The JA-85ST Wireless combined smoke and heat detector 

The JA-85ST Wireless combined smoke and heat detector 

1 / 2 

MLW55605 

 

The  JA-85ST  is  a  wireless  component  of  the  JABLOTRON 

ALARMS 

OASIS

 alarm system. It is used to detect fire hazards in 

the interior of residential or commercial buildings. The detector can 
be  installed  in  mobile  homes  or  caravans.  The  product  is  not 
designed  to  be  installed  in  industrial  premises.  The  JA-85ST 
detector uses wireless communication and it is powered with three 
AA batteries.

 

The  detector  indicates  a  fire  hazard  using  the  built-in  LED 

indicator and acoustic signalling

.

  

The JA-85ST consists of two independent detectors – an optical 

smoke  detector  and  a  heat  detector.  The  optical  smoke  detector 
works  on  the  principle  detection  of  scattered  light.  It  is  very 
sensitive to large dust particles which are present in dense smoke. 
It is less sensitive to smaller particles generated by the combustion 
of liquids such as alcohol. That is why the fire detector also contains a 
built-in heat detector which has a slower reaction but is much better at 
detecting fire which generates only a small amount of smoke.

 

Detector range and location 

The  smoke  detector  must  be  installed  so  that  any smoke  easily 

drifts into the detector owing to natural thermal currents, e.g. on the 
ceiling. It is suitable for residential buildings but not suitable for free 
spaces,  outdoor  environments  or  interiors  with  extremely  high 
ceilings  (above  5  m)  where  fire  by-products  can  disperse  over  a 
large area – the smoke would not reach the detector position. 

The  detectors should  be  installed  by  a  trained  technician  with  a 

valid manufacturer’s certificate. 

Detectors  should  be  installed  in  the  building  according  to  the 

project documentation. If such documentation is not available, their 
position  should  comply  with  the  effective  standards  for  fire  alarm 
signalling systems. 

The detector must always be placed in the section leading to the 

exit of the building (escape route), see

 Fig. 1

. If the building has a 

floor area greater than 150 m

2

, installation of an additional detector 

in some other suitable place is required, see 

Fig.2

.  

 

 

Fig 1 

Fig 2 

 

 
1. kitchen,  
2. living room,  
3. – 6. bedrooms  

y

 / 

basic coverage 

 

{

{

 

 

recommended 

coverage

 

Fig 3 

 

0,9 m

 

Fig 4 

Fig 5

 

 centre of the room, best location 

 acceptable location

 

 

 

In  multi-storey  flats  and  family  houses  the  detector  should  be 

installed  above  the  stairs.  It  is  recommended  to  place  additional 
detectors in rooms where people sleep. See 

Fig 3

.  

Installation on level ceilings 

Place the detector in the centre of the room if possible. The 

detector must not be recessed into the ceiling due to the possible 
existence of a cool air layer on the ceiling. Never place the detector 
in the corner of the room (always keep at least 

 

0.5 m distance from the corner - see Fig 4). There is an insufficient 
circulation of air in the corners.

 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5.  

Walls, partitions, barriers and lattice ceilings 

The JA-85ST detector must not be installed closer than 0.5 m 

from  any  wall  or  partition. 

A narrow room with a width of less than 

1.2m requires the detector(s) to be placed at a distance of at least one 
third of the room’s width away.  In  a  case  when  a  room  is  separated 
into  sections  with  furniture,  racks  or  semi  partition  walls  which  do 
not reach the ceiling, the space is considered to be fully separated 
if the gap between the top of these and the ceiling does not exceed 
0.3 m

.

  A free space of at least 0.5 m is required under and around the 

detector. Any irregularities of the ceiling (e.g. girders) exceeding 5 % of 
the ceiling height should be considered a wall and the above mentioned 
limitations should apply.  

Ventilation and air circulation 

The detectors must not be installed directly by ventilation or air 

conditioning  vents.

  In  the  case  of  air  being  supplied  through  a 

perforated  ceiling,  each  detector  must  be  placed  so  that  no 
perforation hole occurs within 0.6 m of the detector. 

Avoid installing the detector in the following locations:

 

x

  places  with  poor  air  circulation  (niches,  corners,  apexes  of  A-

shaped roofs, etc.) 

x

  places exposed to dust, cigarette smoke or steam 

x

  places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

x

  in kitchens and other cooking places (because steam, smoke or oily 

fumes can cause false alarms or reduce detector sensitivity). 

x

  beside  fluorescent  lights  or  energy-saving  light  bulbs  (electrical 

interference can cause a false alarm) 

x

  in areas with lots of small insects 

 

Warning: 

Most false alarms are caused by improper detector 

location.

 

See CEN/TS 54-14 standard for detailed installation guidelines.

 

Installation 

When  installing  the  detector,  abide  by  the  procedures 
recommended in the previous paragraphs. 

 

 

Fig 1: 1 – detector cover opening; 2 – detector cover closing; 3 – optical 

status signalling; 4 – arrow showing where to insert the detector;  

5 – production code; 6 – configuration terminals; 7 – battery holders; 

 8 – button for test 

 

1. 

Open the detector cover

, by turning it anti-clockwise (1)

 

 

2. 

Attach the plastic base

 to the selected place using screws 

 

3. 

Use the terminals (6) to set the required detector function 

– 

see the table below  

ON

 

Siren disabled

 

OFF 

Smoke (EN 14604 or 
EN 54-7) or heat (EN 
54-5) 

OFF 

Siren enabled 
(EN 14604) 

OFF 

ON 

Memory disabled 

OFF 

Smoke  only  (EN  14604 
or EN 54-7) (not heat) 

OFF 

Memory enabled 
(EN 54-7 and EN 54-
5) 

ON 

 

ON

OFF

 

ON 

Heat  only  (EN  54-5) 
(not smoke) 

OFF 

ON 

Both  smoke  and  heat 
(both  conditions  at  the 
same time)

 

ON 

ON 

Immediate alarm

 

OFF 

Fire alarm

 