION BUSHING)

DUCT DETECTOR

HOUSING

O-RINGS

MOUNTING

SCREWS

INLET SAMPLING

TUBE BUSHING

H0238-00

Figure 3. Speed nut mounting location:

HOLE B

HOLE A

DUCT

WALL

SPEED

NUT

H0116-00

[4.4] Install The Inlet

The inlet tube (shown in Figure 4) is identified by a series 
of air inlet holes on the tube. This tube must be purchased 
separately. Order the correct length, as specified in Table 1, 
for width of the duct where it will be installed. The exhaust 
tube is molded into the base of the duct housing, and the 
A2440-00 Exhaust Tube Extension is available as an acces-
sory in those cases where the molded exhaust port does not 
extend at least 2 inches into the duct.

The inlet tube is always installed in the centermost hous-
ing  bushing,  with  air  inlet  holes  facing  into  the  air  flow. 
To assist proper installation, the tube’s mounting flange is 
marked with arrows. Make sure the inlet tube is mounted 
so that the arrows point into the air flow. Figure 5 shows 
the various combinations of tube mounting configurations 
with respect to air flow. 
 

Mounting  the  detector  housing  in  a  vertical  orientation 
is acceptable, provided that the air flows directly into the 
sampling tube holes as indicated in Figure 4.

Table 1. Inlet tubes required for different duct 
widths:

       Outside Duct Width              Inlet Tube Required

                1 to 2 ft.                                  ST-1.5
                2 to 4 ft.                                   ST-3
                4 to 8 ft.                                   ST-5
               8 to 12 ft.                                  ST-10

[4.4.1] Installation For Ducts Less Than 8 Feet Wide

1. 

If the tube is longer than the width of the air duct,

 drill 

a  3/4-inch  hole  in  the  duct  directly  opposite  the  hole 
already cut for the inlet tube. 

If the tube is shorter than 

the  width  of  the  air  duct,

  install  the  end  plug  into  the 

inlet tube as shown in Figure 4. Sampling tubes over 3 
ft. long must be supported at the end opposite the duct 
detector.

2. Slide  the  tube  into  the  centermost  housing  bushing. 

Position  the  tube  so  that  the  arrows  point  into  the  air 
flow. 

3. Secure the tube flange to the housing bushing with two 

#6 self-tapping screws.

4. For tubes longer than the width of the air duct, the tube 

should  extend  out  of  the  opposite  side  of  the  duct.  If 
there  are  more  than  2  holes  in  the  section  of  the  tube 
extending out of the duct, select a different length using 
Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1 to 2 inches of the tube extend 
outside  the  duct.  Plug  this  end  with  the  end  plug  and 
tape  closed  any  holes  in  the  protruding  section  of  the 
tube. Be sure to seal the duct when the tube protrudes.

WARNING

In no case should more than 2 air inlet holes be cut off the 
tube.  There  must  be  a  minimum  of  10  holes  in  the  tube 
exposed to the air stream.

[4.4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

  To  install  inlet  tubes  in  ducts  more  than  8  feet 

wide,  work  must  be  performed  inside  the  air 
duct.  Sampling  of  air  in  ducts  wider  than  8  feet  
is accomplished by using the ST-10 inlet sampling 
tube.  If  the  tube  is  shorter  than  the  width  of  the 
air duct, install the end plug into the inlet tube as 
shown  in  Figure  4  and  support  the  end  opposite 
the duct detector.

D400-64-00                                                                                              3                                                                                              I56-991-08R

Summary of Contents for DH400ACDCIHT

Page 1: ...Fig 11 Detector Head Removal 9 Fig 12 RTS451 RTS451KEY Test Coil Installation 10 Fig 13 Ion Head Exploded View 10 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in th...

Page 2: ...4 7 Perform detector check 5 4 8 Install the cover 8 4 1 Verify Duct Air Flow Direction And Velocity Model DH400ACDCIHT detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary use a velocity meter to check the air ...

Page 3: ...o the sampling tube holes as indicated in Figure 4 Table 1 Inlet tubes required for different duct widths Outside Duct Width Inlet Tube Required 1 to 2 ft ST 1 5 2 to 4 ft ST 3 4 to 8 ft ST 5 8 to 12 ft ST 10 4 4 1 Installation For Ducts Less Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct directly opposite the hole already cut for the inle...

Page 4: ...TION FLANGE H0108 02 AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations wi...

Page 5: ...l strip with clamp ing plates Wiring connections are made by stripping about 3 8 inch of insulation from the end of the wire sliding the bare end under the plate and tightening the clamping plate screw The detector may be wired for interconnection to UL listed control panels or for stand alone service per NFPA 90A Refer to the wiring diagrams of Figures 6 7 and 8 to select the appropriate circuit ...

Page 6: ... IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDCIHT LAST DETECTOR IN THE LOOP DH400ACDCIHT EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY...

Page 7: ...S REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM I...

Page 8: ...ke behavior even when they are up to 90 clogged Quarterly visual inspec tion is usually often enough to determine if filters should be replace because only a high percentage of contamina tion affects duct detector performance Figure 9 Wiring diagrams for optional accessories see Figure 7 for APA451 wiring diagram ALARM SIGNAL AUX POWER 5 6 DUCT DETECTOR DH400ACDC PA400 OPTIONAL AUDIBLE ALERT ALARM...

Page 9: ...head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD H0243 00 H0244 00 5 2 3 Sensitivity Tests 5 2 3 1 MOD400R Sensitivity Test After verification of alarm capability use the MOD400R test module with a voltmeter to check detector sensitivity as described in t...

Page 10: ...H400ACDCIHT Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization smoke detector for separately powered systems or stand alone systems Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke Environmental Limits Operating Temperature 32 to 158 F 0 to 70 C Storage Temperature 22 to 158 F 30 to 70 C Humidity 10 to 93 R H non co...

Page 11: ...ements This enclosure provides protection in outdoor installations against rain sleet and snow or in indoor installations against dripping water NOTE The DH400 OE 1 is designed solely for the use with System Sensor model DH400ACDCIHT high temperature duct smoke detector Preparation Locate the two adhesive backed gaskets packaged with the enclosure NOTE In order to provide effective sealing these g...

Page 12: ... repair or replace units which are found to be defective because of damage unrea sonable use modifications or alterations occurring after the date of manu facture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or fault Some st...