Gamewell-FCI
S3 Series
All Revisions
Honeywell
XLS120
Rev. 21 or Higher
Honeywell
XLS140-2
Rev. 21 or Higher
Honeywell
XLS3000
Rev. 21 or Higher
Silent Knight
5820XL, 5820XL-EVS
Rev. 13 or Higher
Silent Knight
5808
Rev. 13 or Higher
Silent Knight
5700
Rev. 13 or Higher
Silent Knight
IFP-2000, IFP-2000ECS
Rev. 4 or Higher
Silent Knight
IFP-1000, IFP-1000ECS
Rev. 13 or Higher
Silent Knight
IFP-100, IFP-100ECS
Rev. 13 or Higher
Silent Knight
IFP-50
Rev. 13 or Higher
Johnson Controls
IFS-320
Rev. 21 or Higher
Johnson Controls
IFC2-640
Rev. 21 or Higher
Johnson Controls
IFC2-3030
Rev. 21 or Higher
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction and must not be of such length or wire
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and
accessory devices should be color coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm
2
) may be used with the base. The sounder
base will be shipped with the screw terminals set for 14 AWG wiring. If 12
AWG wire is to be used, back out the screws to allow the wire to fit beneath
the clamping plates.For best system performance, the power (+ and -) wires
and the communication circuit wires should be twisted pair or shielded cable
installed in a separate grounded conduit to protect the communication loop
from electrical interference.
MOUNTING
Mount the B200S-LF mounting plate directly to an electrical box. The plate
will mount directly to 4˝ square (with and without plaster ring), 4 inch octa-
gon, 3
1
/
2
inch octagon, single gang or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove
on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the
product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual
for the sensor.
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool. To activate this feature, break the tab
from the detector base as shown in Figure 7A. Then, install the detector. To
remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 7B). This allows the detector to be rotated
counterclockwise for removal. The tamper-resist feature can be defeated by
breaking and removing the plastic lever from the base. However, this prevents
the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a
periodic maintenance program. Test the B200S-LF as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor
system is undergoing maintenance and, therefore, will be temporarily out of
service. Disable the system undergoing maintenance to prevent unwanted
alarms.
1. Via the fire alarm control panel, command the individual B200S-LF to acti-
vate using the associated sensor address. That sounder base should sound
in approximately five seconds.
2. Via the fire alarm control panel, command all B200S-LF low frequency
sounder bases to activate using group communication to all associated ad-
dresses. All devices on the loop should sound, and if a temporal tone is
commanded, the tones can be synchronized to each other.
NOTE: Synchronization requires a power supply capable of producing the Sys-
tem Sensor synchronization pulses or a synchronization module.
When performing maintenance on connected smoke sensors, carefully note
the location and address of each removed sensor. When re-installed, the
B200S-LF will confirm that address of the sensor matches the address stored
in the sounder base memory. If there is a mismatch, this will be communi-
cated to the fire alarm control panel and the sounder base can be commanded
to chirp at regular intervals until the correct head is installed.
If a replacement head is installed or address changes are required, the mis-
match may be resolved at the panel by commanding the B200S-LF low fre-
quency sounder base to re-enter its address learning mode and adopting the
address of the new sensor.
FIGURE 2:
C0471-08
C0473-00
C0891-09
FIGURE 1:
1
2
3
4
5
6
Make wire connections by stripping about
3
/
8
inch of insulation from the end
of the wire. Then, slide the bare end of the wire under the appropriate clamp-
ing plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop
the wire under the clamping plate (See Figure 2) The wiring diagram for a
typical 2-wire intelligent system is shown in Figure 4.
CAUTION
For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire under
terminals. Break wire run as shown in Figure 2 to provide monitoring of connections.
B200S-LF TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Remote Annunciator
FIGURE 3: MOUNTING
2
I56-4151-003R
06-10