background image

The JA-85ST Wireless combined smoke and heat detector 

The JA-85ST Wireless combined smoke and heat detector 

2 / 2 

MLW55605 

 

Caution: When the detector is installed in caravan trailers, use only 
the “smoke only“ or “both smoke and heat” settings. 

4.  Proceed according to the control panel installation manual.  
         Basic procedure: 

a. 

Switch on the enrollment mode in the control panel. 

 

b. When you insert all batteries into the detector, an enrollment code 

is sent to the system – its sending is confirmed with a short flash 
of the LED indicator (3). 

c. 

The  control  panel  confirms  the  enrollment  with  a  flashing  of  the 
“A“ LED on the system keypad at the corresponding position. 

 

Note: 

 

The detector can also be enrolled into the system by entering its 
production code (5) in the O-Link program. (Enter the last 8 digits 
under the bar code).

 

5. 

Insert the detector into the plastic base.

 The detector can be 

inserted  into  the  base  in  one  position  only.  It  is  marked  with 
arrows  (4)  on 

both

  plastic  parts.  Close  the  detector  cover  by 

turning it clockwise (2). 

 

 

Note: 

Detector  cover  closing  is  blocked unless  all  3  batteries 

are inserted! 
The  mounting  base must not  be  replaced by  bases  meant for 
detectors  without  the  test  button  consisting  of  pressing  the 
body of the detector.

 

Detector setting 

The detector properties can be set in the 

Devices

 window in the 

O-Link

 program and with the configuration terminals. 

The 

Reaction

 option in the 

Devices

 window allows you to set the 

type  of  reaction  of  the  system  to  the  activation  of  the  enrolled 
detector.  The  configuration  terminals  on  the  detector  PCB 
determine other reactions:

 

SIR 

enables deactivating the built-in siren.

 

MEM

 alarm memory signalling – if enabled, the detector LED 

remains active for an additional 24 hours Signalling can also be 
terminated by pressing the detector body against the base.

 

SMOKE and TEMP

 the combination of these terminals defines 

whether the detector will react to smoke and heat. 

INST

 if a reaction different than 

NATURAL 

is set in the

 

O-Link

 

program, the control panel will react as set in the program. 

Fire alarm 

A  fire  alarm 

is  signalled  acoustically  and  optically  according  to 

the settings. 

When  the  conditions  for  fire  alarm  triggering  are  met  (smoke  is 

detected  in  the  room,  the  alarm  temperature  is  reached,  or  both 
conditions  are  met),  the  detector  signals  the  danger  by  sounding 
the siren and  quick flashing the LED indicator (3). 

Silencing the siren during an alarm:

 The siren can be silenced 

by  pressing  the  detector  body  against  the  base.  The  siren  is 
inactive  for  10  minutes.  If  the  detector  still  detects  smoke  or  heat 
then, the siren is reactivated. 

When the need arises (e.g. in the case of a detector failure), it is 

possible to postpone siren reactivation by up to 12 hours. This can 
be  done  by  pressing  the  detector  again  for  5  s  after silencing  the 
siren. When the  detector chirps, you  have  to  release  the  pressure 
within  1  s.  The  switchover  to  the  postponed  siren  mode  is 
confirmed  with  5  chirps.  The  detector  LED  flashes  all  the  time 
during the postponement. 

Alarm memory: 

 If it is enabled, alarm indication continues even 

when  the  smoke  clears  or  when  the  temperature  decreases.  The 
slow-flashing  indication  lasts  24  hours  unless  it  is  terminated  by 
pressing the detector body. 

Tamper alarm:

 When the detector cover is opened, the detector 

sends a tamper signal.

 

Detector testing and maintenance 

The  detector  should  be  tested  at  least  once  per  month.

  To 

test the detector press the detector against the base and wait until 
the LED indicator switches on. The LED flashing signals switchover 
to  test  mode.  The  LED  flashes  for  the  whole  duration  of  the  test. 
When  the  test  is  complete,  the  LED  switches  off.  The  detector  then 
signals the result. If the detector beeps once, the test has been done 
successfully. If a failure is discovered, the LED flashes and beeps 

three times. If the battery is low, there is no acoustic signalling but 
just one flash when the test is completed.  

The result of a test is sent to the control panel. If the detector is 

OK then the LCD keypad shows the text “Test OK”. When there is a 
problem or fault then the keypad shows the text “Fault”. 

The complete functioning of the detector can be tested with a test 

spray (e.g.. SD- TESTER) ) or hot air (e.g a hair dryer). 

If the control panel is not in the SERVICE/MAINTENANCE mode, 

a fire alarm is triggered. 

Warning: never test the detector with fire.

 

 

Fault indication 

The detector checks its functioning. If it discovers a fault, it chirps 

and  flashes  the  LED  three  times  and  then  flashes  briefly  three 
times every 30 s.  

A detector test can  be carried out when a fault is signalled. To test 

the detector, press its whole body against the base. During the test the 
detector  checks  whether  there  is  still  a  fault.  The  red  LED  flashes 
during the testing. When the test is completed, the LED stops flashing 
and then signals the result. A persistent fault is signalled by 3 flashes 
and 3 beeps. If the fault has been fixed, the detector chirps briefly. 

If you have not managed to fix the fault, the detector must be sent to 

a service centre. 

Battery replacement 

The  detector  checks  the  battery  status  and  if  the  batteries  are 

running low, the detector signals that they need replacing by short 
flashes  repeated  every  30  s.  The  information  is  also  sent  to  the 
control panel. Replace the batteries as soon as possible. 

Exchange procedure: 

If  the  detector  is  already  enrolled  to  the  system  it’s 
necessary to enter service / maintenance mode 

open the detector  

remove the old batteries 

press and hold the test button (8) until the LED (3) goes ON 

when the LED goes OFF , it shows the capacitors inside the 
detector have been discharged 

insert some new batteries 

Always  replace  all  three  batteries  with  the  same  type  and 
manufacturer. 
Use only high-quality 1.5 V AA alkaline batteries. 
  
 

Do not throw used batteries into ordinary household waste. 

Deposit them at authorized collection points.

 

Technical specifications 

Power 

3 x Alkaline battery  type LR6 (AA) 1.5 V / 2.4 Ah 

 

Please note: Batteries are not included 

Typical lifetime  

approx. 3 years 

Smoke detection 

optical light scattering 

Smoke detector sensitivity 

 m = 0.11 - 0.13 dB/m 

Pursuant to EN 14604, EN 54-7 
Heat detection 

class A1 according to EN 54-5 

Alarm temperature 

+ 60 °C to +65 °C 

Communication band 

 868.5 MHz, Oasis protocol 

Communication range 

approx. 300 m (unrestricted area) 

Dimensions 

diameter 126 mm, height 50 mm 

Weight 

150 g 

Operating temperature range 

-10 to +65°C 

Also complies with  

EN 54-25,  

 

ETSI EN 300 220, EN 60950-1, EN 50130-4 and EN 55022, 

Can be operated according to 

ERC REC 70-03 

 

           

 

14 

1293-CPR-0392

 

  1293 

 

JABLOTRON ALARMS a.s. hereby declares that the JA-85ST is in 
a  compliance  with  the  relevant  Union  harmonisation  legislation: 
Directives No: 2014/53/EU, 2014/35/EU, 2014/30/EU, 2011/65/EU. 
The  original  of  the  conformity  assessment  can  be  found  at 
www.jablotron.com - Section Downloads.

 

 

Note:

  Although  this  product  does  not  contain  any  harmful 

materials  we  suggest  you  return  the  product  to  the  dealer  or 
directly to the producer after use. 

 

 

Reviews: