background image

[5] DETECTOR INSTALLATION
[5.1] VERIfy DUCT AIR fLOw DIRECTION AND VELOCITy

Model D2-AUS detectors are designed to be used in air handling systems hav-
ing air velocities of 0.5 to 20.3 m/sec. Duct widths from 15.2 cm to 3.7 m can 
be accommodated. Be sure to check engineering specifications to ensure that 
the air velocity in the duct falls within these parameters. If necessary, use a 
velocity meter (anemometer) to check the air velocity in the duct.

[5.2] DETERMINE MOUNTINg LOCATION 
AND CONfIgURATION

On ducts wider than 45.7 cm it is recommended that the detector be mounted 
downstream of a bend, obstruction in the duct, or the supply or return air inlet. 

Exception:  Installation  of  duct  detectors  can  be  on  or  within  a  commercial 
packaged  rooftop  heating  and  air-conditioning  system,  fire/smoke  dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.

Once a suitable location is selected, determine if the detector is to be mounted 
in  a  side-by-side  “rectangular”  configuration  or  a  top-over-bottom  “square” 
configuration as shown in 

Figure 2

. If mounting in the square configuration, 

remove the rear attachment screw, rotate the unit at hinge, and replace the 
screw into the new attachment hole as shown in 

Figure 2

. Do NOT remove 

the hinge screw during this process. Final installation approval shall be based 
upon passing section 10.4.2 and 10.4.4 tests.

fIgURE 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[5.3] DRILL ThE MOUNTINg hOLES

Remove the paper backing from the mounting template supplied. Affix the tem-
plate to the duct at the desired mounting location. Make sure the template lies 
flat and smooth on the duct. 

[5.3.1] fOR RECTANgULAR SIDE-By-SIDE MOUNTINg CONfIgURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 3.5 cm diameter holes using 
a hole saw or punch. Drill 4.0 mm diameter holes at target “B” centers.

[5.3.2] fOR SqUARE TOP-OVER-BOTTOM MOUNTINg CONfIgURATION:

Center  punch  at  (4)  target  centers:  (2)  “A”  for  sampling  tubes  and  (2)  “C” 
for the square configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 3.5 cm diameter holes us-
ing a hole saw or punch. Drill 4.0 mm diameter holes at target “C” centers. If 
desired, drill an additional 4.0 mm hole at the location of one of the mounting 
tabs on the lower housing.

[5.4] SECURE ThE DUCT DETECTOR TO ThE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION: Do not overtighten the screws.

SS-300-023 

I56-3641-001R

[4] fIgURE 1. ExPLODED VIEw Of DUCT SMOkE DETECTOR COMPONENTS:

MAGNET TEST LOCATION

SENSOR MODULE COVER

TERMINAL HOUSING 

MODULE COVER

SAMPLING TUBE

EXHAUST TUBE

SENSOR HEAD

WIRING TERMINALS

(sold seperately)

H0574-01

Summary of Contents for D2-AUS

Page 1: ...revent the detector from activating when smoke is present in the air duct 2 General Description Smoke introduced into the air duct system will be distributed throughout the entire building Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct Model D2 AUS Duct Smoke Detector utilizes photoelectric technology for the detection of smoke This detecti...

Page 2: ...and 10 4 4 tests Figure 2 REMOVE SCREW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center ...

Page 3: ...ither side of the 1000Ω resistor Allow unit to warm up for 15 seconds With both HIGH and LOW pressure ports open to ambient air measure and record the voltage drop across the 1000Ω resistor measurement 1 4 00 volts is typical Using flexible tubing and rubber stoppers connect the 6 Sampling Tube Installation 6 1 Sampling Tube Selection The sampling tube must be purchased separately Order the correc...

Page 4: ... being used before wiring the detector loop 8 1 Wiring Instructions The D2 AUS detectors are designed for easy wiring The housing provides a terminal strip with clamping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 6 below for system wiring 9 DETECTOR STATUS INDICATION Detector status is indicated by the L...

Page 5: ... m sec Spray aerosol smoke into the duct through the 6 4 mmhole for five seconds Wait two minutes for the duct smoke detector to alarm If the duct smoke detector alarms air is flowing through the detec tor Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber and reset the duct smoke detector Use duct tape to seal the aerosol smoke entry hole Aerosol smoke c...

Page 6: ...nction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss o...

Reviews: