background image

D450-16-01

2

I56-659-06

Installation Guidelines

All wiring must be installed in compliance with all appli-
cable local codes and any special requirements of the local
authority having jurisdiction, using the proper wire sizes.
The conductors used to connect smoke detectors to control
panels and accessory devices should be color-coded to re-
duce the likelihood of wiring errors. Improper connections
can prevent a system from responding properly in the event
of a fire.

For signal wiring (the wiring between interconnected de-
tectors), it is recommended that the wire be no smaller
than 18 gauge (1.0 square mm). However, wire sizes up to
12 gauge (3.3 square mm) can be used with the base. The
use of twisted pair wiring or shielded cable for the power
(+ and -) loop is recommended to minimize the effects of
electrical interference.

If shielded cable is used, the shield connection to and from
the detector must be continuous by using wire nuts, crimp-
ing, or soldering, as appropriate, for a reliable connection.

Alarm system control panels have specifications for allow-
able loop resistance. Consult the control panel specifica-
tions for the total loop resistance allowed  before wiring the
detector loops.

Wiring Instructions

WARNING

The base uses a latching relay that can change states if it is
subjected to mechanical shocks or jarring. As a result, even
though relay contacts are in the open state when the base is
shipped from the factory, the contacts may have closed
during shipment.

Connecting an auxiliary control circuit to closed relay con-
tacts can cause an unexpected, and possibly dangerous, ac-
tivation of that circuit. Therefore, do NOT connect an
auxiliary control circuit to the relay contacts (terminals 1,
2, and 3) before ensuring that the relay contacts are in their
open state. Ensure that the contacts are open by applying
power to the bases WITHOUT the sensor heads installed.

Make wiring connections by stripping about 

3

/

8

" (10 mm)

of insulation from the end of the wire. Then, slide the wire
under the clamping plate and tighten the clamping plate
screw.

SCREWS (NOT
SUPPLIED)

BOX (NOT
SUPPLIED)

DETECTOR
BASE

SNAP ON 
DECORATIVE
RING

Figure 1. Mounting the base to an electrical box:

A78-1175-21

Wire the normally open (NO) line to terminal 2 (see Figure
2). Insert the normally closed (NC) line of the relay to ter-
minal 1 and the relay common line to terminal 3. Wire the
communication lines in (+) and out (+)to terminal 4. In-
sert the communication line in (–) and out (–) to terminal
5. Terminal 6 is for shielded cable only (see Figure 2). If
shielded cable is used, the shield connection to and from
the detector must be continuous by using wire nuts,
crimping, or soldering to ensure a reliable connection. If
shielded cable is not used, leave terminal 6 in the screwed-
down position.

Check the zone wiring of all bases in the system before in-
stalling detector heads. This includes checking the wiring
for continuity, correct polarity, ground fault testing, and
performing a dielectric test.

Summary of Contents for B224RB

Page 1: ... or without plaster ring Min Depth 1 5 inches 13 mm 4 inch octagon box Min depth 1 5 inches 13 mm 31 2 inch octagon box Min depth 1 5 inches 13 mm Operating Temperature Range 0 to 49 C 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity Non condensing Electrical Ratings Operating Voltage 15 to 28 VDC Time Averaged Standby Ratings 500 µA 24 VDC Relay Characteristics Coil 2 coil latching...

Page 2: ...n state when the base is shipped from the factory the contacts may have closed during shipment Connecting an auxiliary control circuit to closed relay con tacts can cause an unexpected and possibly dangerous ac tivation of that circuit Therefore do NOT connect an auxiliary control circuit to the relay contacts terminals 1 2 and 3 before ensuring that the relay contacts are in their open state Ensu...

Page 3: ...the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that pre vents its removal from the base without the use of a tool To activate this feature break the tab from the detector base as shown in Figure 3A see page 4 Then install the detector To remove the detector from the base once the tamper re sist feature has been activated insert a sma...

Page 4: ...detecting a smoldering fire with either an ionization type detector or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may not reach the smoke detector and alarm it A detector cannot detect a fire de...

Reviews: